Derating data

SINAMICS G180 converters and the associated system components are rated for an ambient temperature of 40 °C and installation altitudes up to 1000 m above sea level.

At ambient temperatures of > 40 °C, the output current must be reduced. SINAMICS G180 converters may not operate in ambient temperatures in excess of 50 °C except for compact units (up to 55 °C; option V63).

At installation altitudes > 1000 m above sea level, it must be taken into account that the air pressure, and therefore air density, decreases as the height increases. As a consequence, the cooling efficiency and the insulation capacity of the air also decrease.

Due to the reduced cooling efficiency, it is necessary, on the one hand, to reduce the ambient temperature, and on the other hand, to lower heat loss in the compact unit by reducing the output current, whereby ambient temperatures lower than 40 °C may be offset to compensate.

The following table specifies the permissible output currents as a function of the installation altitude and ambient temperature (the permissible compensation between installation altitude and ambient temperatures of < 40 °C (air intake temperature at the entry to the compact unit) is taken into account in the specified values).

The values apply under the precondition that a cooling air flow through the units is ensured as stated in the technical data.

Derating for air-cooled converters

Installation altitude above sea level

Current derating factor (as a % of the rated current) at an ambient/air intake temperature of 40 °C

m

20 °C

25 °C

30 °C

35 °C

40 °C

45 °C

50 °C

55 °C1)

0 ... 1000

100 %

100 %

100 %

100 %

100 %

87.5 %

75 %

62.5 %

1001 ... 1500

100 %

100 %

100 %

100 %

94.4 %

82.6 %

70.8 %

59.0 %

1501 ... 2000

100 %

100 %

99.4 %

94.3 %

88.9 %

77.8 %

66.7 %

55.6 %

2001 ... 25002)

100 %

97.7 %

93.2 %

88.4 %

83.3 %

72.9 %

62.5 %

52.1 %

2501 ... 30002)

95.3 %

91.2 %

87.0 %

82.5 %

77.8 %

68.1 %

58.3 %

48.6 %

3001 ... 35002)3)

89.8 %

86.0 %

82.0 %

77.8 %

73.3 %

64.2 %

55.0 %

45.8 %

3501 ... 40002)3)

84.4 %

80.8 %

77.0 %

73.1 %

68.9 %

60.3 %

51.7 %

43.1 %

4001 ... 45002)3)

78.9 %

75.6 %

72.1 %

68.4 %

64.4 %

56.4 %

48.3 %

40.3 %

4501 ... 50002)3)

73.5 %

70.4 %

67.1 %

63.6 %

60.0 %

52.5 %

45.0 %

37.5 %



1) Applies only to compact units which are not cabinet-mounted

2) Voltage derating (see voltage derating factor) is also required for compact units at an installation altitude of > 2000 m.

3) Voltage derating (see voltage derating factor) is also required for cabinet units at an installation altitude of > 3000 m.

Derating for liquid-cooled converters with coolant inlet temperature of max. 28 °C

Installation altitude above sea level

Current derating factor (as a % of the rated current) for a coolant inlet temperature of 28 °C

m

18 °C

23 °C

28 °C

33 °C

38 °C

0 ... 1000

100 %

100 %

100 %

84.0 %

64.2 %

1001 ... 1500

100 %

100 %

94.4 %

79.3 %

60.6 %

1501 ... 2000

100 %

100 %

88.9 %

74.7 %

57.0 %

2001 ... 2500

100 %

94.8 %

83.3 %

70.0 %

53.5 %

2501 ... 3000

98.0 %

88.5 %

77.8 %

65.3 %

49.9 %

3001 ... 35001)

92.4 %

83.4 %

73.3 %

61.6 %

47.1 %

3501 ... 40001)

86.8 %

78.4 %

68.9 %

57.9 %

44.2 %

4001 ... 45001)

81.2 %

73.3 %

64.4 %

54.1 %

41.4 %

4501 ... 50001)

75.6 %

68.3 %

60.0 %

50.4 %

38.5 %



1) Voltage derating (see voltage derating factor) is also required for cabinet units at an installation altitude of > 3000 m.

Derating for liquid-cooled converters with coolant inlet temperature of max. 30 °C

Installation altitude above sea level

Current derating factor (as a % of the rated current) for a coolant inlet temperature of 30 °C

m

20 °C

25 °C

30 °C

35 °C

40 °C

0 ... 1000

100 %

100 %

100 %

81.6 %

57.7 %

1001 ... 1500

100 %

100 %

94.4 %

77.1 %

54.5 %

1501 ... 2000

100 %

100 %

88.9 %

72.6 %

51.3 %

2001 ... 2500

100 %

96.2 %

83.3 %

68.0 %

48.1 %

2501 ... 3000

100 %

89.8 %

77.8 %

63.5 %

44.9 %

3001 ... 35001)

94.7 %

84.7 %

73.3 %

59.9 %

42.3 %

3501 ... 40001)

88.9 %

79.5 %

68.9 %

56.2 %

39.8 %

4001 ... 45001)

83.2 %

74.4 %

64.4 %

52.6 %

37.2 %

4501 ... 50001)

77.5 %

69.3 %

60.0 %

49.0 %

34.6 %



1) Voltage derating (see voltage derating factor) is also required for cabinet units at an installation altitude of > 3000 m.

Derating for liquid-cooled converters with coolant inlet temperature of max. 35 °C

Installation altitude above sea level

Current derating factor (as a % of the rated current) for a coolant inlet temperature of 35 °C

m

25 °C

30 °C

35 °C

40 °C

0 ... 1000

100 %

100 %

100 %

70.7 %

1001 ... 1500

100 %

100 %

94.4 %

66.8 %

1501 ... 2000

100 %

100 %

88.9 %

62.9 %

2001 ... 2500

100 %

100 %

83.3 %

58.9 %

2501 ... 3000

100 %

95.3 %

77.8 %

55.0 %

3001 ... 35001)

100 %

89.8 %

73.3 %

51.9 %

3501 ... 40001)

97.4 %

84.4 %

68.9 %

48.7 %

4001 ... 45001)

91.1 %

78.9 %

64.4 %

45.6 %

4501 ... 50001)

84.9 %

73.5 %

60.0 %

42.4 %



1) Voltage derating (see voltage derating factor) is also required for cabinet units at an installation altitude of > 3000 m.

The compact units are designed according to minimum air clearances at up to 2000 m above sea level, and the cabinet units according to minimum air clearances at up to 3000 m above sea level, i.e. voltage derating is not required for compact units at altitudes of 2000 m or below or for cabinet units at altitudes of 3000 m or below.

Since the air clearances in the converter cannot be changed, this factor must be taken into account in the voltage derating calculation.

Vmax is the reference value for voltage derating.

Voltage derating factor

Installation altitude above sea level

For compact units and cabinet systems:
Voltage derating factor (in % of line voltage)

- For 400 V units → Vmax = 500 V

- For 500 V units → Vmax = 500 V

- For 690 V units → Vmax = 690 V

For cabinet units:
Voltage derating factor (in % of line voltage)

- For 400 V units → Vmax = 415 V

- For 500 V units → Vmax = 500 V

- For 690 V units → Vmax = 690 V

m

400/500/690 V

400/500/690 V

0 ... 2000

100 %

100 %

2001 ... 2500

93.4 %

100 %

2501 ... 3000

87.7 %

100 %

3001 ... 3500

81.9 %

93.9 %

3501 ... 4000

77.5 %

88.5 %

4001 ... 4500

71.9 %

82.4 %

4501 ... 5000

67.6 %

77.0 %



Overload capability

The SINAMICS G180 converters have an overload reserve of typically about 110 % to deal with breakaway torques, for example. The overload period of the potential short-time current is regulated automatically (thermal converter model), but is at least 60 s at 40 °C on condition that the converter is operated at its rated current prior to and following the period of overload. This calculation is based on a duty cycle duration of 600 s.

If larger surge loads occur, this must be taken into account when configuring. It may be necessary to select a converter in the next-higher rating class.

Overload capability of SINAMICS G180

















skener.ru

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Àðìàòóðà DENDOR

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Äàò÷èêè è èçìåðèòåëè

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ðåãóëÿòîðû è ðåãèñòðàòîðû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ïíåâìàòè÷åñêîå îáîðóäîâàíèå

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Êðàíû è Êëàïàíû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Èçìåðèòåëüíûå ïðèáîðû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ñèñòåìû áåñïðîâîäíîãî óïðàâëåíèÿ «óìíûé äîì»

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Áåñêîíòàêòíûå âûêëþ÷àòåëè Êîíå÷íûå âûêëþ÷àòåëè Îïòè÷åñêèå äàò÷èêè Ýíêîäåðû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FS - Óñòàíîâêà óìÿã÷åíèÿ

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FK - Óñòàíîâêà îáåçæåëåçèâàíèÿ
Êàòàëîã îáîðóäîâàíèÿ 2018
Siemens Industry Catalog Drive technology Converters AC Low-voltage converters SINAMICS V basic performance converters General performance converters SINAMICS G SINAMICS G110 standard inverters SINAMICS G120C compact inverters SINAMICS G120P and G120P Cabinet pump, fan, compressor converters SINAMICS G120 standard inverters SINAMICS G110M distributed inverters SINAMICS G110D distributed inverters SINAMICS G120D distributed inverters SINAMICS G130 Drive converter chassis units SINAMICS G150 Drive converter cabinet units SINAMICS G180 Introduction SINAMICS G180 compact units and SINAMICS G180 cabinet systems SINAMICS G180 cabinet units Option descriptions Configuring instructions Functions Characteristic curves Cable cross-sections and connections Standard interface Communication possibilities The SINAMICS G180 type plate Supplementary Supply Agreements for Converter Drives in Power Plants SIZER for Siemens Drives engineering tool DT Configurator selection guide IMS commissioning tool Services and documentation High performance converters SINAMICS S Frequency inverters MICROMASTER SIPLUS POSMO A LOHER DYNAVERT Drive System Medium-Voltage AC Converter DC converter units Motors Generators Geared Motors Flender Gear Units Couplings Selection and engineering tools Further Components Automation technology Energy Building Technologies Low-Voltage controls and distribution Safety Systems - Safety Integrated Market-specific solutions Industry Services Software ... and everything else you need




  © ÎÎÎ "ÑÊ ÝÍÅÐÃÎ" 2007-2022
  (4872) 700-366  skenergo@mail.ru
ßíäåêñ.Ìåòðèêà