6ES7591-3AA00-0AA0Цена на сайте указана розничная в ЕВРО без учета НДС. Для уточнения цены и размера предоставляемой скидки - звоните или присылайте заявки | Заказной номер | Вес | PG | Описание продукта | Цена | | 6ES7591-3AA00-0AA0 | 0.02 | 215 | SIMATIC ET 200SP, ЗАПЧАСТИ - 5 ПЕРЕДНИХ КРЫШЕК ДЛЯ ИНТЕРФЕЙСА СЕТЕВОГО АДАПТЕРА ET200SP CPU | По запросу |
п»ї- Fast deterministic data exchange between CPUs with PROFINET controller, even beyond network boundaries
- Configuration with two PROFINET devices completely independent of the communication technology
 Data transmission between two S7-1500 IO controllers beyond a PROFINET limit - Very simple configuration of the data exchange via virtual IO modules or alternatively via data records for larger amounts of data
- Simultaneous data transfer to up to 3 CPUs on own network side and/or up to 4 CPUs on opposite network side
- Easy to integrate into any PROFINET network with 2 ports per network side
- Fieldbus connection via a SIMATIC BusAdapter;
this allows free selection of the connection system (RJ45, FC cable direct connection) and connection hardware (copper, POF, PCF, glass fiber). FO-to-copper media conversion can also be realized economically and without external converters.
Additional functions - Quantity structures
- Cyclic transmission: Up to 1В 440 bytes each for input and output data
- Data record transfer: Up to 4В 096 bytes per slot. Buffering of up to eight data records per slot
- Maximum 16 input/output areas for data exchange
- Max. 254 bytes of input and 253 bytes of output data per module
- Exchange of fail-safe data between two F-CPUs via F-SendDP and F_ReceiveDP
- Shared device with up to four IO controllers per network side
- Module-internal shared input / shared output (MSI/MSO)
- Device replacement without programming device
- With topological configuration via neighborhood detection (LLDP)
- Without topological configuration via redundant storage of the station name in the BusAdapter. A separate removable memory card is not required.
- Reset button for restoring the factory settings
- Redundant power supply
- Electrical isolation between the two PROFINET IO subnets
- Media redundancy (MRP and MRPD)
- I&M data
- Firmware update
- Support for Ethernet services (ping, arp, SNMP, MIP-2, LLDP)
- Comprehensive diagnostics via LED displays and interrupts
- Extensive compatibility with the PN/PN coupler up to firmware version V3.0
|
|