General information | | | |
Product type designation | CPU 414-2 | CPU 414-3 | CPU 414-3 PN/DP |
HW functional status | 01 | 01 | 01 |
Firmware version | V7.0 | V7.0 | V7.0 |
Engineering with | | | |
| STEP 7 V5.4 or higher with HSP 261 | STEP 7 V5.4 or higher with HSP 261 | STEP 7 V5.5 or higher with HSP 262 |
CiR Configuration in RUN | | | |
CiR synchronization time, basic load | 100ms | 100ms | 100ms |
CiR synchronization time, time per I/O byte | 15s | 15s | 15s |
Supply voltage | | | |
Rated value (DC) | | | |
| No; Power supply via system power supply | No; Power supply via system power supply | No; Power supply via system power supply |
Input current | | | |
from backplane bus 5 V DC, typ. | 0.9A | 1.1A | 1.3A |
from backplane bus 5 V DC, max. | 1.1A | 1.3A | 1.6A |
from backplane bus 24 V DC, max. | 300mA; 150 mA per DP interface | 450mA; 150 mA per DP interface | 300mA; 150 mA per DP interface |
from interface 5 V DC, max. | 90mA; At each DP interface | 90mA; At each DP interface | 90mA; At each DP interface |
Power loss | | | |
Power loss, typ. | 4.5W | 5.5W | 6.5W |
Power loss, max. | 5.5W | 6.5W | 8W |
Memory | | | |
Type of memory | RAM | RAM | RAM |
Work memory | | | |
| 2Mbyte | 4Mbyte | 4Mbyte |
| 1Mbyte | 2Mbyte | 2Mbyte |
| 1Mbyte | 2Mbyte | 2Mbyte |
| No | No | No |
Load memory | | | |
| Yes; with Memory Card (FLASH) | Yes; with Memory Card (FLASH) | Yes; with Memory Card (FLASH) |
| 64Mbyte | 64Mbyte | 64Mbyte |
| 512kbyte | 512kbyte | 512kbyte |
| Yes; with Memory Card (RAM) | Yes; with Memory Card (RAM) | Yes; with Memory Card (RAM) |
| 64Mbyte | 64Mbyte | 64Mbyte |
Backup | | | |
| Yes | Yes | Yes |
| Yes; all data | Yes; all data | Yes; all data |
| No | No | No |
Battery | | | |
Backup battery | | | |
| 180A; up to 40 C | 180A | 180A; up to 40 C |
| 850A | 850A | 850A |
| Dealt with in the module data manual with the secondary conditions and the factors of influence | Dealt with in the module data manual with the secondary conditions and the factors of influence | Dealt with in the module data manual with the secondary conditions and the factors of influence |
| 5 V DC to 15 V DC | 5 V DC to 15 V DC | 5 V DC to 15 V DC |
CPU processing times | | | |
for bit operations, typ. | 18.75ns | 18.75ns | 18.75ns |
for word operations, typ. | 18.75ns | 18.75ns | 18.75ns |
for fixed point arithmetic, typ. | 18.75ns | 18.75ns | 18.75ns |
for floating point arithmetic, typ. | 37.5ns | 37.5ns | 37.5ns |
CPU-blocks | | | |
DB | | | |
| 6000; Number range: 1 to 16000 | 6000; Number range: 1 to 16000 | 6000; Number range: 1 to 16000 |
| 64kbyte | 64kbyte | 64kbyte |
FB | | | |
| 3000; Number range: 0 to 7999 | 3000; Number range: 0 to 7999 | 3000; Number range: 0 to 7999 |
| 64kbyte | 64kbyte | 64kbyte |
FC | | | |
| 3000; Number range: 0 to 7999 | 3000; Number range: 0 to 7999 | 3000; Number range: 0 to 7999 |
| 64kbyte | 64kbyte | 64kbyte |
OB | | | |
| see instruction list | see instruction list | see instruction list |
| 64kbyte | 64kbyte | 64kbyte |
| 1; OB 1 | 1; OB 1 | 1; OB 1 |
| 4; OB 10-13 | 4; OB 10-13 | 4; OB 10-13 |
| 4; OB 20-23 | 4; OB 20-23 | 4; OB 20-23 |
| 4; OB 32-35 (shortest cycle that can be set = 500 s) | 4; OB 32-35 (shortest cycle that can be set = 500 s) | 4; OB 32, 33, 34, 35 (shortest cycle that can be set = 500 s) |
| 4; OB 40-43 | 4; OB 40-43 | 4; OB 40-43 |
| 3; OB 55-57 | 3; OB 55-57 | 3; OB 55-57 |
| 3; OB 61-63 | 3; OB 61-63 | 3; OB 61-63 |
| 1; OB 60 | 1; OB 60 | 1; OB 60 |
| 1; OB 90 | 1; OB 90 | 1; OB 90 |
| 3; OB 100-102 | 3; OB 100-102 | 3; OB 100-102 |
| 9; OB 80-88 | 9; OB 80-88 | 9; OB 80-88 |
| 2; OB 121, 122 | 2; OB 121, 122 | 2; OB 121, 122 |
Nesting depth | | | |
| 24 | 24 | 24 |
| 1 | 1 | 1 |
Counters, timers and their retentivity | | | |
S7 counter | | | |
| 2048 | 2048 | 2048 |
Retentivity | | | |
| Yes | Yes | Yes |
| 0 | 0 | 0 |
| 2047 | 2047 | 2047 |
| Z 0 to Z 7 | Z 0 to Z 7 | Z 0 to Z 7 |
Counting range | | | |
| 0 | 0 | 0 |
| 999 | 999 | 999 |
IEC counter | | | |
| Unlimited (limited only by RAM capacity) | Unlimited (limited only by RAM capacity) | Unlimited (limited only by RAM capacity) |
S7 times | | | |
| 2048 | 2048 | 2048 |
Retentivity | | | |
| Yes | Yes | Yes |
| 0 | 0 | 0 |
| 2047 | 2047 | 2047 |
| No times retentive | No times retentive | No times retentive |
Time range | | | |
| 10ms | 10ms | 10ms |
| 9990s | 9990s | 9990s |
IEC timer | | | |
| Yes | Yes | Yes |
| SFB | SFB | SFB |
| Unlimited (limited only by RAM capacity) | Unlimited (limited only by RAM capacity) | Unlimited (limited only by RAM capacity) |
Data areas and their retentivity | | | |
retentive data area in total | Total working and load memory (with backup battery) | Total working and load memory (with backup battery) | Total working and load memory (with backup battery) |
Flag | | | |
| 8kbyte; Size of bit memory address area | 8kbyte; Size of bit memory address area | 8kbyte; Size of bit memory address area |
| Yes | Yes | Yes |
| MB 0 to MB 15 | MB 0 to MB 15 | MB 0 to MB 15 |
| 8; in 1 memory byte | 8; in 1 memory byte | 8; in 1 memory byte |
Data blocks | | | |
| 6000; Number range: 1 to 16000 | 6000; Number range: 1 to 16000 | 6000; Number range: 1 to 16000 |
| 64kbyte | 64kbyte | 64kbyte |
Local data | | | |
| 16kbyte | 16kbyte | 16kbyte |
| 8kbyte | 8kbyte | 8kbyte |
Address area | | | |
I/O address area | | | |
| 8kbyte | 8kbyte | 8kbyte |
| 8kbyte | 8kbyte | 8kbyte |
of which distributed | | | |
| 2kbyte | 2kbyte | 2kbyte |
| 2kbyte | 2kbyte | 2kbyte |
| 6kbyte | 6kbyte | 6kbyte |
| 6kbyte | 6kbyte | 6kbyte |
| | | 8kbyte |
| | | 8kbyte |
Process image | | | |
| 8kbyte | 8kbyte | 8kbyte |
| 8kbyte | 8kbyte | 8kbyte |
| 256byte | 256byte | 256byte |
| 256byte | 256byte | 256byte |
| 244byte | 244byte | 244byte |
| Yes | Yes | Yes |
Subprocess images | | | |
| 15 | 15 | 15 |
Digital channels | | | |
| 65536 | 65536 | 65536 |
| 65536 | 65536 | 65536 |
| 65536 | 65536 | 65536 |
| 65536 | 65536 | 65536 |
| 65536; Inputs and outputs in each case | 65536; Inputs and outputs in each case | 65536; Inputs and outputs in each case |
Analog channels | | | |
| 4096 | 4096 | 4096 |
| 4096 | 4096 | 4096 |
| 4096 | 4096 | 4096 |
| 4096 | 4096 | 4096 |
| 4096; Inputs and outputs in each case | 4096; Inputs and outputs in each case | 4096; Inputs and outputs in each case |
Hardware configuration | | | |
Number of expansion units, max. | 21 | 21 | 21 |
connectable OPs | 63 | 63 | 63 |
Multicomputing | Yes; 4 CPUs max. (with UR1 or UR2) | Yes; 4 CPUs max. (with UR1 or UR2) | Yes; 4 CPUs max. (with UR1 or UR2) |
Interface modules | | | |
| 6 | 6 | 6 |
| 6 | 6 | 6 |
| 4; IM 463-2 | 4; IM 463-2 | 4; IM 463-2 |
Number of DP masters | | | |
| 2 | 2 | 1 |
| 10; CP 443-5 Extended | 10; CP 443-5 Extended | 10; CP 443-5 Extended |
| 4 | 4 | 4 |
| No; IM 467 cannot be used jointly with CP 443-5 Ext. or CP 443-1 in PROFINET IO mode | No; IM 467 cannot be used jointly with CP 443-5 Ext. or CP 443-1 in PROFINET IO mode | No; IM 467 cannot be used jointly with CP 443-5 Ext. or CP 443-1 in PROFINET IO mode |
| 0 | 1 | 1; IF 964-DP |
| 6 | 6 | 6 |
Number of IO Controllers | | | |
| 0 | 0 | 1 |
| 4; Max. 4 in the central controller; no mixed operation of different CP 443-1 types in PROFINET IO mode | 4; Max. 4 in the central controller; no mixed operation of different CP 443-1 types in PROFINET IO mode | 4; Max. 4 in the central controller; no mixed operation of different CP 443-1 types in PROFINET IO mode |
Number of operable FMs and CPs (recommended) | | | |
| Limited by number of slots and number of connections | Limited by number of slots and number of connections | Limited by number of slots and number of connections |
| CP 440: Limited by number of slots; CP 441: limited by number of connections | CP 440: Limited by number of slots; CP 441: limited by number of connections | CP 440: Limited by number of slots; CP 441: Limited by number of slots and number of connections |
| 14; In total max. 10 CPs as DP master and PROFINET controller, of which up to 10 IMs or CPs as DP master and up to 4 CPs as PROFINET controller | 14; In total max. 10 CPs as DP master and PROFINET controller, of which up to 10 IMs or CPs as DP master and up to 4 CPs as PROFINET controller | 14; In total max. 10 CPs as DP master and PROFINET controller, of which up to 10 IMs or CPs as DP master and up to 4 CPs as PROFINET controller |
Slots | | | |
| 1 | 2 | 2 |
Time of day | | | |
Clock | | | |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| 1ms | 1ms | 1ms |
| 1.7s; Power off | 1.7s; Power off | 1.7s; Power off |
| 8.6s; For power On | 8.6s; For power On | 8.6s; For power On |
Operating hours counter | | | |
| 16 | 16 | 16 |
| 0 to 15 | 0 to 15 | 0 to 15 |
| SFCs 2, 3 and 4: 0 to 32767 hours SFC 101: 0 to 2^31 - 1 hours | SFCs 2, 3 and 4: 0 to 32767 hours SFC 101: 0 to 2^31 - 1 hours | SFCs 2, 3 and 4: 0 to 32767 hours SFC 101: 0 to 2^31 - 1 hours |
| 1 hour | 1 hour | 1 hour |
| Yes | Yes | Yes |
Clock synchronization | | | |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| No; Via CP | No; Via CP | Yes; As client |
| No | Yes | Yes |
Time difference in system when synchronizing via | | | |
| | | 10ms |
| 200ms | 200ms | 200ms |
Interfaces | | | |
Interfaces/bus type | 1 x MPI/PROFIBUS DP, 1 x PROFIBUS DP | 1 x MPI/PROFIBUS DP, 1 x PROFIBUS DP, 1 x PROFIBUS DP (optionally pluggable) | 1 x MPI/PROFIBUS DP, 1 x PROFINET (2 ports), 1 x PROFIBUS DP (optionally pluggable) |
Number of RS 485 interfaces | 2; Combined MPI / PROFIBUS DP and PROFIBUS DP | 2; Combined MPI / PROFIBUS DP and PROFIBUS DP | 1; Combined MPI / PROFIBUS DP |
Number of other interfaces | | 1; PROFIBUS DP with IF 964-DP (plug-in option; MLFB: 6ES7964-2AA04-0AB0) | 1; PROFIBUS DP with IF 964-DP (plug-in option; MLFB: 6ES7964-2AA04-0AB0) |
1. Interface | | | |
Interface type | Integrated | Integrated | Integrated |
Physics | RS 485 / PROFIBUS + MPI | RS 485 / PROFIBUS + MPI | RS 485 / PROFIBUS + MPI |
Isolated | Yes | Yes | Yes |
Power supply to interface (15 to 30 V DC), max. | 150mA | 150mA | 150mA |
Number of connection resources | MPI: 32, DP: 16 | MPI: 32, DP: 16 | MPI: 32, DP: 16 |
Functionality | | | |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
MPI | | | |
| 32; If a diagnostics repeater is used on the line, the number of connection resources on the line is reduced by 1 | 32; If a diagnostics repeater is used on the line, the number of connection resources on the line is reduced by 1 | 32; If a diagnostics repeater is used on the line, the number of connection resources on the line is reduced by 1 |
| 12Mbit/s | 12Mbit/s | 12Mbit/s |
Services | | | |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
DP master | | | |
| 16; If a diagnostics repeater is used on the line, the number of connection resources on the line is reduced by 1 | 16; If a diagnostics repeater is used on the line, the number of connection resources on the line is reduced by 1 | 16; If a diagnostics repeater is used on the line, the number of connection resources on the line is reduced by 1 |
| 12Mbit/s | 12Mbit/s | 12Mbit/s |
| 32 | 32 | 32 |
Services | | | |
| Yes | Yes | Yes |
| Yes; S7 routing | Yes; S7 routing | Yes; S7 routing |
| No | No | No |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
Address area | | | |
| 2kbyte | 2kbyte | 2kbyte |
| 2kbyte | 2kbyte | 2kbyte |
User data per DP slave | | | |
| 244byte | 244byte | 244byte |
| 244byte | 244byte | 244byte |
| 244byte | 244byte | 244byte |
| 244 | 244 | 244 |
| 128byte | 128byte | 128byte |
DP slave | | | |
| 16 | 16 | 16 |
| http://support.automation.siemens.com/WW/view/en/113652 | http://support.automation.siemens.com/WW/view/en/113652 | http://support.automation.siemens.com/WW/view/en/113652 |
| 12Mbit/s | 12Mbit/s | 12Mbit/s |
| No | No | No |
| 32; Virtual slots | 32; Virtual slots | 32; Virtual slots |
| 32byte | 32byte | 32byte |
| 32byte | 32byte | 32byte |
Services | | | |
| Yes; with interface active | Yes; with interface active | Yes; with interface active |
| Yes; with interface active | Yes; with interface active | Yes; with interface active |
| No | No | No |
| No | No | No |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| No | No | No |
| No | No | No |
Transfer memory | | | |
| 244byte | 244byte | 244byte |
| 244byte | 244byte | 244byte |
2. Interface | | | |
Interface type | Integrated | Integrated | PROFINET |
Physics | RS 485 / PROFIBUS | RS 485 / PROFIBUS | Ethernet RJ45 |
Isolated | Yes | Yes | Yes |
Power supply to interface (15 to 30 V DC), max. | 150mA | 150mA | |
automatic detection of transmission rate | | | Yes; Autosensing |
Autonegotiation | | | Yes |
Autocrossing | | | Yes |
Change of IP address at runtime, supported | | | Yes; Assignment by higher-level IO-Controller or by the user program with SFB104 "IP_CONF" |
Number of connection resources | 16 | 16 | 64 |
Interface types | | | |
| | | 2 |
| | | Yes |
Media redundancy | | | |
| | | Yes |
| | | 200ms |
| | | 50 |
Functionality | | | |
| | | Yes |
| | | Yes |
| | | Yes |
| Yes | Yes | No |
| Yes | Yes | No |
| | | Yes |
| | | Yes |
| | | 5 |
| | | No |
DP master | | | |
| 16 | 16 | |
| 12Mbit/s | 12Mbit/s | |
| 96 | 96 | |
Services | | | |
| Yes | Yes | |
| Yes; S7 routing | Yes; S7 routing | |
| No | No | |
| Yes | Yes | |
| Yes | Yes | |
| Yes | Yes | |
| Yes | Yes | |
| Yes | Yes | |
| Yes | Yes | |
| Yes | Yes | |
| Yes | Yes | |
| Yes | Yes | |
| Yes | Yes | |
Address area | | | |
| 6kbyte | 6kbyte | |
| 6kbyte | 6kbyte | |
User data per DP slave | | | |
| 244byte | 244byte | |
| 244byte | 244byte | |
| 244byte | 244byte | |
| 244 | 244 | |
| 128byte | 128byte | |
DP slave | | | |
| 16 | 16 | |
| http://support.automation.siemens.com/WW/view/en/113652 | http://support.automation.siemens.com/WW/view/en/113652 | |
| 12Mbit/s | 12Mbit/s | |
| 32 | 32 | |
| 32byte | 32byte | |
| 32byte | 32byte | |
Services | | | |
| Yes; with interface active | Yes; with interface active | |
Transfer memory | | | |
| 244byte | 244byte | |
| 244byte | 244byte | |
PROFINET IO Controller | | | |
| | | 100Mbit/s |
Services | | | |
| | | Yes |
| | | Yes |
| | | Yes |
| | | Yes; Only with IRT and the High Performance option |
| | | Yes |
| | | Yes |
| | | Yes |
| | | 32 |
| | | 256 |
| | | 64 |
| | | 64 |
| | | 256 |
| | | 61 |
| | | 256 |
| | | 256 |
| | | Yes |
| | | 8 |
| | | Yes |
| | | 8; 8 parallel calls of the SFC 12 "D_ACT_DP" possible per line. Max. 32 IO Devices changing during operation (partner ports) are supported |
| | | Yes |
| | | 250 μs, 500 μs, 1 ms, 2 ms, 4 ms additionally with IRT with high performance: 250 s to 4 ms in 125 s frame |
| | | 250 s to 512 ms; minimum value depends on preset communication share for PROFINET IO, on the number of IO Devices and on the amount of configured user data, see PROFINET system description |
Address area | | | |
| | | 8kbyte |
| | | 8kbyte |
| | | 1024byte |
PROFINET IO Device | | | |
Services | | | |
| | | Yes |
| | | Yes |
| | | Yes |
| | | No |
| | | Yes |
| | | Yes |
| | | Yes |
| | | Yes |
| | | 2 |
Transfer memory | | | |
| | | 1440byte; Per IO Controller with shared device |
| | | 1440byte; Per IO Controller with shared device |
Submodules | | | |
| | | 64 |
| | | 1024byte |
PROFINET CBA | | | |
| | | Yes |
| | | Yes |
Open IE communication | | | |
| | | 62 |
| | | 0, 20, 21, 25, 80, 102, 135, 161, 34962, 34963, 34964, 65532, 65533, 65534, 65535 |
| | | Yes |
3. Interface | | | |
Interface type | | Pluggable interface module (IF), technical data as for 2nd interface | Pluggable interface module (IF) |
Plug-in interface modules | | IF 964-DP (MLFB: 6ES7964-2AA04-0AB0) | IF 964-DP (MLFB: 6ES7964-2AA04-0AB0) |
Physics | | RS 485 / PROFIBUS | RS 485 / PROFIBUS |
Isolated | | Yes | Yes |
Power supply to interface (15 to 30 V DC), max. | | 150mA | 150mA |
automatic detection of transmission rate | | No | No |
Number of connection resources | | 16 | 16 |
Functionality | | | |
| | No | No |
| | Yes | Yes |
| | Yes | Yes |
DP master | | | |
| | 16 | 16 |
| | 96 | 96 |
Services | | | |
| | Yes | Yes |
| | Yes; S7 routing | Yes; S7 routing |
| | No | No |
| | Yes | Yes |
| | Yes | Yes |
| | Yes | Yes |
| | Yes | Yes |
| | Yes | Yes |
| | Yes | Yes |
| | Yes | Yes |
| | Yes | Yes |
| | Yes | Yes |
| | Yes | Yes |
| | Yes | Yes |
Address area | | | |
| | 6kbyte | 6kbyte |
| | 6kbyte | 6kbyte |
User data per DP slave | | | |
| | 244byte | 244byte |
| | 244byte | 244byte |
| | 244byte | 244byte |
| | 244 | 244 |
| | 128byte | 128byte |
DP slave | | | |
| | 16 | 16 |
| | http://support.automation.siemens.com/WW/view/en/113652 | http://support.automation.siemens.com/WW/view/en/113652 |
| | 12Mbit/s | 12Mbit/s |
| | No | No |
| | 32 | 32; Virtual slots |
| | 32byte | 32byte |
| | 32byte | 32byte |
Services | | | |
| | Yes | Yes |
| | Yes; with interface active | Yes; with interface active |
| | No | No |
| | No | No |
| | Yes | Yes |
| | Yes | Yes |
| | Yes | Yes |
| | No | No |
| | No | No |
Transfer memory | | | |
| | 244byte | 244byte |
| | 244byte | 244byte |
Open IE communication | | | |
| | | Yes; via integrated PROFINET interface and loadable FBs |
| | | 32kbyte |
| | | Yes |
| Via CP 443-1 and loadable FB | Via CP 443-1 and loadable FB | Yes; Via integrated PROFINET interface or CP 443-1 Adv. and loadable FBs |
| 1452 bytes via CP 443-1 Adv. | 1452 bytes via CP 443-1 Adv. | 32kbyte; 1452 bytes via CP 443-1 Adv. |
| | | Yes; via integrated PROFINET interface and loadable FBs |
| | | 1472byte |
Web server | | | |
| | | Yes |
| | | 5 |
Isochronous mode | | | |
Isochronous operation (application synchronized up to terminal) | Yes; For PROFIBUS only | Yes; For PROFIBUS only | Yes; Via PROFIBUS DP or PROFINET interface |
Equidistance | Yes | Yes | Yes |
Number of DP masters with isochronous mode | 2 | 3 | 2 |
User data per isochronous slave, max. | 244byte | 244byte | 244byte |
shortest clock pulse | 1ms; 0.5 ms without use of SFC 126, 127 | 1ms; 0.5 ms without use of SFC 126, 127 | 1ms; 0.5 ms without use of SFC 126, 127 |
max. cycle | 32ms | 32ms | 32ms |
Communication functions | | | |
PG/OP communication | Yes | Yes | Yes |
| 63 | 63 | 63 |
| 63; When using Alarm_S/SQ and Alarm_D/DQ | 63; When using Alarm_S/SQ and Alarm_D/DQ | 63; When using Alarm_S/SQ and Alarm_D/DQ |
Data record routing | Yes | Yes | Yes |
Global data communication | | | |
| Yes | Yes | Yes |
| 8 | 8 | 8 |
| 8 | 8 | 8 |
| 16 | 16 | 16 |
| 54byte | 54byte | 54byte |
| 1 variable | 1 variable | 1 variable |
S7 basic communication | | | |
| Yes | Yes | Yes |
| 76byte | 76byte | 76byte |
| 1 variable | 1 variable | 1 variable |
S7 communication | | | |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| 64kbyte | 64kbyte | 64kbyte |
| 462byte; 1 variable | 462byte; 1 variable | 462byte; 1 variable |
S5 compatible communication | | | |
| Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5 | Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5 | Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5 |
| 8kbyte | 8kbyte | 8kbyte |
| 240byte | 240byte | 240byte |
| 24/24 | 24/24 | 24/24 |
Standard communication (FMS) | | | |
| Yes; Via CP and loadable FB | Yes; Via CP and loadable FB | Yes; Via CP and loadable FB |
Web server | | | |
| No | No | Yes |
PROFINET CBA (at set setpoint communication load) | | | |
| | | 20% |
| | | 32 |
| | | 150 |
| | | 4500 |
| | | 45000byte |
| | | 45000byte |
| | | 1000 |
| | | 16000byte |
| | | 2000byte |
Remote interconnections with acyclic transmission | | | |
| | | 200ms; Depending on preset communication load, number of interconnections and data length used |
| | | 250 |
| | | 250 |
| | | 8000byte |
| | | 8000byte |
| | | 2000byte |
Remote interconnections with cyclic transmission | | | |
| | | 1ms; Depending on preset communication load, number of interconnections and data length used |
| | | 300 |
| | | 300 |
| | | 4800byte |
| | | 4800byte |
| | | 450byte |
HMI variables via PROFINET (acyclic) | | | |
| | | 2x PN OPC/1x iMap |
| | | 500ms |
| | | 1000 |
| | | 32000byte |
PROFIBUS proxy functionality | | | |
| | | Yes; 32 PROFIBUS slaves max. connectable |
| | | 240byte; Slave-dependent |
Number of connections | | | |
| 64 | 64 | 64 |
| 63 | 63 | 63 |
| 1 | 1 | 1 |
| 0 | 0 | 0 |
| 63 | 63 | 63 |
| 1 | 1 | 1 |
| 0 | 0 | 0 |
| 62 | 62 | 62 |
| 0 | 0 | 0 |
| 0 | 0 | 0 |
| 62 | 62 | 62 |
| 0 | 0 | 0 |
| 0 | 0 | 0 |
| 31 | 31 | 31 |
| 0 | 0 | 0 |
| 0 | 0 | 0 |
S7 message functions | | | |
Number of login stations for message functions, max. | 63; Max. 63 with Alarm_S/SQ and Alarm_D/DQ (OPs); max. 8 with Alarm, Alarm_8, Alarm_8P, Notify and Notify_8 (e.g. WinCC) | 63; Max. 63 with Alarm_S/SQ and Alarm_D/DQ (OPs); max. 8 with Alarm, Alarm_8, Alarm_8P, Notify and Notify_8 (e.g. WinCC) | 63; Max. 63 with Alarm_S/SQ and Alarm_D/DQ (OPs); max. 8 with Alarm, Alarm_8, Alarm_8P, Notify and Notify_8 (e.g. WinCC) |
Symbol-related messages | Yes | Yes | Yes |
SCAN procedure | Yes | Yes | Yes |
Program alarms | Yes | Yes | Yes |
Process diagnostic messages | Yes | Yes | Yes |
simultaneously active Alarm-S blocks, max. | 400; Simultaneously active alarm_S/SQ blocks or alarm_D/DQ blocks | 400; Simultaneously active alarm_S/SQ blocks or alarm_D/DQ blocks | 400; Simultaneously active alarm_S/SQ blocks or alarm_D/DQ blocks |
Alarm 8-blocks | Yes | Yes | Yes |
| 1200 | 1200 | 1200 |
| 300 | 300 | 300 |
Process control messages | Yes | Yes | Yes |
Number of archives that can log on simultaneously (SFB 37 AR_SEND) | 16 | 16 | 16 |
Number of messages | | | |
| 512 | 512 | 512 |
| 128 | 128 | 128 |
| 256 | 256 | 256 |
| 512 | 512 | 512 |
Number of additional values | | | |
| 1 | 1 | 1 |
| 10 | 10 | 10 |
Test commissioning functions | | | |
Status block | Yes; Up to 16 simultaneously | Yes; Up to 16 simultaneously | Yes; Up to 16 simultaneously |
Single step | Yes | Yes | Yes |
Number of breakpoints | 16 | 16 | 16 |
Status/control | | | |
| Yes; Up to 16 variable tables | Yes; Up to 16 variable tables | Yes; Up to 16 variable tables |
| Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters | Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters | Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters |
| 70; Status/control | 70; Status/control | 70; Status/control |
Forcing | | | |
| Yes | Yes | Yes |
| Inputs, outputs, bit memories, peripheral inputs, peripheral outputs | Inputs, outputs, bit memories, peripheral inputs, peripheral outputs | Inputs/outputs, bit memories, distributed I/Os |
| 256 | 256 | 256 |
Diagnostic buffer | | | |
| Yes | Yes | Yes |
| 3200 | 3200 | 3200 |
| Yes | Yes | Yes |
| 120 | 120 | 120 |
Service data | | | |
| Yes | Yes | Yes |
Standards, approvals, certificates | | | |
CE mark | Yes | Yes | Yes |
CSA approval | Yes | Yes | Yes |
UL approval | Yes | Yes | Yes |
cULus | Yes | Yes | Yes |
FM approval | Yes | Yes | Yes |
RCM (formerly C-TICK) | Yes | Yes | Yes |
KC approval | Yes | Yes | Yes |
EAC (formerly Gost-R) | Yes | Yes | Yes |
Use in hazardous areas | | | |
| ATEX II 3G Ex nA IIC T4 Gc | ATEX II 3G Ex nA IIC T4 Gc | ATEX II 3G Ex nA IIC T4 Gc |
Ambient conditions | | | |
Ambient temperature during operation | | | |
| 0C | 0C | 0C |
| 60C | 60C | 60C |
Configuration | | | |
Configuration software | | | |
| Yes | Yes | Yes |
Programming | | | |
| see instruction list | see instruction list | see instruction list |
| 7 | 7 | 7 |
| Yes | Yes | Yes |
| see instruction list | see instruction list | see instruction list |
| see instruction list | see instruction list | see instruction list |
Programming language | | | |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
Number of simultaneously active SFCs | | | |
| 2; SFC 11; per interface | 2; SFC 11; per interface | 2; SFC 11; per interface |
| 8; SFC 12; per interface | 8; SFC 12; per interface | 8; SFC 12; per interface |
| 8; SFC 59; per interface | 8; SFC 59; per interface | 8; SFC 59; per interface |
| 8; SFC 58; per interface | 8; SFC 58; per interface | 8; SFC 58; per interface |
| 8; SFC 55; per interface | 8; SFC 55; per interface | 8; SFC 55; per interface |
| 1; SFC 57; per interface | 1; SFC 57; per interface | 1; SFC 57; per interface |
| 2; SFC 56; per interface | 2; SFC 56; per interface | 2; SFC 56; per interface |
| 8; SFC 13; per interface | 8; SFC 13; per interface | 8; SFC 13; per interface |
| 8; SFC 51 | 8; SFC 51 | 8; SFC 51 |
| 1; SFC 103; per interface | 1; SFC 103; per interface | 1; SFC 103; per interface |
Number of simultaneously active SFBs | | | |
| 8; SFB 52; per interface, but not more than 32 across all external interfaces | 8; SFB 52; per interface, but not more than 32 across all external interfaces | 8; SFB 52; per interface, but not more than 32 across all external interfaces |
| 8; SFB 53; per interface, but not more than 32 across all external interfaces | 8; SFB 53; per interface, but not more than 32 across all external interfaces | 8; SFB 53; per interface, but not more than 32 across all external interfaces |
Know-how protection | | | |
| Yes | Yes | Yes |
| Yes; With S7 block Privacy | Yes; With S7 block Privacy | Yes; With S7 block Privacy |
Dimensions | | | |
Width | 25mm | 50mm | 50mm |
Height | 290mm | 290mm | 290mm |
Depth | 219mm | 219mm | 219mm |
Weights | | | |
Weight, approx. | 700g | 900g | 900g |