SIPART DR21 Controllers |
|---|
General | | Mounting position | Any | Climatic classes | | - Storage: 1K2 according to
DIN IEC 721 Part 3-1
| -25 to +75 °C
| - Transport: 2K2 according to
DIN IEC 721 Part 3-2
| -25 to +75 °C
| - Operation 3K3 according to
DIN IEC 721 Part 3-3
| 0 to +50 °C
| Protection according to EN 60 529 | | | IP64 | | IP30 | | IP20 | Controller design Electrical safety - to DIN EN 61 010 Part 1
- Protection class I
- Safe separation between supply connection and field signals
- Clearances and creepage paths for surge class III and pollution level 2, unless stated otherwise
EC Certificate of Conformity no. 1243.00-05/01 CE marking: conformity concerning EMC Guideline 89/336/EWG and NS Guideline 73/23/EWG is fulfilled without restrictions. Emitted interference, immunity to interference to EN 61 326, NAMUR NE21 8/98 The SIPART DR21 controller has already acquired the following certifications: - Certification of Germanischen Lloyd, Certificate No. 97 974-96 HH
- Certificate of „DIN CERTCO, Berlin“,
Approval as temperature control and limiting equipment for heat generators, Certificate of Conformity with DIN 3440: 1984-07, Registration no.: TR 10692000 S - TГњV certificate on approval of a component symbol for water level controller, test requirement according to VdTГњV instructions „water level 100“ and „water level 100/1“, component symbol no. TГњV.WRS(WR).00-378K
| Weight of basic unit | Approx. 1.2 kg | Dimensions | | Color | | | RAL 7037 | | RAL 7035 | Material | | | Polycarbonate, reinforced with glass fiber | | Polyester | Power supply connections: | | | 3-pin earthed plug IEC 320/V DIN 49 457A | | Special 2-pin plug | Connections for process signals | Multi-pin screw-type terminal blocks, protected against reversed polarity for cables of 1.5 mm2 (AWG 14) | Protective earth connection | Earthing screw | A rail can be mounted on the rear panel of the power supply. The rail is included in the delivery of the coupling relay module. | The connector for the power supply and the screw-type terminal blocks for the process signals are part of the scope of the supply of the basic unit or the option modules. Exception: : 6DR2803-8C interface module and 6DR2803-8P PROFIBUS-DP module. The connectors have to be ordered separately. |
Power supply |
|---|
Rated voltage | Switchable | | | | 230 V AC | 115 V AC | 24 V AC/DC | Operating voltage range | 195 to 264 V AC | 97 to 132 V AC | 20 to 28 V AC | 20 to 35 V DC 1) | Frequency range | 48 to 63 Hz
| –
| Peak voltages to IEC 801-5 (1.2/50 Ојs) | | | | | symmetric | 1 kV | 1 kV | 0.5 kV | 0.5 kV | asymmetric | 2 kV | 2 kV | 1 kV | 1 kV | Total of all output currents (L+, BA, AA and SES) |
max. 200 mA
| Power consumption Apparent power (capacitive) Basic unit | | | | | | 5 W/9 VA | 5 W/9 VA | 4 W/6 VA | 4 W | - with options,
without IExt
| 11 W/15 VA | 11 W/15 VA | 8.5 W/12 VA | 8.5 W | | 15 W/19 VA | 15 W/19 VA | 12 W/17 VA | 12 W | Permitted voltage dips at 0.85 UN Standard controller with options |
20 ms
| Test voltages (1 min) | | | | 1.5 kV AC
| 500 V AC
| - Primary –
protective conductor
| 1.5 kV AC
| 500 V AC
| - Secondary -
protective conductor
| 700 V DC
| 700 V DC
|
1 ) Includes harmonic content. Basic unit |
|---|
Analog inputs AE1, AE2 | | | 0/4 to 20 mA | | 248 Ω | | -0.1 to +22 mA | | 10 ms | | | | 20 to 26 V | | ≤ 60 mA, short-circuit proof | | ≤ 200 mA, pulsed | Digital inputs BE1 and BE2 | | ≤ 4.5 V or open | | ≥ 13 V | | ≥ 27 kΩ | Digital outputs BA1 and BA2 (with wired OR diodes) | | | ≤ 1.5 V | | +19 to 26 V | | ≤ 30 mA | | ≤ 50 mA, pulsed | Analog output Iy | | | 0 to 20 mA or 4 to 20 mA | | 0 to 20.5 mA or 3.8 to 20.5 mA | | -1 to +18 V | - Max.permitted inductive load
| 0.1 H | Relay output | | | Ag-Ni | | | | 250 V AC 250 V DC | | 8 A 8 A | | 1250 VA 100 W at 24 V 30 W at 250 V | Service life | | | 2 . 107 switching operations | - Electrical 230 V AC, loading
| 2 . 106 switching operations | Spark suppressor | 22 nF and 220 Ω connected in series with a 420 V varistor wired in parallel | CPU data | | | 100 ms | A/D conversion | | | Successive approximation with > 120 measurements per input and averaging within 20 or 16.67 ms | | 11 bit ≡ 0.06 % | | ≤ 0,2 % of measuring span | | ≤ 0,2 % of measuring span | | ≤ 0,2 % of measuring span | Display technology | Digital x/w indicator | 4-digit, red, 7-segment LED display | | 7 mm | | Adjustable start and full scale | | -1999 to +9999 | | Adjustable (fixed-point) | | 0.1 to 9.9 s, variable | Analog x indicator | Vertical row of 30 LEDs (red) | Analog w indicator | Vertical row of 30 LEDs (green) | | 0 to 100 % | | 1.7 % | Digital y indicator | 2-digit, red, 7-segment LED display | | 7 mm | | 0 to 100 % | | 1 % | | 0.1 to 9.9 s, variable |
|
|