• The correlation between the minimum output frequency and permissible output current (current derating). Information is provided in the SINAMICS Low Voltage Engineering Manual.
Line voltage 380 ... 480 V 3 AC
Power Modules
6SL3310-1TE32-1AA3
6SL3310-1TE32-6AA3
6SL3310-1TE33-1AA3
6SL3310-1TE33-8AA3
6SL3310-1TE35-0AA3
Type rating
At IL (50 Hz 400 V) 1)
kW
110
132
160
200
250
At IH (50 Hz 400 V) 1)
kW
90
110
132
160
200
At IL (60 Hz 460 V) 2)
hp
150
200
250
300
400
At IH (60 Hz 460 V) 2)
hp
150
200
200
250
350
Output current
Rated current Irated O
A
210
260
310
380
490
Base-load current IL3)
A
205
250
302
370
477
Base-load current IH4)
A
178
233
277
340
438
Maximum current Imax O
A
307
375
453
555
715
Input current
Rated input current Irated I
A
229
284
338
395
509
Maximum input current Imax I
A
335
410
495
606
781
Current demand
24 V DC auxiliary power supply
A
0.8
0.8
0.9
0.9
0.9
Pulse frequency 5)
Rated frequency
kHz
2
2
2
2
2
Pulse frequency, max.
Without current derating
kHz
2
2
2
2
2
With current derating
kHz
8
8
8
8
8
Power loss, max. 6)
At 50 Hz 400 V
kW
2.46
3.27
4
4.54
5.78
At 60 Hz 460 V
kW
2.54
3.36
4.07
4.67
5.96
Cooling air requirement
m3/s (ft3/s)
0.17 (6.0)
0.23 (8.1)
0.36 (12.7)
0.36 (12.7)
0.36 (12.7)
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
66/67
71/71
68/72
68/72
68/72
Line connection
U1, V1, W1
Flat connector for M10 screw
Flat connector for M10 screw
Flat connector for M10 screw
Flat connector for M10 screw
Flat connector for M10 screw
Conductor cross section, max. (IEC)
mm2
2 ? 185
2 ? 185
2 ? 240
2 ? 240
2 ? 240
Motor connection
U2/T1, V2/T2, W2/T3
Flat connector for M10 screw
Flat connector for M10 screw
Flat connector for M10 screw
Flat connector for M10 screw
Flat connector for M10 screw
Conductor cross section, max. (IEC)
mm2
2 ? 185
2 ? 185
2 ? 240
2 ? 240
2 ? 240
Cable length, max. 7)
Shielded
m (ft)
300 (984)
300 (984)
300 (984)
300 (984)
300 (984)
Unshielded
m (ft)
450 (1476)
450 (1476)
450 (1476)
450 (1476)
450 (1476)
PE1/GND connection
Flat connector for M10 screw
Flat connector for M10 screw
Flat connector for M10 screw
Flat connector for M10 screw
Flat connector for M10 screw
Conductor cross section, max. (IEC)
mm2
2 ? 185
2 ? 185
2 ? 240
2 ? 240
2 ? 240
PE2/GND connection
M10 screw
M10 screw
M10 screw
M10 screw
M10 screw
Conductor cross section, max. (IEC)
mm2
2 ? 185
2 ? 185
2 ? 240
2 ? 240
2 ? 240
Degree of protection
IP20
IP20
IP20
IP20
IP20
Dimensions
Width
mm (in)
326 (12.8)
326 (12.8)
326 (12.8)
326 (12.8)
326 (12.8)
Height
mm (in)
1400 (55.1)
1400 (55.1)
1533 (60.3)
1533 (60.3)
1533 (60.3)
Depth
mm (in)
356 (14.0) 8)
356 (14.0) 8)
549 (21.6)
549 (21.6)
549 (21.6)
Weight, approx.
kg (lb)
104 (229)
104 (229)
162 (357)
162 (357)
162 (357)
Frame size
FX
FX
GX
GX
GX
Minimum short-circuit current 9)
A
3000
3600
4400
4400
8000
1) Rated output of a typical 6-pole standard induction motor based on IL or IH for 400 V 3 AC 50 Hz.
2) Rated output of a typical 6-pole standard induction motor based on IL or IH for 460 V 3 AC 60 Hz.
3) The base-load current IL is based on a duty cycle of 110 % for 60 s or 150 % for 10 s with a duty cycle duration of 300 s.
4) The base-load current IH is based on a duty cycle of 150 % for 60 s or 160 % for 10 s with a duty cycle duration of 300 s.
5)Information regarding the correlation between the pulse frequency and maximum output current/output frequency is provided in the SINAMICS Low Voltage Engineering Manual.
6) The specified power loss represents the maximum value at 100% utilization. The value is lower under normal operating conditions.
7) Longer cable lengths for specific configurations are available on request. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.
8) Depth = 421 mm (16.6 in) including front cover when CU310?2 Control Unit is installed.
9) Current required for reliably triggering protective devices.