General technical specificationsElectrical specifications |
|---|
Line connection voltage Up to 2000 m (6562 ft) above sea level | 380 ... 480 V 3 AC ±10 % (-15 % <1 min) | Line power factor for a 3 AC line supply voltage and output power | | - Basic fundamental (cos φ1)
| >0.96 | | 0.75 ... 0.93 | DC link voltage, approx. 1) | 1.35 × line voltage | Output voltage, approx. | 0.97 x Uline | Output frequency 2) | | | 0 ... 550 Hz | | 0 ... 550 Hz | | 0 ... 550 Hz | Main contactor control | | | 240 V AC, max. 8 A 30 V DC, max. 1 A | Safety Integrated | Safety Integrity Level 2 (SIL2) acc. to IEC 61508, Performance Level d (PLd) acc. to EN ISO 13849‑1 and Control Category 3 acc. to EN ISO 13849‑1. |
1) The DC link voltage is unregulated and load-dependent. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual. 2) Please note: • Note the correlation between max. output frequency, pulse frequency and current derating. Higher output frequencies on request For further information, see https://support.industry.siemens.com/cs/document/104020669 • The correlation between the minimum output frequency and permissible output current (current derating). Information is provided in the SINAMICS Low Voltage Engineering Manual. Line voltage 380 ... 480 V 3 AC | Power Modules |
|---|
| 6SL3310-1TE32-1AA3 | 6SL3310-1TE32-6AA3 | 6SL3310-1TE33-1AA3 | 6SL3310-1TE33-8AA3 | 6SL3310-1TE35-0AA3 |
|---|
Type rating | | | | | | | | kW | 110 | 132 | 160 | 200 | 250 | | kW | 90 | 110 | 132 | 160 | 200 | | hp | 150 | 200 | 250 | 300 | 400 | | hp | 150 | 200 | 200 | 250 | 350 | Output current | | | | | | | | A | 210 | 260 | 310 | 380 | 490 | | A | 205 | 250 | 302 | 370 | 477 | | A | 178 | 233 | 277 | 340 | 438 | | A | 307 | 375 | 453 | 555 | 715 | Input current | | | | | | | - Rated input current Irated I
| A | 229 | 284 | 338 | 395 | 509 | - Maximum input current Imax I
| A | 335 | 410 | 495 | 606 | 781 | Current demand | | | | | | | - 24 V DC auxiliary power supply
| A | 0.8 | 0.8 | 0.9 | 0.9 | 0.9 | Pulse frequency 5) | | | | | | | | kHz | 2 | 2 | 2 | 2 | 2 | | | | | | | | | kHz | 2 | 2 | 2 | 2 | 2 | | kHz | 8 | 8 | 8 | 8 | 8 | Power loss, max. 6) | | | | | | | | kW | 2.46 | 3.27 | 4 | 4.54 | 5.78 | | kW | 2.54 | 3.36 | 4.07 | 4.67 | 5.96 | Cooling air requirement | m3/s (ft3/s) | 0.17 (6.00) | 0.23 (8.12) | 0.36 (12.7) | 0.36 (12.7) | 0.36 (12.7) | Sound pressure level LpA (1 m) at 50/60 Hz | dB | 64/67 | 71/71 | 69/73 | 69/73 | 69/73 | Line connection U1, V1, W1 | | M10 screw | M10 screw | M10 screw | M10 screw | M10 screw | - Conductor cross-section, max. (IEC)
| mm2 | 2 × 185 | 2 × 185 | 2 × 240 | 2 × 240 | 2 × 240 | Motor connection U2/T1, V2/T2, W2/T3 | | M10 screw | M10 screw | M10 screw | M10 screw | M10 screw | - Conductor cross-section, max. (IEC)
| mm2 | 2 × 185 | 2 × 185 | 2 × 240 | 2 × 240 | 2 × 240 | Cable length, max. 7) | | | | | | | | m (ft) | 300 (984) | 300 (984) | 300 (984) | 300 (984) | 300 (984) | | m (ft) | 450 (1476) | 450 (1476) | 450 (1476) | 450 (1476) | 450 (1476) | PE1/GND connection | | M10 screw | M10 screw | M10 screw | M10 screw | M10 screw | - Conductor cross-section, max. (IEC)
| mm2 | 2 × 185 | 2 × 185 | 2 × 240 | 2 × 240 | 2 × 240 | PE2/GND connection | | M10 screw | M10 screw | M10 screw | M10 screw | M10 screw | - Conductor cross-section, max. (IEC)
| mm2 | 2 × 185 | 2 × 185 | 2 × 240 | 2 × 240 | 2 × 240 | Degree of protection | | IP20 | IP20 | IP20 | IP20 | IP20 | Dimensions | | | | | | | | mm (in) | 326 (12.8) | 326 (12.8) | 326 (12.8) | 326 (12.8) | 326 (12.8) | | mm (in) | 1400 (55.1) | 1400 (55.1) | 1533 (60.4) | 1533 (60.4) | 1533 (60.4) | | mm (in) | 356 (14.0) 8) | 356 (14.0) 8) | 549 (21.6) | 549 (21.6) | 549 (21.6) | Weight, approx. | kg (lb) | 104 (229) | 104 (229) | 162 (357) | 162 (357) | 162 (357) | Frame size | | FX | FX | GX | GX | GX | Minimum short-circuit current 9) | A | 3000 | 3600 | 4400 | 4400 | 8000 |
1) Rated output of a typical 6-pole standard induction motor based on IL or IH for 400 V 3 AC 50 Hz. 2) Rated output of a typical 6-pole standard induction motor based on IL or IH for 460 V 3 AC 60 Hz. 3) The base-load current IL is based on a load cycle of 110 % for 60 s or 150 % for 10 s with a load cycle duration of 300 s. 4) The base-load current IH is based on a duty cycle of 150 % for 60 s or 160 % for 10 s with a duty cycle duration of 300 s. 5)Information regarding the correlation between the pulse frequency and maximum output current/output frequency is provided in the Engineering Manual. SINAMICS Low Voltage Engineering Manual. 6) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions. 7) Longer cable lengths for specific configurations are available on request. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual. 8) Depth = 421 mm (16.6 in) including front cover when CU310‑2 Control Unit is installed. 9) Current required for reliably triggering protective devices.
|