Siemens
01 2018
(4872) 700-366
skenergo@mail.ru

The most important directives and standards are listed below. These are used as basis for the SINAMICSG180 cabinet units and they must be carefully observed to achieve an EMC-compliant configuration that is safe both functionally and in operation.

Standards for cabinet units

European directives

2006/95/EC

Low-voltage directive:
Legal guidelines of the EU member states concerning electrical equipment for use within specified voltage limits

2004/108/EC

EMC Directive:
Legal guidelines of the EU member states for electromagnetic compatibility

International and European standards

EN954‑1

Safety of machinery Safety-related parts of control systems;
Part 1: General design principles

ENISO13849‑1

Safety of machinery Safety-related parts of control systems;
Part 1: General design principles (ISO13849‑1:2006) (replaced EN954‑1)

EN60146‑1‑1

Semiconductor converters General requirements and line-commutated converters
Part 1-1: Specification of basic requirements

EN60204‑1

Electrical equipment of machines
Part1: General definitions

EN 60529

Degrees of protection provided by enclosures (IP code)

EN 61140

Protection against electric shock - Common aspects for installation and equipment

EN61508‑1

Functional safety of electrical/electronic/programmable electronic safety-related systems
Part1: General requirements

EN61800‑2

Adjustable speed electrical power drive systems,
Part 2: General requirements Rating specifications for low-voltage adjustable frequency AC power drive systems

EN61800‑3

Adjustable speed electrical power drive systems,
Part 3: EMC requirements and specific test methods

EN 61800-5-1

Adjustable speed electrical power drive systems,
Part 5-1: Safety requirements -
Electrical, thermal and energy requirements

EN61800‑5‑2

Adjustable speed electrical power drive systems,
Part 5-2: Safety requirements Functional safety (IEC61800‑5‑2:2007)

North American standards

UL508C1)

Power conversion equipment

Approvals

TÜV NRTL US1)

Nationally Recognized Testing Laboratory



1) On request

General technical data

Electrical data

Line voltages

Type of supply system

Output ranges

230…400…415V3AC, -15/+10%

TN/TT system

200...630kW(at 400V)

230…500V3AC, -15/+10%

TN/TT/IT system

250...800kW(at 500 V)

400…690 V3AC, -15/+10%

TN/TT/IT system

250...6000kW(at 690 V)

Line frequency

47 … 63 Hz

Output frequency

0 … 250 Hz

Voltage rise in motor

Typ. 500...1000V/s, but <1500V/s

Pulse number

6/12/18/24

Typical line harmonics (I) in % of fundamental mode for the 5/7/11/13/17/19/23/25 harmonics, max.
(6-pulse converter)

38/18/8/7/5/4/3/2

Typical line harmonics (I) in % of fundamental mode for the 5/7/11/13/17/19/23/25 harmonics, max.
(12-pulse converter)

1.5/1/6/4/0.5/0.2/2/2

Typical line harmonics (I) in % of fundamental mode for the 5/7/11/13/17/19/23/25 harmonics, max.
(18-pulse converter)

1/0.5/0.5/0.5/4/3.5/0.5/0.5

Typical line harmonics (I) in % of fundamental mode for the 5/7/11/13/17/19/23/25 harmonics, max.
(24-pulse converter)

1/0.5/0.5/0.5/0.5/0.2/2/2

Typical line harmonics (I) in % of fundamental mode for the 5/7/11/13/17/19/23/25
harmonics max. with LHF filter

4.5/4.7/2.8/1.6/1.2/0.9/0.6/0.5

Overvoltage category

III to EN61800‑5‑1

Short Circuit Current Rating (SCCR)
according to UL508C (up to 600V), in conjunction with the specified fuses or circuit breakers

20 times rated current, but at least 50kA

Control method

  • For motors: Field-oriented control (FOC) with sensor and approval for explosion-proof motors as well as vector control (SVC) with/without sensor (speed, process speed (n), torque, hoist1), line synchronization1))
  • Motor-independent control of current or voltage (current, process current (I), voltage, process voltage (U))

Fixed speeds

3 fixed speeds + 1 minimum speed, parameterizable

Skipped speed ranges

2, parameterizable

Setpoint resolution

13 bits digital with n/f setpoint, 12bits digital with U/I torque setpoint, 9bits + sign analog

Braking operation

The oversaturation control system makes it possible to generate a braking torque of up to 50% at low to mid-range speeds, and of up to 10 % at high speeds. If a higher braking torque is required, an optionally available braking module with appropriate braking resistor must be installed.

Mechanical data

Degree of protection

IP21 (higher degrees of protection optionally available) / with liquid cooling IP54

Protection class

I acc. to EN61800‑5‑1

Touch protection

EN 50274 / BGV A3

Type of cooling

Forced air cooling AF to EN60146 / Coolant is water and a mixture of water and Antifrogen N with 45% Antifrogen N

Paint finish

RAL7035; Rittal TS8 cabinet frame: With nano-ceramic and anodized coating, layer thickness approx.10to20m; parts mounted on TS8 cabinet: With nano-ceramic and anodized coating, layer thickness approx.10to20m, plus layer of hybrid polyester epoxy powder, thickness approx.50to80m

Cable entry

From below by means of profile clamp (from the top as option)

Door hinge and opening angle

Right/130

For liquid-cooled units only

Coolant quality

See below under "Permissible substance values for the coolant"

Permissible coolant temperature

+10C…28/30/35C (dependent on output, see technical data)

Ambient conditions2)

Storage 3)

Transport 3)

Operation

Ambient temperature

-25…+70C

Class 1K4 acc. to EN60721‑3‑1

-25...+70C
Down to -40C for 24h
Class 2K3 acc. to EN60721‑3‑2

Air: 0…40C/
Water: 1C…40C
(up to +40C see derating data)

Relative humidity
(condensation not permissible)

5...95%
Class 1K3 acc. to EN60721‑3‑1

5…95%
Class 2K3 acc. to EN60721‑3‑2

5…95%
Class 3K3 acc. to EN60721‑3‑3

Environmental class/harmful chemical substances

Class 1C2 acc. to EN60721‑3‑1

Class 2C2 acc. to EN60721‑3‑2

Class 3C2 acc. to EN60721‑3‑3

Organic/biological influences

Class 1B1 acc. to EN60721‑3‑1

Class 2B1 acc. to EN60721‑3‑2

Class 3B1 acc. to EN60721‑3‑3

Pollution degree

2 acc. to EN61800‑5‑1

Installation altitude

Up to 1000m above sea level without derating, >1000 m see derating data

Mechanical stability2)

Storage 3)

Transport 3)

Operation

Vibratory load

  • Deflection
  • Acceleration

1.5 mm at 5 … 9 Hz

5m/s2 at >9…200Hz
Class 1M2 to EN60721‑3‑1

3.5 mm at 5 … 9 Hz

10 m/s2 at > 9 …200Hz
Class 2M2 to EN60721‑3‑2

0.075mmat10…57 Hz

10m/s2 at >57…150 Hz

Shock load

  • Acceleration

40m/s2 at 22ms
Class 1M2 to EN60721‑3‑1

100m/s2 at 11ms
Class 2M2 to EN60721‑3‑2

100m/s2 at 11ms
Class 3M4 to EN60721‑3‑3

Compliance with standards

CE Label

Acc. to EMC Directive No. 2004/108/EC and Low-Voltage Directive No. 2006/95/EC

Radio interference suppression

Complies with EMC guidelines defined in EN61800‑3 thanks to line filter which is integrated as standard with grounded supply system:

  • Category C3 for cabinet units in TN/TT system of the second environment (industrial area)
  • Category C4 for cabinet units in IT system of the second environment (industrial area)

Approvals

TÜV NRTL US2)



1) On request

2) Higher standards on request

3) In transport packaging

Deviations from the specified classes are underlined.

Permissible substance values for the coolant

The following table lists the permissible substance values for the cooling water (service water and demineralized water) for cooling the converter with an open standard cooling system without cooling unit.

Permissible values for SINAMICSG180 cabinet units

Coolant temperature

+10 … 28/30/35 C

pH value

7…8

Total hardness

6…20dH

Carbonate hardness

3…10dH

Total dissolved solids 105C

<500 mg/l

Free carbon dioxide

<1 mmol/l

Chlorides

<150 mg/l

Sulfates

500 mg/l

Nitrates

<10 mg/l

Nitrites

0 mg/l

Phosphates

<0.5 mg/l

Ammonium NH4

<0.5 mg/l

Ammoniac

0 mg/l

Silicon (SiO2 crystalline)

<10 mg/l

Free CO2 (p value)

<15 mg/l

Iron

<0.2 mg/l

Hydrogen sulfide

<1 mg/l

Suspended solids <50μm

<10 mg/l

Conductivity

<3000μS/cm

Oxygen

8 … 12 mg/l



Cooling water additives for the closed converter cooling system with cooling unit

We recommend the agent "Antifrogen N" supplied by Clariant as a cooling water additive.
The appropriate level of anti-freeze protection can be provided by choosing the correct mixing ratio. A minimum concentration of 20% by volume provides anti-freeze protection down to ‑10C. An Antifrogen/water mixing ratio of 1:2 provides anti-freeze protection down to ‑20C.

Unpolluted water mixed with a minimum concentration of 20% by volume of Antifrogen N prevents the growth of microorganisms and the formation of algae.

400 V, 6‑pulse

Line voltage, supply system type

400,415V3AC TT/TN

SINAMICS G180
cabinet units air-cooled

6SE0180‑1BA33‑7❑A7

6SE0180‑1BA34‑6❑A7

6SE0180‑1BA36‑3❑A7

6SE0180‑1BA37‑3❑A7

6SE0180‑1BA38‑8❑A7

Converter type (air-cooled)

2T3A‑87401‑200

2T3A‑87401‑250

2T3A‑87401‑315

2T3A‑87401‑400

2T3A‑87401‑500

SINAMICS G180
cabinet units liquid-cooled

6SE0170‑1BA33‑7❑A7

6SE0170‑1BA34‑6❑A7

6SE0170‑1BA36‑3❑A7

6SE0170‑1BA37‑3❑A7

6SE0170‑1BA38‑8❑A7

Converter type (liquid-cooled)

2T6A‑77401‑200

2T6A‑77401‑250

2T6A‑77401‑315

2T6A‑77401‑400

2T6A‑77401‑500

Electrical data at motor end

Type rating 1)

  • at 50 Hz 400 V

kW

200

250

315

400

500

  • at 50 Hz 400 V

hp

268

335

422

536

671

Output voltage2)

V

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

Output current

  • Continuous current

A

380

460

630

740

910

  • Short-time current
    (60s every 10minutes) max.

A

470

560

700

900

1110

Overload capability
(60s every 10minutes) max.

%

24

22

11

22

22

Output power

kVA

263

319

436

513

630

Output frequency, max.

Hz

250

250

250

120

120

Rated clock cycle

kHz

3

3

3

2.4

2.4

adjustable from

kHz

2...5

2...5

2...5

1.5...3.7

1.5...3.7

Power loss 3)

kW

5.6

6.42

8.4

11.9

14.9

Rated efficiency

%

97.4

97.6

97.5

97.2

97.2

Electrical data at line end

Connected load

kVA

249

300

403

476

603

Rated input voltage

V

400

400

400

400

400

Input current

  • Continuous line current

A

360

433

582

687

871

  • Short-time line current (60s) max.

A

445

527

647

836

1062

Line fuse (provided by customer)

gL(A)

400

500

630

800

900

λline

0.931

0.928

0.943

0.942

0.946

Cosφline

1

1

1

1

1

Radio interference suppression acc. to EN61800‑3

C3 (class A filter)

C3 (class A filter)

C3 (class A filter)

C3 (class A filter)

C3 (class A filter)

Mechanical data for air-cooled cabinet units

Frame size (dimensional drawing classification)

SL2

SL2

SL2

SL21

SL3

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

70

70

73

75

75

Standard converter dimensions

  • Width

mm

806

806

806

1206

1606

  • Height4)

mm

2112

2112

2112

2112

2112

  • Depth

mm

605

605

605

605

605

Coolant requirements

m3/h

1900

1900

1900

2250

3800

Weight, approx.

kg

490

510

530

780

890

Mechanical data for liquid-cooled cabinet units

Frame size (dimensional drawing classification)

SW2

SW2

SW2

SW21

SW3

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

68

68

71

73

73

Standard converter dimensions6)

  • Width

mm

806

806

806

1206

1806

  • Height

mm

2202

2202

2202

2202

2202

  • Depth

mm

605

605

605

605

605

Coolant requirements

l/h

1200

1200

1200

1200

2000

Min. coolant pressure

bar

2.5

2.5

2.5

2.5

2.5

Max. coolant pressure

bar

6

6

6

6

6

Coolant test pressure

bar

10

10

10

10

10

Coolant pressure loss

bar

1.9

1.9

1.9

1.9

1.9

Min. coolant temperature

C

10

10

10

10

10

Max. coolant temperature

C

35

35

35

30

35

Weight, approx.

kg

490

510

530

860

920

General mechanical data

Max. cable length between converter and motor with standard insulation

(shielded)

m

3005)

3005)

3005)

3005)

3005)

Line/load connection

L1, L2, L3/U2, V2, W2

For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"

Approvals, according to

NRTL6)

NRTL6)

NRTL6)

NRTL6)

NRTL6)



1)Rated power of a typical 2- to 6-pole standard motor.

2) Typical output voltage dependent on filter and unit type.

3)Maximum power loss with continuous motor current.

4)With IP21 protective top cover (110mm).

5) Option L10 included (strengthened dv/dt filter; strengthened filter is integrated in unit).

6) On request.

Line voltage, supply system type

400,415V3AC TT/TN

SINAMICS G180
cabinet units air-cooled

6SE0180‑1BA41‑0❑A7

6SE0180‑1BA41‑1❑A7

Converter type (air-cooled)

2T3A‑87401‑560

2T3A‑87401‑630

SINAMICS G180
cabinet units liquid-cooled

6SE0170‑1BA41‑0❑A7

6SE0170‑1BA41‑1❑A7

Converter type (liquid-cooled)

2T6A‑77401‑560

2T6A‑77401‑630

Electrical data at motor end

Type rating 1)

  • at 50 Hz 400 V

kW

560

630

  • at 50 Hz 400 V

hp

751

845

Output voltage2)

V

0...0.98×Vline

0...0.98×Vline

Output current

  • Continuous current

A

1020

1140

  • Short-time current
    (60s every 10minutes) max.

A

1230

1370

Overload capability
(60s every 10minutes) max.

%

21

20

Output power

kVA

707

790

Output frequency, max.

Hz

120

120

Rated clock cycle

kHz

2.4

2.4

adjustable from

kHz

1.5...3.7

1.5...3.7

Power loss 3)

kW

16.7

18.1

Rated efficiency

%

97.2

97.3

Electrical data at line end

Connected load

kVA

676

761

Rated input voltage

V

400

400

Input current

  • Continuous line current

A

975

1098

  • Short-time line current (60s) max.

A

1176

1320

Line fuse (provided by customer)

gL(A)

1000

1250

λline

0.947

0.95

Cosφline

1

1

Radio interference suppression acc. to EN61800‑3

C3 (class A filter)

C3 (class A filter)

Mechanical data for air-cooled cabinet units

Frame size (dimensional drawing classification)

SL3

SL3

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

75

75

Standard converter dimensions

  • Width

mm

1606

1606

  • Height4)

mm

2112

2112

  • Depth

mm

605

605

Coolant requirements

m3/h

3200

3800

Weight, approx.

kg

900

930

Mechanical data for liquid-cooled cabinet units

Frame size (dimensional drawing classification)

SW3

SW3

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

73

73

Standard converter dimensions6)

  • Width

mm

1806

1806

  • Height

mm

2202

2202

  • Depth

mm

605

605

Coolant requirements

l/h

2000

2000

Min. coolant pressure

bar

2.5

2.5

Max. coolant pressure

bar

6

6

Coolant test pressure

bar

10

10

Coolant pressure loss

bar

1.9

1.9

Min. coolant temperature

C

10

10

Max. coolant temperature

C

35

35

Weight, approx.

kg

930

960

General mechanical data

Max. cable length between converter and motor with standard insulation

(shielded)

m

3005)

3005)

Line/load connection

L1, L2, L3/U2, V2, W2

For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"

Approvals, according to

NRTL6)

NRTL6)



1)Rated power of a typical 2- to 6-pole standard motor.

2) Typical output voltage dependent on filter and unit type.

3)Maximum power loss with continuous motor current.

4)With IP21 protective top cover (110mm).

5) Option L10 included (strengthened dv/dt filter; strengthened filter is integrated in unit).

6) On request.

400 V, 12‑pulse

Line voltage, supply system type

400, 415V3AC IT

SINAMICS G180
cabinet units air-cooled

6SE0180‑2BA33‑7❑A7

6SE0180‑2BA34‑6❑A7

6SE0180‑2BA36‑3❑A7

6SE0180‑2BA37‑3❑A7

6SE0180‑2BA38‑8❑A7

Converter type (air-cooled)

2T3F‑87401‑200

2T3F‑87401‑250

2T3F‑87401‑315

2T3F‑87401‑400

2T3F‑87401‑500

SINAMICS G180
cabinet units liquid-cooled

6SE0170‑2BA33‑7❑A7

6SE0170‑2BA34‑6❑A7

6SE0170‑2BA36‑3❑A7

6SE0170‑2BA37‑3❑A7

6SE0170‑2BA38‑8❑A7

Converter type (liquid-cooled)

2T6F‑77401‑200

2T6F‑77401‑250

2T6F‑77401‑315

2T6F‑77401‑400

2T6F‑77401‑500

Electrical data at motor end

Type rating 1)

  • at 50 Hz 400 V

kW

200

250

315

400

500

  • at 50 Hz 400 V

hp

268

335

422

536

671

Output voltage2)

V

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

Output current

  • Continuous current

A

380

460

630

740

910

  • Short-time current
    (60s every 10minutes) max.

A

470

560

700

900

1110

Overload capability
(60s every 10minutes) max.

%

24

22

11

22

22

Output power

kVA

263

319

436

513

630

Output frequency, max.

Hz

250

250

250

120

120

Rated clock cycle

kHz

3

3

3

2.4

2.4

adjustable from

kHz

2...5

2...5

2...5

1.5...3.7

1.5...3.7

Power loss 3)

kW

5.6

6.42

8.4

11.9

14.9

Rated efficiency

%

97.4

97.6

97.5

97.2

97.2

Electrical data at line end

Connected load

kVA

249

301

405

477

604

Rated input voltage

V

400

400

400

400

400

Input current

  • Continuous line current

A

180

217

292

344

436

  • Short-time line current (60s) max.

A

223

264

324

418

532

Line fuse (provided by customer)

gL(A)

200

250

400

400

500

λline

0.994

0.994

0.994

0.996

0.996

Cosφline

1

1

1

1

1

Radio interference suppression acc. to EN61800‑3

C3 (class A filter)

C3 (class A filter)

C3 (class A filter)

C3 (class A filter)

C3 (class A filter)

Mechanical data for air-cooled cabinet units

Frame size (dimensional drawing classification)

SL5

SL5

SL5

SL5

SL6

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

70

70

73

75

75

Standard converter dimensions

  • Width

mm

1406

1406

1406

1406

1806

  • Height4)

mm

2112

2112

2112

2112

2112

  • Depth

mm

605

605

605

605

605

Coolant requirements

m3/h

1900

1900

1900

2250

3800

Weight, approx.

kg

690

710

730

810

920

Mechanical data for liquid-cooled cabinet units

Frame size (dimensional drawing classification)

SW5

SW5

SW5

SW5

SW6

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

68

68

71

73

73

Standard converter dimensions

  • Width

mm

1406

1406

1406

1406

2006

  • Height

mm

2202

2202

2202

2202

2202

  • Depth

mm

605

605

605

605

605

Coolant requirements

l/h

1200

1200

1200

1200

2000

Min. coolant pressure

bar

2.5

2.5

2.5

2.5

2.5

Max. coolant pressure

bar

6

6

6

6

6

Coolant test pressure

bar

10

10

10

10

10

Coolant pressure loss

bar

1.9

1.9

1.9

1.9

1.9

Min. coolant temperature

C

10

10

10

10

10

Max. coolant temperature

C

35

35

35

30

35

Weight, approx.

kg

690

710

730

810

950

General mechanical data

Max. cable length between converter and motor with standard insulation

(shielded)

m

3005)

3005)

3005)

3005)

3005)

Line/load connection

L1, L2, L3/U2, V2, W2

For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"

Approvals, according to

NRTL6)

NRTL6)

NRTL6)

NRTL6)

NRTL6)



1)Rated power of a typical 2- to 6-pole standard motor.

2) Typical output voltage dependent on filter and unit type.

3)Maximum power loss with continuous motor current.

4)With IP21 protective top cover (110mm).

5) Option L10 included (strengthened dv/dt filter; strengthened filter is integrated in unit).

6) On request.

Line voltage, supply system type

400, 415V3AC IT

SINAMICS G180
cabinet units air-cooled

6SE0180‑2BA41‑0❑A7

6SE0180‑2BA41‑1❑A7

Converter type (air-cooled)

2T3F‑87401‑560

2T3F‑87401‑630

SINAMICS G180
cabinet units liquid-cooled

6SE0170‑2BA41‑0❑A7

6SE0170‑2BA41‑1❑A7

Converter type (liquid-cooled)

2T6F‑77401‑560

2T6F‑77401‑630

Electrical data at motor end

Type rating 1)

  • at 50 Hz 400 V

kW

560

630

  • at 50 Hz 400 V

hp

751

845

Output voltage2)

V

0...0.98×Vline

0...0.98×Vline

Output current

  • Continuous current

A

1020

1140

  • Short-time current
    (60s every 10minutes) max.

A

1230

1370

Overload capability
(60s every 10minutes) max.

%

21

20

Output power

kVA

707

790

Output frequency, max.

Hz

120

120

Rated clock cycle

kHz

2.4

2.4

adjustable from

kHz

1.5...3.7

1.5...3.7

Power loss 3)

kW

16.7

18.1

Rated efficiency

%

97.2

97.3

Electrical data at line end

Connected load

kVA

676

762

Rated input voltage

V

400

400

Input current

  • Continuous line current

A

488

550

  • Short-time line current (60s) max.

A

588

661

Line fuse (provided by customer)

gL(A)

630

630

λline

0.996

0.997

Cosφline

1

1

Radio interference suppression acc. to EN61800‑3

C4

C4

Mechanical data for air-cooled cabinet units

Frame size (dimensional drawing classification)

SL6

SL6

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

75

75

Standard converter dimensions

  • Width

mm

1806

1806

  • Height4)

mm

2112

2112

  • Depth

mm

605

605

Coolant requirements

m3/h

3200

3800

Weight, approx.

kg

930

960

Mechanical data for liquid-cooled cabinet units

Frame size (dimensional drawing classification)

SW6

SW6

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

73

73

Standard converter dimensions

  • Width

mm

2006

2006

  • Height

mm

2202

2202

  • Depth

mm

605

605

Coolant requirements

l/h

2000

2000

Min. coolant pressure

bar

2.5

2.5

Max. coolant pressure

bar

6

6

Coolant test pressure

bar

10

10

Coolant pressure loss

bar

1.9

1.9

Min. coolant temperature

C

10

10

Max. coolant temperature

C

35

35

Weight, approx.

kg

960

990

General mechanical data

Max. cable length between converter and motor with standard insulation

(shielded)

m

3005)

3005)

Line/load connection

L1, L2, L3/U2, V2, W2

For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"

Approvals, according to

NRTL6)

NRTL6)



1)Rated power of a typical 2- to 6-pole standard motor.

2) Typical output voltage dependent on filter and unit type.

3)Maximum power loss with continuous motor current.

4)With IP21 protective top cover (110mm).

5) Option L10 included (strengthened dv/dt filter; strengthened filter is integrated in unit).

6) On request.

500 V, 6‑pulse

Line voltage, supply system type

400, 415, 460, 500V3ACIT/TT/TN

SINAMICS G180
cabinet units air-cooled

6SE0180‑1BD33‑7❑A7

6SE0180‑1BD34‑6❑A7

6SE0180‑1BD36‑3❑A7

6SE0180‑1BD37‑3❑A7

6SE0180‑1BD38‑2❑A7

Converter type (air-cooled)

2T3A‑87501‑250

2T3A‑87501‑315

2T3A‑87501‑400

2T3A‑87501‑500

2T3A‑87501‑560

SINAMICS G180
cabinet units liquid-cooled

6SE0170‑1BD33‑7❑A7

6SE0170‑1BD34‑6❑A7

6SE0170‑1BD36‑3❑A7

6SE0170‑1BD37‑3❑A7

6SE0170‑1BD38‑2❑A7

Converter type (liquid-cooled)

2T6A‑77501‑250

2T6A‑77501‑315

2T6A‑77501‑400

2T6A‑77501‑500

2T6A‑77501‑560

Electrical data at motor end

Type rating 1)

  • at 50 Hz 500 V

kW

250

315

400

500

560

  • at 60 Hz 460 V

hp

309

389

494

617

691

Output voltage2)

V

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

Output current

  • Continuous current

A

370

460

640

730

820

  • Short-time current
    (60s every 10minutes) max.

A

450

560

700

900

980

Overload capability
(60s every 10minutes) max.

%

22

22

9

23

20

Output power

kVA

320

398

554

632

710

Output frequency, max.

Hz

250

250

250

120

120

Rated clock cycle

kHz

3

3

2.4

2.4

2.4

adjustable from

kHz

2...5

2...5

1.5...3.7

1.5...3.7

1.5...3.7

Power loss 3)

kW

6.15

7.39

9.37

12.8

13.7

Rated efficiency

%

97.7

97.8

97.8

97.6

97.7

Electrical data at line end

Connected load

kVA

303

378

515

606

678

Rated input voltage

V

500

500

500

500

500

Input current

  • Continuous line current

A

350

437

595

700

783

  • Short-time line current (60s) max.

A

426

532

651

863

936

Line fuse (provided by customer)

gL(A)

400

500

630

800

800

λline

0.918

0.916

0.936

0.942

0.944

Cosφline

1

1

1

1

1

Radio interference suppression acc. to EN61800‑34)

C3 (class A filter)

C3 (class A filter)

C3 (class A filter)

C3 (class A filter)

C3 (class A filter)

Mechanical data for air-cooled cabinet units

Frame size (dimensional drawing classification)

SL2

SL2

SL2

SL21

SL3

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

70

73

73

75

75

Standard converter dimensions

  • Width

mm

806

806

806

1206

1606

  • Height5)

mm

2112

2112

2112

2112

2112

  • Depth

mm

605

605

605

605

605

Coolant requirements

m3/h

1900

1900

1900

2250

3200

Weight, approx.

kg

490

510

530

780

890

Mechanical data for liquid-cooled cabinet units

Frame size (dimensional drawing classification)

SW2

SW2

SW2

SW21

SW3

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

68

71

71

73

73

Standard converter dimensions

  • Width

mm

806

806

806

1206

1806

  • Height

mm

2202

2202

2202

2202

2202

  • Depth

mm

605

605

605

605

605

Coolant requirements

l/h

1200

1200

1200

1200

2000

Min. coolant pressure

bar

2.5

2.5

2.5

2.5

2.5

Max. coolant pressure

bar

6

6

6

6

6

Coolant test pressure

bar

10

10

10

10

10

Coolant pressure loss

bar

1.9

1.9

1.9

1.9

1.9

Min. coolant temperature

C

10

10

10

10

10

Max. coolant temperature

C

35

35

35

30

35

Weight, approx.

kg

490

510

530

850

920

General mechanical data

Max. cable length between converter and motor with standard insulation

(shielded)

m

2506)

2506)

2506)

2506)

2506)

Line/load connection

L1, L2, L3/U2, V2, W2

For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"

Approvals, according to

NRTL7)

NRTL7)

NRTL7)

NRTL7)

NRTL7)



1)Rated power of a typical 2- to 6-pole standard motor.

2) Typical output voltage dependent on filter and unit type.

3)Maximum power loss with continuous motor current.

4)EMC filter not required for IT system, in which case RI suppression category C4.

5)With IP21 protective top cover (110mm).

6) Option L10 included (strengthened dv/dt filter; strengthened filter is integrated in unit).

7) On request.

Line voltage, supply system type

400, 415, 460, 500V3ACIT/TT/TN

SINAMICS G180
cabinet units air-cooled

6SE0180‑1BD38‑8❑A7

6SE0180‑1BD41‑0❑A7

6SE0180‑1BD41‑1❑A7

Converter type (air-cooled)

2T3A‑87501‑630

2T3A‑87501‑710

2T3A‑87501‑800

SINAMICS G180
cabinet units liquid-cooled

6SE0170‑1BD38‑8❑A7

6SE0170‑1BD41‑0❑A7

6SE0170‑1BD41‑1❑A7

Converter type (liquid-cooled)

2T6A‑77501‑630

2T6A‑77501‑710

2T6A‑77501‑800

Electrical data at motor end

Type rating 1)

  • at 50 Hz 500 V

kW

630

710

800

  • at 60 Hz 460 V

hp

777

876

987

Output voltage2)

V

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

Output current

  • Continuous current

A

920

1030

1150

  • Short-time current
    (60s every 10minutes) max.

A

1100

1230

1380

Overload capability
(60s every 10minutes) max.

%

20

19

20

Output power

kVA

797

892

996

Output frequency, max.

Hz

120

120

120

Rated clock cycle

kHz

2.4

2.4

2.4

adjustable from

kHz

1.5...3.7

1.5...3.7

1.5...3.7

Power loss 3)

kW

15.4

18.1

20.3

Rated efficiency

%

97.7

97.6

97.6

Electrical data at line end

Connected load

kVA

767

848

944

Rated input voltage

V

500

500

500

Input current

  • Continuous line current

A

886

979

1090

  • Short-time line current (60s) max.

A

1059

1169

1308

Line fuse (provided by customer)

gL(A)

900

1000

1250

λline

0.946

0.948

0.95

Cosφline

1

1

1

Radio interference suppression acc. to EN61800‑34)

C3 (class A filter)

C3 (class A filter)

C3 (class A filter)

Mechanical data for air-cooled cabinet units

Frame size (dimensional drawing classification)

SL3

SL3

SL3

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

75

75

75

Standard converter dimensions

  • Width

mm

1606

1606

1606

  • Height5)

mm

2112

2112

2112

  • Depth

mm

605

605

605

Coolant requirements

m3/h

3800

3200

3800

Weight, approx.

kg

900

930

980

Mechanical data for liquid-cooled cabinet units

Frame size (dimensional drawing classification)

SW3

SW3

SW3

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

73

73

73

Standard converter dimensions

  • Width

mm

1806

1806

1806

  • Height

mm

2202

2202

2202

  • Depth

mm

605

605

605

Coolant requirements

l/h

2000

2000

2000

Min. coolant pressure

bar

2.5

2.5

2.5

Max. coolant pressure

bar

6

6

6

Coolant test pressure

bar

10

10

10

Coolant pressure loss

bar

1.9

1.9

1.9

Min. coolant temperature

C

10

10

10

Max. coolant temperature

C

35

35

30

Weight, approx.

kg

930

960

1010

General mechanical data

Max. cable length between converter and motor with standard insulation

(shielded)

m

2506)

2506)

2506)

Line/load connection

L1, L2, L3/U2, V2, W2

For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"

Approvals, according to

NRTL7)

NRTL7)

NRTL7)



1)Rated power of a typical 2- to 6-pole standard motor.

2) Typical output voltage dependent on filter and unit type.

3)Maximum power loss with continuous motor current.

4)EMC filter not required for IT system, in which case RI suppression category C4.

5)With IP21 protective top cover (110mm).

6) Option L10 included (strengthened dv/dt filter; strengthened filter is integrated in unit).

7) On request.

500 V, 12‑pulse

Line voltage, supply system type

2×400, 415, 460, 500V3AC IT

SINAMICS G180
cabinet units air-cooled

6SE0180‑2BD33‑7❑A7

6SE0180‑2BD34‑6❑A7

6SE0180‑2BD36‑3❑A7

6SE0180‑2BD37‑3❑A7

6SE0180‑2BD38‑2❑A7

Converter type (air-cooled)

2T3F‑87501‑250

2T3F‑87501‑315

2T3F‑87501‑400

2T3F‑87501‑500

2T3F‑87501‑560

SINAMICS G180
cabinet units liquid-cooled

6SE0170‑2BD33‑7❑A7

6SE0170‑2BD34‑6❑A7

6SE0170‑2BD36‑3❑A7

6SE0170‑2BD37‑3❑A7

6SE0170‑2BD38‑2❑A7

Converter type (liquid-cooled)

2T6F‑77501‑250

2T6F‑77501‑315

2T6F‑77501‑400

2T6F‑77501‑500

2T6F‑77501‑560

Electrical data at motor end

Type rating 1)

  • at 50 Hz 500 V

kW

250

315

400

500

560

  • at 60 Hz 460 V

hp

309

389

494

617

691

Output voltage2)

V

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

Output current

  • Continuous current

A

370

460

640

730

820

  • Short-time current
    (60s every 10minutes) max.

A

450

560

700

900

980

Overload capability
(60s every 10minutes) max.

%

22

22

9

23

20

Output power

kVA

320

398

554

632

710

Output frequency, max.

Hz

250

250

250

120

120

Rated clock cycle

kHz

3

3

2.4

2.4

2.4

adjustable from

kHz

2...5

2...5

1.5...3.7

1.5...3.7

1.5...3.7

Power loss 3)

kW

6.15

7.39

9.37

12.8

13.7

Rated efficiency

%

97.7

97.8

97.8

97.6

97.7

Electrical data at line end

Connected load

kVA

303

378

516

606

677

Rated input voltage

V

2 × 500

2 × 500

2 × 500

2 × 500

2 × 500

Input current

  • Continuous line current

A

2 × 175

2 × 218

2 × 298

2 × 350

2 × 391

  • Short-time line current (60s) max.

A

2 × 213

2 × 265

2 × 326

2 × 432

2 × 467

Line fuse (provided by customer)

gL(A)

200

250

400

400

500

λline

0.994

0.994

0.994

0.996

0.996

Cosφline

1

1

1

1

1

Radio interference suppression acc. to EN61800‑3

C4

C4

C4

C4

C4

Mechanical data for air-cooled cabinet units

Frame size (dimensional drawing classification)

SL5

SL5

SL5

SL5

SL6

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

70

73

73

75

75

Standard converter dimensions

  • Width

mm

1406

1406

1406

1406

1806

  • Height4)

mm

2112

2112

2112

2112

2112

  • Depth

mm

605

605

605

605

605

Coolant requirements

m3/h

1900

1900

1900

2250

3200

Weight, approx.

kg

690

710

730

810

920

Mechanical data for liquid-cooled cabinet units

Frame size (dimensional drawing classification)

SW5

SW5

SW5

SW5

SW6

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

68

71

71

73

73

Standard converter dimensions

  • Width

mm

1406

1406

1406

1406

2006

  • Height

mm

2202

2202

2202

2202

2202

  • Depth

mm

605

605

605

605

605

Coolant requirements

l/h

1200

1200

1200

1200

2000

Min. coolant pressure

bar

2.5

2.5

2.5

2.5

2.5

Max. coolant pressure

bar

6

6

6

6

6

Coolant test pressure

bar

10

10

10

10

10

Coolant pressure loss

bar

1.9

1.9

1.9

1.9

1.9

Min. coolant temperature

C

10

10

10

10

10

Max. coolant temperature

C

35

35

35

30

35

Weight, approx.

kg

690

710

730

810

950

General mechanical data

Max. cable length between converter and motor with standard insulation

(shielded)

m

2505)

2505)

2505)

2505)

2505)

Line/load connection

L1, L2, L3/U2, V2, W2

For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"

Approvals, according to

NRTL6)

NRTL6)

NRTL6)

NRTL6)

NRTL6)



1)Rated power of a typical 2- to 6-pole standard motor.

2) Typical output voltage dependent on filter and unit type.

3)Maximum power loss with continuous motor current.

4)With IP21 protective top cover (110mm).

5) Option L10 included (strengthened dv/dt filter; strengthened filter is integrated in unit).

6) On request.

Line voltage, supply system type

2×400, 415, 460, 500V3AC IT

SINAMICS G180
cabinet units air-cooled

6SE0180‑2BD38‑8❑A7

6SE0180‑2BD41‑0❑A7

6SE0180‑2BD41‑1❑A7

Converter type (air-cooled)

2T3F‑87501‑630

2T3F‑87501‑710

2T3F‑87501‑800

SINAMICS G180
cabinet units liquid-cooled

6SE0170‑2BD38‑8❑A7

6SE0170‑2BD41‑0❑A7

6SE0170‑2BD41‑1❑A7

Converter type (liquid-cooled)

2T6F‑77501‑630

2T6F‑77501‑710

2T6F‑77501‑800

Electrical data at motor end

Type rating 1)

  • at 50 Hz 500 V

kW

630

710

800

  • at 60 Hz 460 V

hp

777

876

987

Output voltage2)

V

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

Output current

  • Continuous current

A

920

1030

1150

  • Short-time current
    (60s every 10minutes) max.

A

1100

1230

1380

Overload capability
(60s every 10minutes) max.

%

20

19

20

Output power

kVA

797

892

996

Output frequency, max.

Hz

120

120

120

Rated clock cycle

kHz

2.4

2.4

2.4

adjustable from

kHz

1.5...3.7

1.5...3.7

1.5...3.7

Power loss 3)

kW

15.4

18.1

20.3

Rated efficiency

%

97.7

97.6

97.6

Electrical data at line end

Connected load

kVA

767

849

944

Rated input voltage

V

2 × 500

2 × 500

2 × 500

Input current

  • Continuous line current

A

2 × 443

2 × 490

2 × 545

  • Short-time line current (60s) max.

A

2 × 530

2 × 585

2 × 654

Line fuse (provided by customer)

gL(A)

500

630

630

λline

0.996

0.996

0.997

Cosφline

1

1

1

Radio interference suppression acc. to EN61800‑3

C4

C4

C4

Mechanical data for air-cooled cabinet units

Frame size (dimensional drawing classification)

SL6

SL6

SL6

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

75

75

75

Standard converter dimensions

  • Width

mm

1806

1806

1806

  • Height4)

mm

2112

2112

2112

  • Depth

mm

605

605

605

Coolant requirements

m3/h

3800

3200

3800

Weight, approx.

kg

930

960

1010

Mechanical data for liquid-cooled cabinet units

Frame size (dimensional drawing classification)

SW6

SW6

SW6

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

73

73

73

Standard converter dimensions

  • Width

mm

2006

2006

2006

  • Height

mm

2202

2202

2202

  • Depth

mm

605

605

605

Coolant requirements

l/h

2000

2000

2000

Min. coolant pressure

bar

2.5

2.5

2.5

Max. coolant pressure

bar

6

6

6

Coolant test pressure

bar

10

10

10

Coolant pressure loss

bar

1.9

1.9

1.9

Min. coolant temperature

C

10

10

10

Max. coolant temperature

C

35

35

30

Weight, approx.

kg

960

990

1040

General mechanical data

Max. cable length between converter and motor with standard insulation

(shielded)

m

2505)

2505)

2505)

Line/load connection

L1, L2, L3/U2, V2, W2

For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"

Approvals, according to

NRTL6)

NRTL6)

NRTL6)



1)Rated power of a typical 2- to 6-pole standard motor.

2) Typical output voltage dependent on filter and unit type.

3)Maximum power loss with continuous motor current.

4)With IP21 protective top cover (110mm).

5) Option L10 included (strengthened dv/dt filter; strengthened filter is integrated in unit).

6) On request

690 V, 6‑pulse

Line voltage, supply system type

400, 415, 460, 500, 575, 690V3AC TT/TN or IT

SINAMICS G180
cabinet units air-cooled

6SE0180‑1B❑33‑2❑A7

6SE0180‑1B❑33‑6❑A7

6SE0180‑1B❑34‑2❑A7

6SE0180‑1B❑35‑2❑A7

6SE0180‑1B❑35‑7❑A7

Converter type (air-cooled)

2T3A‑87601‑250

2T3A‑87601‑315

2T3A‑87601‑400

2T3A‑87601‑500

2T3A‑87601‑560

SINAMICS G180
cabinet units liquid-cooled

6SE0170‑1B❑33‑2❑A7

6SE0170‑1B❑33‑6❑A7

6SE0170‑1B❑34‑2❑A7

6SE0170‑1B❑35‑2❑A7

6SE0170‑1B❑35‑7❑A7

Converter type (liquid-cooled)

2T6A‑77601‑250

2T6A‑77601‑315

2T6A‑77601‑400

2T6A‑77601‑500

2T6A‑77601‑560

Electrical data at motor end

Type rating 1)

  • at 50 Hz 690 V

kW

250

315

400

500

560

  • at 60 Hz 575 V

hp

279

352

447

559

626

Output voltage2)

V

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

Output current

  • Continuous current

A

270

340

440

530

590

  • Short-time current
    (60s every 10minutes) max.

A

320

410

510

640

710

Overload capability
(60s every 10minutes) max.

%

19

21

16

21

20

Output power

kVA

323

406

526

633

705

Output frequency, max.

Hz

250

250

250

120

120

Rated clock cycle

kHz

3

3

2.4

2.4

2.4

adjustable from

kHz

2...5

2...5

1.5...3.7

1.5...3.7

1.5...3.7

Power loss 3)

kW

6.15

7.73

9.37

12.2

13.7

Rated efficiency

%

97.7

97.7

97.8

97.7

97.7

Electrical data at line end

Connected load

kVA

312

391

502

608

676

Rated input voltage

V

690

690

690

690

690

Input current

  • Continuous line current

A

261

327

420

509

566

  • Short-time line current (60s) max.

A

309

394

487

615

681

Line fuse (provided by customer)

gL(A)

315

400

500

630

630

λline

0.901

0.905

0.91

0.939

0.94

Cosφline

1

1

1

1

1

Radio interference suppression acc. to EN61800‑34)

C3 (class A filter)

C3 (class A filter)

C3 (class A filter)

C3 (class A filter)

C3 (class A filter)

Mechanical data for air-cooled cabinet units

Frame size (dimensional drawing classification)

SL2

SL2

SL2

SL21

SL3

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

70

70

70

75

75

Standard converter dimensions

  • Width

mm

806

806

806

1206

1606

  • Height5)

mm

2112

2112

2112

2112

2112

  • Depth

mm

605

605

605

605

605

Coolant requirements

m3/h

1900

1900

1900

2650

3200

Weight, approx.

kg

490

510

530

780

890

Mechanical data for liquid-cooled cabinet units

Frame size (dimensional drawing classification)

SW2

SW2

SW2

SW21

SW3

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

68

68

68

73

73

Standard converter dimensions

  • Width

mm

806

806

806

1206

1806

  • Height

mm

2202

2202

2202

2202

2202

  • Depth

mm

605

605

605

605

605

Coolant requirements

l/h

1200

1200

1200

1200

2000

Min. coolant pressure

bar

2.5

2.5

2.5

2.5

2.5

Max. coolant pressure

bar

6

6

6

6

6

Coolant test pressure

bar

10

10

10

10

10

Coolant pressure loss

bar

1.9

1.9

1.9

1.9

1.9

Min. coolant temperature

C

10

10

10

10

10

Max. coolant temperature

C

35

35

35

30

35

Weight, approx.

kg

490

510

530

850

920

General mechanical data

Max. cable length between converter and motor with standard insulation

(shielded)

m

100/2506)

100/250 6)

100/2506)

100/2506)

100/2507)

Line/load connection

L1, L2, L3/U2, V2, W2

For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"

Approvals, according to

NRTL8)

NRTL8)

NRTL8)

NRTL8)

NRTL8)



1)Rated power of a typical 2- to 6-pole standard motor.

2) Typical output voltage dependent on filter and unit type.

3)Maximum power loss with continuous motor current.

4)EMC filter not required for IT system, in which case RI suppression category C4.

5)With IP21 protective top cover (110mm).

6) Value is applicable with option L10 (strengthened dv/dt filter; filter is integrated in additional 400 mm cabinet).

7) Value is applicable with option L10 (strengthened dv/dt filter; filter is integrated in unit).

8) On request; the voltage range for NRTL units ends at max. 600V.

Line voltage, supply system type

400, 415, 460, 500, 575, 690V3AC TT/TN or IT

SINAMICS G180
cabinet units air-cooled

6SE0180‑1B❑36‑4❑A7

6SE0180‑1B❑37‑1❑A7

6SE0180‑1B❑37‑7❑A7

6SE0180‑1B❑41‑0❑A7

6SE0180‑1B❑41‑1❑A7

Converter type (air-cooled)

2T3A‑87601‑630

2T3A‑87601‑710

2T3A‑87601‑800

2T3A‑87601‑909

2T3A‑87601‑910

SINAMICS G180
cabinet units liquid-cooled

6SE0170‑1B❑36‑4❑A7

6SE0170‑1B❑37‑1❑A7

6SE0170‑1B❑37‑7❑A7

6SE0170‑1B❑41‑0❑A7

6SE0170‑1B❑41‑1❑A7

Converter type (liquid-cooled)

2T6A‑77601‑630

2T6A‑77601‑710

2T6A‑77601‑800

2T6A‑77601‑909

2T6A‑77601‑910

Electrical data at motor end

Type rating 1)

  • at 50 Hz 690 V

kW

630

710

800

900

1000

  • at 60 Hz 575 V

hp

704

794

894

1006

1118

Output voltage2)

V

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

Output current

  • Continuous current

A

660

750

840

950

1040

  • Short-time current
    (60s every 10minutes) max.

A

800

890

980

1060

1130

Overload capability
(60s every 10minutes) max.

%

21

19

17

12

9

Output power

kVA

789

896

1004

1135

1243

Output frequency, max.

Hz

120

120

120

120

120

Rated clock cycle

kHz

2.4

2.4

2.4

2.4

2.4

adjustable from

kHz

1.5...3.7

1.5...3.7

1.5...3.7

1.5...3.7

1.5...3.7

Power loss 3)

kW

15.4

16.6

18.7

21

23.3

Rated efficiency

%

97.7

97.8

97.8

97.8

97.8

Electrical data at line end

Connected load

kVA

764

854

956

1078

1165

Rated input voltage

V

690

690

690

690

690

Input current

  • Continuous line current

A

639

715

800

902

975

  • Short-time line current (60s) max.

A

774

848

933

1006

1059

Line fuse (provided by customer)

gL(A)

800

800

900

1000

1000

λline

0.942

0.944

0.945

0.947

0.949

Cosφline

1

1

1

1

1

Radio interference suppression acc. to EN61800‑34)

C3 (class A filter)

C3 (class A filter)

C3 (class A filter)

C3 (class A filter)

C3 (class A filter)

Mechanical data for air-cooled cabinet units

Frame size (dimensional drawing classification)

SL3

SL3

SL3

SL3

SL3

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

75

75

75

75

75

Standard converter dimensions

  • Width

mm

1606

1606

1606

1606

1606

  • Height5)

mm

2112

2112

2112

2112

2112

  • Depth

mm

605

605

605

605

605

Coolant requirements

m3/h

3200

3800

3200

3800

3800

Weight, approx.

kg

890

900

930

980

1030

Mechanical data for liquid-cooled cabinet units

Frame size (dimensional drawing classification)

SW3

SW3

SW3

SW3

SW3

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

73

73

73

73

73

Standard converter dimensions

  • Width

mm

1806

1806

1806

1806

1806

  • Height

mm

2202

2202

2202

2202

2202

  • Depth

mm

605

605

605

605

605

Coolant requirements

l/h

2000

2000

2000

2000

2000

Min. coolant pressure

bar

2.5

2.5

2.5

2.5

2.5

Max. coolant pressure

bar

6

6

6

6

6

Coolant test pressure

bar

10

10

10

10

10

Coolant pressure loss

bar

1.9

1.9

1.9

1.9

1.9

Min. coolant temperature

C

10

10

10

10

10

Max. coolant temperature

C

35

35

35

30

28

Weight, approx.

kg

920

930

960

1010

1060

General mechanical data

Max. cable length between converter and motor with standard insulation

(shielded)

m

100/2506)

100/2506)

100/2507)

100/2507)

100/2507)

Line/load connection

L1, L2, L3/U2, V2, W2

For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"

Approvals, according to

NRTL8)

NRTL8)

NRTL8)

NRTL8)

NRTL8)



1)Rated power of a typical 2- to 6-pole standard motor.

2) Typical output voltage dependent on filter and unit type.

3)Maximum power loss with continuous motor current.

4)EMC filter not required for IT system, in which case RI suppression category C4.

5)With IP21 protective top cover (110mm).

6) Value is applicable with option L10 (strengthened dv/dt filter; filter is integrated in unit).

7) Value is applicable with option L10 (strengthened dv/dt filter; filter is integrated in additional 600 mm cabinet).

8) On request; the voltage range for NRTL units ends at max. 600V.

Line voltage, supply system type

400, 415, 460, 500, 575, 690V3AC TT/TN or IT

SINAMICS G180
cabinet units air-cooled

6SE0180‑1C❑41‑2❑A7

6SE0180‑1C❑41‑3❑A7

6SE0180‑1C❑41‑5❑A7

6SE0180‑1C❑41‑7❑A7

6SE0180‑1C❑42‑0❑A7

Converter type (air-cooled)

2T3A‑87602‑912

2T3A‑87602‑913

2T3A‑87602‑915

2T3A‑87602‑917

2T3A‑87602‑919

SINAMICS G180
cabinet units liquid-cooled

6SE0170‑1C❑41‑2❑A7

6SE0170‑1C❑41‑3❑A7

6SE0170‑1C❑41‑5❑A7

6SE0170‑1C❑41‑7❑A7

6SE0170‑1C❑42‑0❑A7

Converter type (liquid-cooled)

2T6A‑77602‑912

2T6A‑77602‑913

2T6A‑77602‑915

2T6A‑77602‑917

2T6A‑77602‑919

Electrical data at motor end

Type rating 1)

  • at 50 Hz 690 V

kW

1200

1300

1500

1700

1900

  • at 60 Hz 575 V

hp

1341

1453

1676

1900

2123

Output voltage2)

V

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

Output current

  • Continuous current

A

1260

1430

1600

1810

1980

  • Short-time current
    (60s every 10minutes) max.

A

1520

1700

1870

2020

2150

Overload capability
(60s every 10minutes) max.

%

21

19

17

12

9

Output power

kVA

1506

1709

1912

2163

2366

Output frequency, max.

Hz

120

120

120

120

120

Rated clock cycle

kHz

2.4

2.4

2.4

2.4

2.4

adjustable from

kHz

1.5...3.7

1.5...3.7

1.5...3.7

1.5...3.7

1.5...3.7

Power loss 3)

kW

28.2

33.6

37.5

42.6

46.5

Rated efficiency

%

97.8

97.7

97.7

97.7

97.7

Electrical data at line end

Connected load

kVA

1410

1603

1795

2030

2220

Rated input voltage

V

690

690

690

690

690

Input current

  • Continuous line current

A

1180

1341

1502

1699

1858

  • Short-time line current (60s) max.

A

1424

1594

1756

1896

2018

Line fuse (provided by customer)

gL(A)

1250

1500

1600

1800

2000

λline

0.952

0.954

0.956

0.958

0.96

Cosφline

1

1

1

1

1

Radio interference suppression acc. to EN61800‑34)

C3 (class A filter)

C3 (class A filter)

C3 (class A filter)

C3 (class A filter)

C3 (class A filter)

Mechanical data for air-cooled cabinet units

Frame size (dimensional drawing classification)

SL4

SL4

SL4

SL4

SL4

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

77

77

77

77

77

Standard converter dimensions

  • Width

mm

3206

3206

3206

3206

3206

  • Height5)

mm

2112

2112

2112

2112

2112

  • Depth

mm

605

605

605

605

605

Coolant requirements

m3/h

6400

7600

6400

7600

7600

Weight, approx.

kg

1780

1800

1860

1960

2060

Mechanical data for liquid-cooled cabinet units

Frame size (dimensional drawing classification)

SW4

SW4

SW4

SW4

SW4

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

75

75

75

75

75

Standard converter dimensions

  • Width

mm

3606

3606

3606

3606

3606

  • Height

mm

2202

2202

2202

2202

2202

  • Depth

mm

605

605

605

605

605

Coolant requirements

l/h

4000

4000

4000

4000

4000

Min. coolant pressure

bar

2.5

2.5

2.5

2.5

2.5

Max. coolant pressure

bar

6

6

6

6

6

Coolant test pressure

bar

10

10

10

10

10

Coolant pressure loss

bar

1.9

1.9

1.9

1.9

1.9

Min. coolant temperature

C

10

10

10

10

10

Max. coolant temperature

C

35

35

35

30

28

Weight, approx.

kg

1840

1860

1920

2020

2120

General mechanical data

Max. cable length between converter and motor with standard insulation

(shielded)

m

100/2506)

100/2506)

100/2507)

100/2507)

100/2507)

Line/load connection

L1, L2, L3/U2, V2, W2

For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"

Approvals, according to

NRTL8)

NRTL8)

NRTL8)

NRTL8)

NRTL8)



1)Rated power of a typical 2- to 6-pole standard motor.

2) Typical output voltage dependent on filter and unit type.

3)Maximum power loss with continuous motor current.

4)EMC filter not required for IT system, in which case RI suppression category C4.

5)With IP21 protective top cover (110mm).

6) Value is applicable with option L10 (strengthened dv/dt filter; filter is integrated in unit).

7) Value is applicable with option L10 (strengthened dv/dt filter; filter is integrated in additional 2 x 600 mm cabinet).

8) On request; the voltage range for NRTL units ends at max. 600V.

690 V, 12‑pulse

Line voltage, supply system type

2×400, 415, 460, 500, 575, 690V3AC IT

SINAMICS G180
cabinet units air-cooled

6SE0180‑2BH33‑2❑A7

6SE0180‑2BH33‑6❑A7

6SE0180‑2BH34‑2❑A7

6SE0180‑2BH35‑2❑A7

6SE0180‑2BH35‑7❑A7

Converter type (air-cooled)

2T3F‑87601‑250

2T3F‑87601‑315

2T3F‑87601‑400

2T3F‑87601‑500

2T3F‑87601‑560

SINAMICS G180
cabinet units liquid-cooled

6SE0170‑2BH33‑2❑A7

6SE0170‑2BH33‑6❑A7

6SE0170‑2BH34‑2❑A7

6SE0170‑2BH35‑2❑A7

6SE0170‑2BH35‑7❑A7

Converter type (liquid-cooled)

2T6F‑77601‑250

2T6F‑77601‑315

2T6F‑77601‑400

2T6F‑77601‑500

2T6F‑77601‑560

Electrical data at motor end

Type rating 1)

  • at 50 Hz 690 V

kW

250

315

400

500

560

  • at 60 Hz 575 V

hp

279

352

447

559

626

Output voltage2)

V

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

Output current

  • Continuous current

A

270

340

440

530

590

  • Short-time current
    (60s every 10minutes) max.

A

320

410

510

640

710

Overload capability
(60s every 10minutes) max.

%

19

21

16

21

20

Output power

kVA

323

406

526

633

705

Output frequency, max.

Hz

250

250

250

120

120

Rated clock cycle

kHz

3

3

2.4

2.4

2.4

adjustable from

kHz

2...5

2...5

1.5...3.7

1.5...3.7

1.5...3.7

Power loss 3)

kW

6.15

7.73

9.37

12.2

13.7

Rated efficiency

%

97.7

97.7

97.8

97.7

97.7

Electrical data at line end

Connected load

kVA

311

392

502

600

667

Rated input voltage

V

2×690

2×690

2×690

2×690

2×690

Input current

  • Continuous line current

A

2×130

2×164

2×210

2×251

2×279

  • Short-time line current (60s) max.

A

2×154

2×198

2×243

2×303

2×336

Line fuse (provided by customer)

gL(A)

160

200

250

315

315

λline

0.995

0.995

0.995

0.997

0.997

Cosφline

1

1

1

1

1

Radio interference suppression acc. to EN61800‑3

C4

C4

C4

C4

C4

Mechanical data for air-cooled cabinet units

Frame size (dimensional drawing classification)

SL5

SL5

SL5

SL5

SL6

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

70

70

70

75

75

Standard converter dimensions

  • Width

mm

1406

1406

1406

1406

1806

  • Height4)

mm

2112

2112

2112

2112

2112

  • Depth

mm

605

605

605

605

605

Coolant requirements

m3/h

1900

1900

1900

2650

3200

Weight, approx.

kg

690

710

730

810

920

Mechanical data for liquid-cooled cabinet units

Frame size (dimensional drawing classification)

SW5

SW5

SW5

SW5

SW6

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

68

68

68

73

73

Standard converter dimensions

  • Width

mm

1406

1406

1406

1406

2006

  • Height

mm

2202

2202

2202

2202

2202

  • Depth

mm

605

605

605

605

605

Coolant requirements

l/h

1200

1200

1200

1200

2000

Min. coolant pressure

bar

2.5

2.5

2.5

2.5

2.5

Max. coolant pressure

bar

6

6

6

6

6

Coolant test pressure

bar

10

10

10

10

10

Coolant pressure loss

bar

1.9

1.9

1.9

1.9

1.9

Min. coolant temperature

C

10

10

10

10

10

Max. coolant temperature

C

35

35

35

30

35

Weight, approx.

kg

690

710

730

810

950

General mechanical data

Max. cable length between converter and motor with standard insulation

(shielded)

m

100/2505)

100/2505)

100/2505)

100/2505)

100/2506)

Line/load connection

L1, L2, L3/U2, V2, W2

For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"

Approvals, according to

NRTL7)

NRTL7)

NRTL7)

NRTL7)

NRTL7)



1)Rated power of a typical 2- to 6-pole standard motor.

2) Typical output voltage dependent on filter and unit type.

3)Maximum power loss with continuous motor current.

4)With IP21 protective top cover (110mm).

5) Value is applicable with option L10 (strengthened dv/dt filter; filter is integrated in additional 400 mm cabinet).

6) Value is applicable with option L10 (strengthened dv/dt filter; filter is integrated in unit).

7) On request; the voltage range for NRTL units ends at max. 600V.

Line voltage, supply system type

2×400, 415, 460, 500, 575, 690V3AC IT

SINAMICS G180
cabinet units air-cooled

6SE0180‑2BH36‑4❑A7

6SE0180‑2BH37‑1❑A7

6SE0180‑2BH37‑7❑A7

6SE0180‑2BH41‑0❑A7

6SE0180‑2BH41‑1❑A7

Converter type (air-cooled)

2T3F‑87601‑630

2T3F‑87601‑710

2T3F‑87601‑800

2T3F‑87601‑909

2T3F‑87601‑910

SINAMICS G180
cabinet units liquid-cooled

6SE0170‑2BH36‑4❑A7

6SE0170‑2BH37‑1❑A7

6SE0170‑2BH37‑7❑A7

6SE0170‑2BH41‑0❑A7

6SE0170‑2BH41‑1❑A7

Converter type (liquid-cooled)

2T6F‑77601‑630

2T6F‑77601‑710

2T6F‑77601‑800

2T6F‑77601‑909

2T6F‑77601‑910

Electrical data at motor end

Type rating 1)

  • at 50 Hz 690 V

kW

630

710

800

900

1000

  • at 60 Hz 575 V

hp

704

794

894

1006

1118

Output voltage2)

V

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

Output current

  • Continuous current

A

660

750

840

950

1040

  • Short-time current
    (60s every 10minutes) max.

A

800

890

980

1060

1130

Overload capability
(60s every 10minutes) max.

%

21

19

17

12

9

Output power

kVA

789

896

1004

1135

1243

Output frequency, max.

Hz

120

120

120

120

120

Rated clock cycle

kHz

2.4

2.4

2.4

2.4

2.4

adjustable from

kHz

1.5...3.7

1.5...3.7

1.5...3.7

1.5...3.7

1.5...3.7

Power loss 3)

kW

15.4

16.6

18.7

21

23.3

Rated efficiency

%

97.7

97.8

97.8

97.8

97.8

Electrical data at line end

Connected load

kVA

755

848

949

1071

1159

Rated input voltage

V

2×690

2×690

2×690

2×690

2×690

Input current

  • Continuous line current

A

2×316

2×355

2×397

2×448

2×485

  • Short-time line current (60s) max.

A

2×383

2×421

2×463

2×500

2×527

Line fuse (provided by customer)

gL(A)

400

400

500

500

630

λline

0.997

0.997

0.997

0.997

0.997

Cosφline

1

1

1

1

1

Radio interference suppression acc. to EN61800‑3

C4

C4

C4

C4

C4

Mechanical data for air-cooled cabinet units

Frame size (dimensional drawing classification)

SL6

SL6

SL6

SL6

SL6

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

75

75

75

75

75

Standard converter dimensions

  • Width

mm

1806

1806

1806

1806

1806

  • Height4)

mm

2112

2112

2112

2112

2112

  • Depth

mm

605

605

605

605

605

Coolant requirements

m3/h

3200

3800

3200

3800

3800

Weight, approx.

kg

920

930

960

1010

1060

Mechanical data for liquid-cooled cabinet units

Frame size (dimensional drawing classification)

SW6

SW6

SW6

SW6

SW6

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

73

73

73

73

73

Standard converter dimensions

  • Width

mm

2006

2006

2006

2006

2006

  • Height

mm

2202

2202

2202

2202

2202

  • Depth

mm

605

605

605

605

605

Coolant requirements

l/h

2000

2000

2000

2000

2000

Min. coolant pressure

bar

2.5

2.5

2.5

2.5

2.5

Max. coolant pressure

bar

6

6

6

6

6

Coolant test pressure

bar

10

10

10

10

10

Coolant pressure loss

bar

1.9

1.9

1.9

1.9

1.9

Min. coolant temperature

C

10

10

10

10

10

Max. coolant temperature

C

35

35

35

30

28

Weight, approx.

kg

950

960

990

1040

1090

General mechanical data

Max. cable length between converter and motor with standard insulation

(shielded)

m

100/2505)

100/2505)

100/2506)

100/2506)

100/2506)

Line/load connection

L1, L2, L3/U2, V2, W2

For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"

Approvals, according to

NRTL7)

NRTL7)

NRTL7)

NRTL7)

NRTL7)



1)Rated power of a typical 2- to 6-pole standard motor.

2) Typical output voltage dependent on filter and unit type.

3)Maximum power loss with continuous motor current.

4)With IP21 protective top cover (110mm).

5) Value is applicable with option L10 (strengthened dv/dt filter; filter is integrated in unit).

6) Value is applicable with option L10 (strengthened dv/dt filter; filter is integrated in additional 600 mm cabinet).

7) On request; the voltage range for NRTL units ends at max. 600V.

Line voltage, supply system type

2×400, 415, 460, 500, 575, 690V3AC IT

SINAMICS G180
cabinet units air-cooled

6SE0180‑2CH41‑2❑A7

6SE0180‑2CH41‑3❑A7

6SE0180‑2CH41‑5❑A7

6SE0180‑2CH41‑7❑A7

6SE0180‑2CH42‑0❑A7

Converter type (air-cooled)

2T3F‑87602‑912

2T3F‑87602‑913

2T3F‑87602‑915

2T3F‑87602‑917

2T3F‑87602‑919

SINAMICS G180
cabinet units liquid-cooled

6SE0170‑2CH41‑2❑A7

6SE0170‑2CH41‑3❑A7

6SE0170‑2CH41‑5❑A7

6SE0170‑2CH41‑7❑A7

6SE0170‑2CH42‑0❑A7

Converter type (liquid-cooled)

2T6F‑77602‑912

2T6F‑77602‑913

2T6F‑77602‑915

2T6F‑77602‑917

2T6F‑77602‑919

Electrical data at motor end

Type rating 1)

  • at 50 Hz 690 V

kW

1200

1300

1500

1700

1900

  • at 60 Hz 575 V

hp

1341

1453

1676

1900

2123

Output voltage2)

V

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

Output current

  • Continuous current

A

1260

1430

1600

1810

1980

  • Short-time current
    (60s every 10minutes) max.

A

1520

1700

1870

2020

2150

Overload capability
(60s every 10minutes) max.

%

21

19

17

12

9

Output power

kVA

1506

1709

1912

2163

2366

Output frequency, max.

Hz

120

120

120

120

120

Rated clock cycle

kHz

2.4

2.4

2.4

2.4

2.4

adjustable from

kHz

1.5...3.7

1.5...3.7

1.5...3.7

1.5...3.7

1.5...3.7

Power loss 3)

kW

28.2

33.6

37.5

42.6

46.5

Rated efficiency

%

97.8

97.7

97.7

97.7

97.7

Electrical data at line end

Connected load

kVA

1405

1597

1781

2010

2194

Rated input voltage

V

2×690

2×690

2×690

2×690

2×690

Input current

  • Continuous line current

A

2×588

2×668

2×745

2×841

2×918

  • Short-time line current (60s) max.

A

2×709

2×794

2×871

2×939

2×997

Line fuse (provided by customer)

gL(A)

800

800

900

1000

1250

λline

0.997

0.997

0.997

0.997

0.997

Cosφline

1

1

1

1

1

Radio interference suppression acc. to EN61800‑3

C4

C4

C4

C4

C4

Mechanical data for air-cooled cabinet units

Frame size (dimensional drawing classification)

SL4

SL4

SL4

SL4

SL4

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

77

77

77

77

77

Standard converter dimensions

  • Width

mm

3206

3206

3206

3206

3206

  • Height4)

mm

2112

2112

2112

2112

2112

  • Depth

mm

605

605

605

605

605

Coolant requirements

m3/h

6400

7600

6400

7600

7600

Weight, approx.

kg

1780

1800

1860

1960

2060

Mechanical data for liquid-cooled cabinet units

Frame size (dimensional drawing classification)

SW4

SW4

SW4

SW4

SW4

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

75

75

75

75

75

Standard converter dimensions

  • Width

mm

3606

3606

3606

3606

3606

  • Height

mm

2202

2202

2202

2202

2202

  • Depth

mm

605

605

605

605

605

Coolant requirements

l/h

4000

4000

4000

4000

4000

Min. coolant pressure

bar

2.5

2.5

2.5

2.5

2.5

Max. coolant pressure

bar

6

6

6

6

6

Coolant test pressure

bar

10

10

10

10

10

Coolant pressure loss

bar

1.9

1.9

1.9

1.9

1.9

Min. coolant temperature

C

10

10

10

10

10

Max. coolant temperature

C

35

35

35

30

28

Weight, approx.

kg

1840

1860

1920

2020

2120

General mechanical data

Max. cable length between converter and motor with standard insulation

(shielded)

m

100/2505)

100/2505)

100/2506)

100/2506)

100/2506)

Line/load connection

L1, L2, L3/U2, V2, W2

For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"

Approvals, according to

NRTL7)

NRTL7)

NRTL7)

NRTL7)

NRTL7)



1)Rated power of a typical 2- to 6-pole standard motor.

2) Typical output voltage dependent on filter and unit type.

3)Maximum power loss with continuous motor current.

4)With IP21 protective top cover (110mm).

5) Value is applicable with option L10 (strengthened dv/dt filter; filter is integrated in unit).

6) Value is applicable with option L10 (strengthened dv/dt filter; filter is integrated in additional 2 x 600 mm cabinet).

7) On request; the voltage range for NRTL units ends at max. 600V.

Line voltage, supply system type

2×400, 415, 460, 500, 575, 690V3AC IT

SINAMICS G180
cabinet units air-cooled

6SE0180‑2DH42‑2❑A7

6SE0180‑2DH42‑4❑A7

6SE0180‑2DH42‑7❑A7

6SE0180‑2DH43‑0❑A7

6SE0180‑2EH43‑2❑A7

Converter type (air-cooled)

2T3F‑87603‑920

2T3F‑87603‑923

2T3F‑87603‑926

2T3F‑87603‑929

2T3F‑87604‑931

SINAMICS G180
cabinet units liquid-cooled

6SE0170‑2DH42‑2❑A7

6SE0170‑2DH42‑4❑A7

6SE0170‑2DH42‑7❑A7

6SE0170‑2DH43‑0❑A7

6SE0170‑2EH43‑2❑A7

Converter type (liquid-cooled)

2T6F‑77603‑920

2T6F‑77603‑923

2T6F‑77603‑926

2T6F‑77603‑929

2T6F‑77604‑931

Electrical data at motor end

Type rating 1)

  • at 50 Hz 690 V

kW

2000

2300

2600

2900

3100

  • at 60 Hz 575 V

hp

2235

2570

2906

3241

3465

Output voltage2)

V

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

Output current

  • Continuous current

A

2140

2400

2710

2970

3200

  • Short-time current
    (60s every 10minutes) max.

A

2540

2800

3030

3230

3730

Overload capability
(60s every 10minutes) max.

%

19

17

12

9

17

Output power

kVA

2558

2868

3239

3549

3824

Output frequency, max.

Hz

120

120

120

120

120

Rated clock cycle

kHz

2.4

2.4

2.4

2.4

2.4

adjustable from

kHz

1.5...3.7

1.5...3.7

1.5...3.7

1.5...3.7

1.5...3.7

Power loss 3)

kW

50.9

57.2

64.5

73.9

77.3

Rated efficiency

%

97.7

97.7

97.7

97.6

97.7

Electrical data at line end

Connected load

kVA

2369

2648

2983

3272

3516

Rated input voltage

V

2×690

2×690

2×690

2×690

2×690

Input current

  • Continuous line current

A

2×991

2×1108

2×1248

2×1369

2×1471

  • Short-time line current (60s) max.

A

2×1176

2×1293

2×1395

2×1489

2×1715

Line fuse (provided by customer)

gL(A)

1250

1250

1500

1600

1800

λline

0.997

0.997

0.997

0.997

0.997

Cosφline

1

1

1

1

1

Radio interference suppression acc. to EN61800‑3

C4

C4

C4

C4

C4

Mechanical data for air-cooled cabinet units

Frame size (dimensional drawing classification)

SL7

SL7

SL7

SL7

SL8

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

78

78

78

78

79

Standard converter dimensions

  • Width

mm

4806

4806

4806

4806

6406

  • Height4)

mm

2112

2112

2112

2112

2112

  • Depth

mm

605

605

605

605

605

Coolant requirements

m3/h

11400

9600

11400

11400

12800

Weight, approx.

kg

2700

2790

2940

3090

3720

Mechanical data for liquid-cooled cabinet units

Frame size (dimensional drawing classification)

SW7

SW7

SW7

SW7

SW8

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

76

76

76

76

77

Standard converter dimensions

  • Width

mm

5206

5206

5206

5206

7006

  • Height

mm

2202

2202

2202

2202

2202

  • Depth

mm

605

605

605

605

605

Coolant requirements

l/h

6000

6000

6000

6000

8000

Min. coolant pressure

bar

2.5

2.5

2.5

2.5

2.5

Max. coolant pressure

bar

6

6

6

6

6

Coolant test pressure

bar

10

10

10

10

10

Coolant pressure loss

bar

1.9

1.9

1.9

1.9

1.9

Min. coolant temperature

C

10

10

10

10

10

Max. coolant temperature

C

35

35

30

28

35

Weight, approx.

kg

2750

2850

2850

3100

3850

General mechanical data

Max. cable length between converter and motor with standard insulation

(shielded)

m

100/2505)

100/2506)

100/2506)

100/2506)

100/2507)

Line/load connection

L1, L2, L3/U2, V2, W2

For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"

Approvals, according to

NRTL8)

NRTL8)

NRTL8)

NRTL8)

NRTL8)



1)Rated power of a typical 2- to 6-pole standard motor.

2) Typical output voltage dependent on filter and unit type.

3)Maximum power loss with continuous motor current.

4)With IP21 protective top cover (110mm).

5) Value is applicable with option L10 (strengthened dv/dt filter; filter is integrated in unit).

6) Value is applicable with option L10 (strengthened dv/dt filter; filter is integrated in additional 3 x 600 mm cabinet).

7) Value is applicable with option L10 (strengthened dv/dt filter; filter is integrated in additional 4 x 600 mm cabinet).

8) On request; the voltage range for NRTL units ends at max. 600V.

Line voltage, supply system type

2×400, 415, 460, 500, 575, 690V3AC IT

SINAMICS G180
cabinet units air-cooled

6SE0180‑2EH43‑6❑A7

6SE0180‑2EH44‑0❑A7

Converter type (air-cooled)

2T3F‑87604‑935

2T3F‑87604‑939

SINAMICS G180
cabinet units liquid-cooled

6SE0170‑2EH43‑6❑A7

6SE0170‑2EH44‑0❑A7

Converter type (liquid-cooled)

2T6F‑77604‑935

2T6F‑77604‑939

Electrical data at motor end

Type rating 1)

  • at 50 Hz 690 V

kW

3500

3900

  • at 60 Hz 575 V

hp

3912

4359

Output voltage2)

V

0...0.98×Vline

0...0.98×Vline

Output current

  • Continuous current

A

3610

3960

  • Short-time current
    (60s every 10minutes) max.

A

4030

4300

Overload capability
(60s every 10minutes) max.

%

12

9

Output power

kVA

4314

4732

Output frequency, max.

Hz

120

120

Rated clock cycle

kHz

2.4

2.4

adjustable from

kHz

1.5...3.7

1.5...3.7

Power loss 3)

kW

87.3

99.7

Rated efficiency

%

97.7

97.6

Electrical data at line end

Connected load

kVA

3956

4336

Rated input voltage

V

2×690

2×690

Input current

  • Continuous line current

A

2×1655

2×1814

  • Short-time line current (60s) max.

A

2×1848

2×1970

Line fuse (provided by customer)

gL(A)

2000

2000

λline

0.997

0.997

Cosφline

1

1

Radio interference suppression acc. to EN61800‑3

C4

C4

Mechanical data for air-cooled cabinet units

Frame size (dimensional drawing classification)

SL8

SL8

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

79

79

Standard converter dimensions

  • Width

mm

6406

6406

  • Height4)

mm

2112

2112

  • Depth

mm

605

605

Coolant requirements

m3/h

15200

15200

Weight, approx.

kg

3920

4120

Mechanical data for liquid-cooled cabinet units

Frame size (dimensional drawing classification)

SW8

SW8

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

77

77

Standard converter dimensions

  • Width

mm

7006

7006

  • Height

mm

2202

2202

  • Depth

mm

605

605

Coolant requirements

l/h

8000

8000

Min. coolant pressure

bar

2.5

2.5

Max. coolant pressure

bar

6

6

Coolant test pressure

bar

10

10

Coolant pressure loss

bar

1.9

1.9

Min. coolant temperature

C

10

10

Max. coolant temperature

C

30

28

Weight, approx.

kg

4050

4250

General mechanical data

Max. cable length between converter and motor with standard insulation

(shielded)

m

100/2505)

100/2505)

Line/load connection

L1, L2, L3/U2, V2, W2

For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"

Approvals, according to

NRTL6)

NRTL6)



1)Rated power of a typical 2- to 6-pole standard motor.

2) Typical output voltage dependent on filter and unit type.

3)Maximum power loss with continuous motor current.

4)With IP21 protective top cover (110mm).

5) Value is applicable with option L10 (strengthened dv/dt filter; filter is integrated in additional 4 x 600 mm cabinet).

6) On request; the voltage range for NRTL units ends at max. 600V.

690 V, 18‑pulse

Line voltage, supply system type

3×400, 415, 460, 500, 575, 690V3AC IT

SINAMICS G180
cabinet units air-cooled

6SE0180‑3DH42‑2❑A7

6SE0180‑3DH42‑4❑A7

6SE0180‑3DH42‑7❑A7

6SE0180‑3DH43‑0❑A7

6SE0180‑3HH44‑3❑A7

Converter type (air-cooled)

2T3K‑87603‑920

2T3K‑87603‑923

2T3K‑87603‑926

2T3K‑87603‑929

2T3K‑87606‑941

SINAMICS G180
cabinet units liquid-cooled

6SE0170‑3DH42‑2❑A7

6SE0170‑3DH42‑4❑A7

6SE0170‑3DH42‑7❑A7

6SE0170‑3DH43‑0❑A7

6SE0170‑3HH44‑3❑A7

Converter type (liquid-cooled)

2T6K‑77603‑920

2T6K‑77603‑923

2T6K‑77603‑926

2T6K‑77603‑929

2T6K‑77606‑941

Electrical data at motor end

Type rating 1)

  • at 50 Hz 690 V

kW

2000

2300

2600

2900

4100

  • at 60 Hz 575 V

hp

2235

2570

2906

3241

4582

Output voltage2)

V

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

Output current

  • Continuous current

A

2140

2400

2710

2970

4290

  • Short-time current
    (60s every 10minutes) max.

A

2540

2800

3030

3230

5100

Overload capability
(60s every 10minutes) max.

%

19

17

12

9

19

Output power

kVA

2558

2868

3239

3549

5127

Output frequency, max.

Hz

120

120

120

120

120

Rated clock cycle

kHz

2.4

2.4

2.4

2.4

2.4

adjustable from

kHz

1.5...3.7

1.5...3.7

1.5...3.7

1.5...3.7

1.5...3.7

Power loss 3)

kW

50.9

57.2

64.5

73.9

102

Rated efficiency

%

97.7

97.7

97.7

97.6

97.7

Electrical data at line end

Connected load

kVA

2369

2648

2983

3272

4692

Rated input voltage

V

3×690

3×690

3×690

3×690

3×690

Input current

  • Continuous line current

A

3×661

3×739

3×832

3×912

3×1308

  • Short-time line current (60s) max.

A

3×785

3×862

3×930

3×992

3×1555

Line fuse (provided by customer)

gL(A)

800

900

1000

1250

1500

λline

1

1

1

1

1

Cosφline

1

1

1

1

1

Radio interference suppression acc. to EN61800‑3

C4

C4

C4

C4

C4

Mechanical data for air-cooled cabinet units

Frame size (dimensional drawing classification)

SL7

SL7

SL7

SL7

SL11

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

78

78

78

78

79

Standard converter dimensions

  • Width

mm

4806

4806

4806

4806

10206

  • Height4)

mm

2112

2112

2112

2112

2112

  • Depth

mm

605

605

605

605

605

Coolant requirements

m3/h

11400

9600

11400

11400

23150

Weight, approx.

kg

2750

2840

2990

3140

5750

Mechanical data for liquid-cooled cabinet units

Frame size (dimensional drawing classification)

SW7

SW7

SW7

SW7

5)

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

76

76

76

76

77

Standard converter dimensions

  • Width

mm

5206

5206

5206

5206

5)

  • Height

mm

2202

2202

2202

2202

5)

  • Depth

mm

605

605

605

605

5)

Coolant requirements

l/h

6000

6000

6000

6000

12000

Min. coolant pressure

bar

2.5

2.5

2.5

2.5

2.5

Max. coolant pressure

bar

6

6

6

6

6

Coolant test pressure

bar

10

10

10

10

10

Coolant pressure loss

bar

1.9

1.9

1.9

1.9

1.9

Min. coolant temperature

C

10

10

10

10

10

Max. coolant temperature

C

35

35

30

28

35

Weight, approx.

kg

2830

2920

3070

3220

5910

General mechanical data

Max. cable length between converter and motor with standard insulation

(shielded)

m

100/2506)

100/2507)

100/2507)

100/2507)

100/2506)

Line/load connection

L1, L2, L3/U2, V2, W2

For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"

Approvals, according to

NRTL8)

NRTL8)

NRTL8)

NRTL8)

NRTL8)



1)Rated power of a typical 2- to 6-pole standard motor.

2) Typical output voltage dependent on filter and unit type.

3)Maximum power loss with continuous motor current.

4)With IP21 protective top cover (110mm).

5) Dimensions on request.

6) Value is applicable with option L10 (strengthened dv/dt filter; filter is integrated in unit).

7) Value is applicable with option L10 (strengthened dv/dt filter; filter is integrated in additional 3 x 600 mm cabinet).

8) On request; the voltage range for NRTL units ends at max. 600V.

Line voltage, supply system type

3×400, 415, 460, 500, 575, 690V3AC IT

SINAMICS G180
cabinet units air-cooled

6SE0180‑3HH44‑8❑A7

6SE0180‑3HH45‑4❑A7

6SE0180‑3HH46‑0❑A7

Converter type (air-cooled)

2T3K‑87606‑947

2T3K‑87606‑953

2T3K‑87606‑958

SINAMICS G180
cabinet units liquid-cooled

6SE0170‑3HH44‑8❑A7

6SE0170‑3HH45‑4❑A7

6SE0170‑3HH46‑0❑A7

Converter type (liquid-cooled)

2T6K‑77606‑947

2T6K‑77606‑953

2T6K‑77606‑958

Electrical data at motor end

Type rating 1)

  • at 50 Hz 690 V

kW

4700

5300

5800

  • at 60 Hz 575 V

hp

5253

5923

6482

Output voltage2)

V

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

Output current

  • Continuous current

A

4800

5420

5940

  • Short-time current
    (60s every 10minutes) max.

A

5610

6040

6450

Overload capability
(60s every 10minutes) max.

%

17

11

9

Output power

kVA

5736

6477

7099

Output frequency, max.

Hz

120

120

120

Rated clock cycle

kHz

2.4

2.4

2.4

adjustable from

kHz

1.5...3.7

1.5...3.7

1.5...3.7

Power loss 3)

kW

110

118

129

Rated efficiency

%

97.8

97.9

97.9

Electrical data at line end

Connected load

kVA

5244

5916

6482

Rated input voltage

V

3×690

3×690

3×690

Input current

  • Continuous line current

A

3×1462

3×1651

3×1809

  • Short-time line current (60s) max.

A

3×1709

3×1840

3×1964

Line fuse (provided by customer)

gL(A)

1800

2000

2000...2500

λline

1

1

1

Cosφline

1

1

1

Radio interference suppression acc. to EN61800‑3

C4

C4

C4

Mechanical data for air-cooled cabinet units

Frame size (dimensional drawing classification)

SL11

SL11

SL11

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

79

79

79

Standard converter dimensions

  • Width

mm

10206

10206

10206

  • Height4)

mm

2112

2112

2112

  • Depth

mm

605

605

605

Coolant requirements

m3/h

19550

23150

23150

Weight, approx.

kg

5930

6230

6530

Mechanical data for liquid-cooled cabinet units

Frame size (dimensional drawing classification)

5)

5)

5)

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

77

77

77

Standard converter dimensions

  • Width

mm

5)

5)

5)

  • Height

mm

5)

5)

5)

  • Depth

mm

5)

5)

5)

Coolant requirements

l/h

12000

12000

12000

Min. coolant pressure

bar

2.5

2.5

2.5

Max. coolant pressure

bar

6

6

6

Coolant test pressure

bar

10

10

10

Coolant pressure loss

bar

1.9

1.9

1.9

Min. coolant temperature

C

10

10

10

Max. coolant temperature

C

38

30

28

Weight, approx.

kg

6090

6390

6690

General mechanical data

Max. cable length between converter and motor with standard insulation

(shielded)

m

100/2506)

100/2506)

100/2506)

Line/load connection

L1, L2, L3/U2, V2, W2

For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"

Approvals, according to

NRTL7)

NRTL7)

NRTL7)



1)Rated power of a typical 2- to 6-pole standard motor.

2) Typical output voltage dependent on filter and unit type.

3)Maximum power loss with continuous motor current.

4)With IP21 protective top cover (110mm).

5)Dimensions on request.

6) Value is applicable with option L10 (strengthened dv/dt filter; filter is integrated in additional 6 x 600 mm cabinet).

7) On request; the voltage range for NRTL units ends at max. 600V.

690 V, 24‑pulse

Line voltage, supply system type

4×400, 415, 460, 500, 575, 690V3AC IT

SINAMICS G180
cabinet units air-cooled

6SE0180‑4CH41‑2❑A7

6SE0180‑4CH41‑3❑A7

6SE0180‑4CH41‑5❑A7

6SE0180‑4CH41‑7❑A7

6SE0180‑4CH42‑0❑A7

Converter type (air-cooled)

2T3L‑87602‑912

2T3L‑87602‑913

2T3L‑87602‑915

2T3L‑87602‑917

2T3L‑87602‑919

SINAMICS G180
cabinet units liquid-cooled

6SE0170‑4CH41‑2❑A7

6SE0170‑4CH41‑3❑A7

6SE0170‑4CH41‑5❑A7

6SE0170‑4CH41‑7❑A7

6SE0170‑4CH42‑0❑A7

Converter type (liquid-cooled)

2T6L‑77602‑912

2T6L‑77602‑913

2T6L‑77602‑915

2T6L‑77602‑917

2T6L‑77602‑919

Electrical data at motor end

Type rating 1)

  • at 50 Hz 690 V

kW

1200

1300

1500

1700

1900

  • at 60 Hz 575 V

hp

1341

1453

1676

1900

2123

Output voltage2)

V

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

Output current

  • Continuous current

A

1260

1430

1600

1810

1980

  • Short-time current
    (60s every 10minutes) max.

A

1520

1700

1870

2020

2150

Overload capability
(60s every 10minutes) max.

%

21

19

17

12

9

Output power

kVA

1506

1709

1912

2163

2366

Output frequency, max.

Hz

120

120

120

120

120

Rated clock cycle

kHz

2.4

2.4

2.4

2.4

2.4

adjustable from

kHz

1.5...3.7

1.5...3.7

1.5...3.7

1.5...3.7

1.5...3.7

Power loss 3)

kW

28.2

33.6

37.5

42.6

46.5

Rated efficiency

%

97.8

97.7

97.7

97.7

97.7

Electrical data at line end

Connected load

kVA

1405

1597

1781

2010

2194

Rated input voltage

V

4×690

4×690

4×690

4×690

4×690

Input current

  • Continuous line current

A

4×294

4×333

4×372

4×421

4×459

  • Short-time line current (60s) max.

A

4×355

4×396

4×435

4×470

4×498

Line fuse (provided by customer)

gL(A)

400

400

500

500

630

λline

1

1

1

1

1

Cosφline

1

1

1

1

1

Radio interference suppression acc. to EN61800‑3

C4

C4

C4

C4

C4

Mechanical data for air-cooled cabinet units

Frame size (dimensional drawing classification)

SL9

SL9

SL9

SL9

SL9

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

77

77

77

77

77

Standard converter dimensions

  • Width

mm

3606

3606

3606

3606

3606

  • Height4)

mm

2112

2112

2112

2112

2112

  • Depth

mm

605

605

605

605

605

Coolant requirements

m3/h

6400

7600

6400

7600

7600

Weight, approx.

kg

1830

1850

1910

2010

2110

Mechanical data for liquid-cooled cabinet units

Frame size (dimensional drawing classification)

SW9

SW9

SW9

SW9

SW9

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

75

75

75

75

75

Standard converter dimensions

  • Width

mm

4406

4406

4406

4406

4406

  • Height

mm

2202

2202

2202

2202

2202

  • Depth

mm

605

605

605

605

605

Coolant requirements

l/h

4000

4000

4000

4000

4000

Min. coolant pressure

bar

2.5

2.5

2.5

2.5

2.5

Max. coolant pressure

bar

6

6

6

6

6

Coolant test pressure

bar

10

10

10

10

10

Coolant pressure loss

bar

1.9

1.9

1.9

1.9

1.9

Min. coolant temperature

C

10

10

10

10

10

Max. coolant temperature

C

35

35

35

30

28

Weight, approx.

kg

1930

1950

2010

2100

2160

General mechanical data

Max. cable length between converter and motor with standard insulation

(shielded)

m

100/2505)

100/2505)

100/2506)

100/2506)

100/2506)

Line/load connection

L1, L2, L3/U2, V2, W2

For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"

Approvals, according to

NRTL7)

NRTL7)

NRTL7)

NRTL7)

NRTL7)



1)Rated power of a typical 2- to 6-pole standard motor.

2) Typical output voltage dependent on filter and unit type.

3)Maximum power loss with continuous motor current.

4)With IP21 protective top cover (110mm).

5) Value is applicable with option L10 (strengthened dv/dt filter; filter is integrated in unit).

6) Value is applicable with option L10 (strengthened dv/dt filter; filter is integrated in additional 600 mm cabinet).

7) On request; the voltage range for NRTL units ends at max. 600V.

Line voltage, supply system type

4×400, 415, 460, 500, 575, 690V3AC IT

SINAMICS G180
cabinet units air-cooled

6SE0180‑4EH43‑2❑A7

6SE0180‑4EH43‑6❑A7

6SE0180‑4EH44‑0❑A7

6SE0180‑4HH44‑3❑A7

6SE0180‑4HH44‑8❑A7

Converter type (air-cooled)

2T3L‑87604‑931

2T3L‑87604‑935

2T3L‑87604‑939

2T3L‑87606‑941

2T3L‑87606‑947

SINAMICS G180
cabinet units liquid-cooled

6SE0170‑4EH43‑2❑A7

6SE0170‑4EH43‑6❑A7

6SE0170‑4EH44‑0❑A7

6SE0170‑4HH44‑3❑A7

6SE0170‑4HH44‑8❑A7

Converter type (liquid-cooled)

2T6L‑77604‑931

2T6L‑77604‑935

2T6L‑77604‑939

2T6L‑77606‑941

2T6L‑77606‑947

Electrical data at motor end

Type rating 1)

  • at 50 Hz 690 V

kW

3100

3500

3900

4100

4700

  • at 60 Hz 575 V

hp

3465

3912

4359

4582

5253

Output voltage2)

V

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

Output current

  • Continuous current

A

3200

3610

3960

4290

4800

  • Short-time current
    (60s every 10minutes) max.

A

3730

4030

4300

5100

5610

Overload capability
(60s every 10minutes) max.

%

17

12

9

19

17

Output power

kVA

3824

4314

4732

5127

5736

Output frequency, max.

Hz

120

120

120

120

120

Rated clock cycle

kHz

2.4

2.4

2.4

2.4

2.4

adjustable from

kHz

1.5...3.7

1.5...3.7

1.5...3.7

1.5...3.7

1.5...3.7

Power loss 3)

kW

77.3

87.3

99.7

102

110

Rated efficiency

%

97.7

97.7

97.6

97.7

97.8

Electrical data at line end

Connected load

kVA

3516

3956

4336

4692

5244

Rated input voltage

V

4×690

4×690

4×690

4×690

4×690

Input current

  • Continuous line current

A

4×735

4×828

4×906

4×982

4×1098

  • Short-time line current (60s) max.

A

4×857

4×924

4×984

4×1167

4×1283

Line fuse (provided by customer)

gL(A)

900

1000

1000...1250

1250

1250...1500

λline

1

1

1

1

1

Cosφline

1

1

1

1

1

Radio interference suppression acc. to EN61800‑3

C4

C4

C4

C4

C4

Mechanical data for air-cooled cabinet units

Frame size (dimensional drawing classification)

SL10

SL10

SL10

SL12

SL12

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

79

79

79

79

79

Standard converter dimensions

  • Width

mm

7206

7206

7206

11406

11406

  • Height4)

mm

2112

2112

2112

2112

2112

  • Depth

mm

605

605

605

605

605

Coolant requirements

m3/h

12800

15200

15200

23150

19550

Weight, approx.

kg

3760

3970

4170

5750

5930

Mechanical data for liquid-cooled cabinet units

Frame size (dimensional drawing classification)

SW10

SW10

SW10

5)

5)

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

77

77

77

77

77

Standard converter dimensions

  • Width

mm

7806

7806

7806

5)

5)

  • Height

mm

2202

2202

2202

5)

5)

  • Depth

mm

605

605

605

5)

5)

Coolant requirements

l/h

8000

8000

8000

12000

12000

Min. coolant pressure

bar

2.5

2.5

2.5

2.5

2.5

Max. coolant pressure

bar

6

6

6

6

6

Coolant test pressure

bar

10

10

10

10

10

Coolant pressure loss

bar

1.9

1.9

1.9

1.9

1.9

Min. coolant temperature

C

10

10

10

10

10

Max. coolant temperature

C

35

30

28

35

38

Weight, approx.

kg

3860

4070

4270

5910

6090

General mechanical data

Max. cable length between converter and motor with standard insulation

(shielded)

m

100/2506)

100/2506)

100/2506)

100/2507)

100/2508)

Line/load connection

L1, L2, L3/U2, V2, W2

For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"

Approvals, according to

NRTL9)

NRTL9)

NRTL9)

NRTL9)

NRTL9)



1)Rated power of a typical 2- to 6-pole standard motor.

2) Typical output voltage dependent on filter and unit type.

3)Maximum power loss with continuous motor current.

4)With IP21 protective top cover (110mm).

5) Dimensions on request.

6) With option L10 (strengthened dv/dt filter) the filter is integrated in additional 4×600mm cabinet.

7) Value is applicable with option L10 (strengthened dv/dt filter; filter is integrated in unit).

8) Value is applicable with option L10 (strengthened dv/dt filter; filter is integrated in additional 6 x 600 mm cabinet).

9) On request; the voltage range for NRTL units ends at max. 600V.

Line voltage, supply system type

4×400, 415, 460, 500, 575, 690V3AC IT

SINAMICS G180
cabinet units air-cooled

6SE0180‑4HH45‑4❑A7

6SE0180‑4HH46‑0nA7

Converter type (air-cooled)

2T3L‑87606‑953

2T3L‑87606‑958

SINAMICS G180
cabinet units liquid-cooled

6SE0170‑4HH45‑4❑A7

6SE0170‑4HH46‑0❑A7

Converter type (liquid-cooled)

2T6L‑77606‑953

2T6L‑77606‑958

Electrical data at motor end

Type rating 1)

  • at 50 Hz 690 V

kW

5300

5800

  • at 60 Hz 575 V

hp

5923

6482

Output voltage2)

V

0...0.98×Vline

0...0.98×Vline

Output current

  • Continuous current

A

5420

5940

  • Short-time current
    (60s every 10minutes) max.

A

6040

6450

Overload capability
(60s every 10minutes) max.

%

11

9

Output power

kVA

6477

7099

Output frequency, max.

Hz

120

120

Rated clock cycle

kHz

2.4

2.4

adjustable from

kHz

1.5...3.7

1.5...3.7

Power loss 3)

kW

118

129

Rated efficiency

%

97.9

97.9

Electrical data at line end

Connected load

kVA

5916

6482

Rated input voltage

V

4×690

4×690

Input current

  • Continuous line current

A

4×1237

4×1357

  • Short-time line current (60s) max.

A

4×1378

4×1474

Line fuse (provided by customer)

gL(A)

1500

1500...1800

λline

1

1

Cosφline

1

1

Radio interference suppression acc. to EN61800‑3

C4

C4

Mechanical data for air-cooled cabinet units

Frame size (dimensional drawing classification)

SL12

SL12

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

79

79

Standard converter dimensions

  • Width

mm

11406

11406

  • Height4)

mm

2112

2112

  • Depth

mm

605

605

Coolant requirements

m3/h

23150

23150

Weight, approx.

kg

6230

6530

Mechanical data for liquid-cooled cabinet units

Frame size (dimensional drawing classification)

5)

5)

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

77

77

Standard converter dimensions

  • Width

mm

5)

5)

  • Height

mm

5)

5)

  • Depth

mm

5)

5)

Coolant requirements

l/h

12000

12000

Min. coolant pressure

bar

2.5

2.5

Max. coolant pressure

bar

6

6

Coolant test pressure

bar

10

10

Coolant pressure loss

bar

1.9

1.9

Min. coolant temperature

C

10

10

Max. coolant temperature

C

30

28

Weight, approx.

kg

6390

6690

General mechanical data

Max. cable length between converter and motor with standard insulation

(shielded)

m

100/2506)

100/2506)

Line/load connection

L1, L2, L3/U2, V2, W2

For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"

Approvals, according to

NRTL7)

NRTL7)



1)Rated power of a typical 2- to 6-pole standard motor.

2) Typical output voltage dependent on filter and unit type.

3)Maximum power loss with continuous motor current.

4)With IP21 protective top cover (110mm).

5) Dimensions on request.

6) Value is applicable with option L10 (strengthened dv/dt filter; filter is integrated in additional 6 x 600 mm cabinet).

7) On request; the voltage range for NRTL units ends at max. 600V.

















skener.ru

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
DENDOR

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FS -

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FK -

  © " " 2007-2022
  (4872) 700-366  skenergo@mail.ru
.