SIPART DR22 controller |
|---|
General | | Mounting position | Any | Climatic classes | | - Storage: 1K2 according to
DIN IEC 721 Part 3-1
| -25 to +75 °C
| - Transport: 2K2 according to
DIN IEC 721 Part 3-2
| -25 to +75 °C
| - Operation: 3K3 according to
DIN IEC 721 Part 3-3
| 0 to +50 °C
| Degree of protection to EN 60 529 | | | IP64 | | IP30 | | IP20 | Controller design Electrical safety - to DIN EN 61 010 Part 1
- Protection class I
- Safe separation between supply connection and field signals
- Clearances and creepage paths for surge class III and pollution level 2, unless stated otherwise
EC Certificate of Conformity no. 691.001 CE marking: conformity concerning EMC Guideline 89/336/EWG and NS Guideline 73/23/EWG. Emitted interference, immunity to interference to EN 61 326, NAMUR NE21 8/98 | Weight (basic unit without options) | Approx. 1.2 kg
| Dimensions | | Color | | | RAL 7037 | | RAL 7035 | Material | | | Polycarbonate, glass-fiber reinforced | | Polyester | Power supply connection | | | 3-pin earthed plug IEC 320/V | | Special 2-pin plug | Connections for process signals | Multiple screw terminal blocks, cannot be confused when connecting, for conductor cross- section 1.5 mm2 (AWG 14) | Protective earth connection | Earthing screw | A rail can be mounted on the rear panel of the power supply. The rail is included in the delivery of the coupling relay module. |
Power supply |
|---|
Rated voltage | Selectable | | | | 230 V AC | 115 V AC | 24 V AC/DC | Operating voltage range | 187 to 276 V AC | 93 to 138 V AC | 20 to 28 V AC | 20 to 35 V DC 1) | Frequency range | 48 to 63 Hz
| –
| Peak voltages, non periodic, to VDE 160 | | | | 1.3 ms | ≤ 780 V | ≤ 390 V | ≤ 70 V | 10 μs | ≤ 1500 V | ≤ 1500 V | ≤ 500 V | External current IExt2) | 450 mA
| Power consumption Active power/ apparent power 3) Basic unit | | | | | - Without
options, without IExt
|
8 W/17 VA
|
8 W/13 VA
|
8 W/11 VA
|
8 W
| - With options,
without IExt
| 13 W/25 VA
| 13 W/20 VA
| 13 W/18 VA
| 13 W
| | 26 W/45 VA
| 26 W/36 VA
| 28 W/35 VA
| 28 W
| Permissible voltage dips 4) Basic unit | | | | | - Without
options, without IExt
|
≤ 90 ms
|
≤ 70 ms
|
≤ 55 ms
|
≤ 30 ms
| - With options,
without IExt
| ≤ 80 ms
| ≤ 60 ms
| ≤ 50 ms
| ≤ 25 ms
| | ≤ 50 ms
| ≤ 35 ms
| ≤ 35 ms
| ≤ 20 ms
| Test voltages (1 min) | | | | 1.5 kV AC
| 500 V AC
| - Primary -
protective conductor
|
1.5 kV AC
|
500 V AC
| - Secondary -
protective conductor
|
700 V DC
|
700 V DC
|
Including harmonics. Consisting of L+, BA and AA. Capacitive. The load voltage of the analog outputs is reduced to 13 V, L+ to +15 V and the voltage at the digital outputs drops to +14 V. Inputs and outputs, display technology |
|---|
Analog inputs AE1, AE2, AE3 and AE6 to AE11 (input module 6DR2800-8A) | Input signal range | | | 0/199.6 to 998 mV or 0/2 to 10 V | | 0/4 to 20 mA | Input impedance | | | 200 kО© | | 49.9 О© ± 0.1 % | | > 500 kО© | Common-mode voltage | 0 to 10 V | Filter time constant | 50 ms | Effect of temperature | | | 0.05 %/10 K | | 0.1 %/10 K | Analog outputs AA1 to AA3 | Rated signal range | 0 to 20 mA or 4 to 20 mA | Operating range | 0 to 20.5 mA or 3.6 to 20.5 mA | Load voltage | -1 to +18 V | Max. inductive load | ≤ 0.1 H | No-load voltage | ≤ 26 V | Time constant | 300 ms | Residual ripple 900 Hz | ≤ 0.2 % | Resolution | ≤ 0.1 % | Zero error | ≤ 0.3 % of measuring span | Gain error | ≤ 0.3 % of measuring span | Linearity error | ≤ 0.05 % of measuring span | Load dependence | ≤ 0.1 % | Effect of temperature | | | ≤ 0.1 %/10 K | | ≤ 0.1 %/10 K | Transmitter supply L+ | Rated voltage | 20 to 26 V | On-load current | ≤ 100 mA, short-circuit proof | Short-circuit current | ≤ 200 mA pulsed | Digital inputs BE1 to BE4 | Signal status "0" | ≤ 4.5 V or open | Signal status "1" | ≥ 13 V | Static destruction limit | ± 35 V | Input impedance | ≥ 27 kО© | Digital outputs BA1 to BA8 (connected via wired-OR diodes) | Signal status "0" | ≤ 1.5 V | Signal status "1" | +19 to 26 V | On-load current | < 50 mA | Short-circuit current | < 80 mA pulsed | Cycle time | > 60 ms, user program dependent | A/D conversion | Method | Successive approximation with > 120 measurements per input and averaging over 20 or 16.67 ms | Resolution | 11 bit в‰Ў 0.06 % | Zero error | ≤ 0.2 % of the measuring span | Gain error | ≤ 0.2 % of the measuring span | Linearity error | ≤ 0.2 % of the measuring span | Effect of temperature | | | ≤ 0.05 %/10 K | | ≤ 0.1 %/10 K | Display technology | Digital x, w displays | 4Ѕ digit, 7-segment LEDs | | Green | | Red | | 7 mm | | Adjustable start and full scale | | -1999 to 19999 | | Adjustable | | 0.08 to 8.0 s, adjustable | | 1 digit, but not better than A/D converter | | Corresponding to A/D converter and analog inputs | Digital y display | 3-digit, 7-segment LEDs | | Yellow | | 7 mm | | 0 to 100 % | | 0.08 to 8.0 s, adjustable | | 1 % | Analog displays | | | Green | | Red | | LED array with 30 LEDs / 0 to 100 % | | 1.7 % by alternate lighting of 1 or 2 LEDs, the center point of the illuminated LEDs acting as a pointer | | 0.08 to 8.0 s, adjustable |
|
|