SINAMICS G180 cabinet units - air-cooled and liquid-cooled
The most important directives and standards are listed below. These are used as basis for the SINAMICS G180 cabinet units and they must be carefully observed to achieve an EMC-compliant configuration that is safe both functionally and in operation.
Standards for cabinet units
European directives
2006/95/EC
Low-voltage directive: Legal guidelines of the EU member states concerning electrical equipment for use within specified voltage limits
2004/108/EC
EMC Directive: Legal guidelines of the EU member states for electromagnetic compatibility
International and European standards
EN 954?1
Safety of machinery – Safety-related parts of control systems; Part 1: General design principles
EN ISO 13849?1
Safety of machinery – Safety-related parts of control systems; Part 1: General design principles (ISO 13849?1:2006) (replaced EN 954?1)
EN 60146?1?1
Semiconductor converters – General requirements and line-commutated converters Part 1-1: Specification of basic requirements
EN 60204?1
Electrical equipment of machines Part 1: General definitions
EN 60529
Degrees of protection provided by enclosures (IP code)
EN 61140
Protection against electric shock - Common aspects for installation and equipment
EN 61508?1
Functional safety of electrical/electronic/programmable electronic safety-related systems Part 1: General requirements
EN 61800?2
Adjustable speed electrical power drive systems, Part 2: General requirements – Rating specifications for low-voltage adjustable frequency AC power drive systems
EN 61800?3
Adjustable speed electrical power drive systems, Part 3: EMC requirements and specific test methods
EN 61800-5-1
Adjustable speed electrical power drive systems, Part 5-1: Safety requirements - Electrical, thermal and energy requirements
EN 61800?5?2
Adjustable speed electrical power drive systems, Part 5-2: Safety requirements – Functional safety (IEC 61800?5?2:2007)
North American standards
UL508C1)
Power conversion equipment
Approvals
TUV NRTL US1)
Nationally Recognized Testing Laboratory
1) On request
General technical data
Electrical data
Line voltages
Type of supply system
Output ranges
230 … 400 … 415 V 3 AC, -15/+10 %
TN/TT system
200 ... 630 kW (at 400 V)
230 … 500 V 3 AC, -15/+10 %
TN/TT/IT system
250 ... 800 kW (at 500 V)
400 … 690 V 3 AC, -15/+10 %
TN/TT/IT system
250 ... 6000 kW (at 690 V)
Line frequency
47 … 63 Hz
Output frequency
0 … 250 Hz
Voltage rise in motor
Typ. 500 ... 1000 V/µs, but < 1500 V/µs
Pulse number
6/12/18/24
Typical line harmonics (I) in % of fundamental mode for the 5/7/11/13/17/19/23/25 harmonics, max. (6-pulse converter)
38/18/8/7/5/4/3/2
Typical line harmonics (I) in % of fundamental mode for the 5/7/11/13/17/19/23/25 harmonics, max. (12-pulse converter)
1.5/1/6/4/0.5/0.2/2/2
Typical line harmonics (I) in % of fundamental mode for the 5/7/11/13/17/19/23/25 harmonics, max. (18-pulse converter)
1/0.5/0.5/0.5/4/3.5/0.5/0.5
Typical line harmonics (I) in % of fundamental mode for the 5/7/11/13/17/19/23/25 harmonics, max. (24-pulse converter)
1/0.5/0.5/0.5/0.5/0.2/2/2
Typical line harmonics (I) in % of fundamental mode for the 5/7/11/13/17/19/23/25 harmonics max. with LHF filter
4.5/4.7/2.8/1.6/1.2/0.9/0.6/0.5
Overvoltage category
III to EN 61800?5?1
Short Circuit Current Rating (SCCR) according to UL508C (up to 600 V), in conjunction with the specified fuses or circuit breakers
20 times rated current, but at least 50 kA
Control method
For motors: Field-oriented control (FOC) with sensor and approval for explosion-proof motors as well as vector control (SVC) with/without sensor (speed, process speed (n), torque, hoist1), line synchronization1))
Motor-independent control of current or voltage (current, process current (I), voltage, process voltage (U))
Fixed speeds
3 fixed speeds + 1 minimum speed, parameterizable
Skipped speed ranges
2, parameterizable
Setpoint resolution
13 bits digital with n/f setpoint, 12 bits digital with U/I torque setpoint, 9 bits + sign analog
Braking operation
The oversaturation control system makes it possible to generate a braking torque of up to 50 % at low to mid-range speeds, and of up to 10 % at high speeds. If a higher braking torque is required, an optionally available braking module with appropriate braking resistor must be installed.
Mechanical data
Degree of protection
IP21 (higher degrees of protection optionally available) / with liquid cooling IP54
Protection class
I acc. to EN 61800?5?1
Touch protection
EN 50274 / BGV A3
Type of cooling
Forced air cooling AF to EN 60146 / Coolant is water and a mixture of water and Antifrogen N with 45 % Antifrogen N
Paint finish
RAL 7035; Rittal TS8 cabinet frame: With nano-ceramic and anodized coating, layer thickness approx. 10 to 20 µm; parts mounted on TS8 cabinet: With nano-ceramic and anodized coating, layer thickness approx. 10 to 20 µm, plus layer of hybrid polyester epoxy powder, thickness approx. 50 to 80 µm
Cable entry
From below by means of profile clamp (from the top as option)
Door hinge and opening angle
Right/130°
For liquid-cooled units only
Coolant quality
See below under "Permissible substance values for the coolant"
Permissible coolant temperature
+10 °C … 28/30/35 °C (dependent on output, see technical data)
Ambient conditions2)
Storage 3)
Transport 3)
Operation
Ambient temperature
-25 … +70 °C
Class 1K4 acc. to EN 60721?3?1
-25 ... +70 °C Down to -40 °C for 24h Class 2K3 acc. to EN 60721?3?2
Air: 0 … 40 °C/ Water: 1 °C … 40 °C (up to +40 °C see derating data) –
Relative humidity (condensation not permissible)
5 ... 95 % Class 1K3 acc. to EN 60721?3?1
5 … 95 % Class 2K3 acc. to EN 60721?3?2
5 … 95 % Class 3K3 acc. to EN 60721?3?3
Environmental class/harmful chemical substances
Class 1C2 acc. to EN 60721?3?1
Class 2C2 acc. to EN 60721?3?2
Class 3C2 acc. to EN 60721?3?3
Organic/biological influences
Class 1B1 acc. to EN 60721?3?1
Class 2B1 acc. to EN 60721?3?2
Class 3B1 acc. to EN 60721?3?3
Pollution degree
2 acc. to EN 61800?5?1
Installation altitude
Up to 1000 m above sea level without derating, > 1000 m see derating data
Mechanical stability2)
Storage 3)
Transport 3)
Operation
Vibratory load
Deflection
Acceleration
1.5 mm at 5 … 9 Hz
5 m/s2 at > 9 … 200 Hz Class 1M2 to EN 60721?3?1
3.5 mm at 5 … 9 Hz
10 m/s2 at > 9 …200 Hz Class 2M2 to EN 60721?3?2
0.075 mm at 10 … 57 Hz
10 m/s2 at > 57 … 150 Hz
Shock load
Acceleration
40 m/s2 at 22 ms Class 1M2 to EN 60721?3?1
100 m/s2 at 11 ms Class 2M2 to EN 60721?3?2
100 m/s2 at 11 ms Class 3M4 to EN 60721?3?3
Compliance with standards
CE Label
Acc. to EMC Directive No. 2004/108/EC and Low-Voltage Directive No. 2006/95/EC
Radio interference suppression
Complies with EMC guidelines defined in EN 61800?3 thanks to line filter which is integrated as standard with grounded supply system:
Category C3 for cabinet units in TN/TT system of the second environment (industrial area)
Category C4 for cabinet units in IT system of the second environment (industrial area)
Approvals
TUV NRTL US2)
1) On request
2) Higher standards on request
3) In transport packaging
Deviations from the specified classes are underlined.
Permissible substance values for the coolant
The following table lists the permissible substance values for the cooling water (service water and demineralized water) for cooling the converter with an open standard cooling system without cooling unit.
Permissible values for SINAMICS G180 cabinet units
Coolant temperature
+10 … 28/30/35 °C
pH value
7 … 8
Total hardness
6 … 20 °dH
Carbonate hardness
3 … 10 dH
Total dissolved solids 105 °C
< 500 mg/l
Free carbon dioxide
< 1 mmol/l
Chlorides
< 150 mg/l
Sulfates
500 mg/l
Nitrates
< 10 mg/l
Nitrites
0 mg/l
Phosphates
< 0.5 mg/l
Ammonium NH4
< 0.5 mg/l
Ammoniac
0 mg/l
Silicon (SiO2 crystalline)
< 10 mg/l
Free CO2 (p value)
< 15 mg/l
Iron
< 0.2 mg/l
Hydrogen sulfide
< 1 mg/l
Suspended solids < 50 ?m
< 10 mg/l
Conductivity
< 3000 ?S/cm
Oxygen
8 … 12 mg/l
Cooling water additives for the closed converter cooling system with cooling unit
We recommend the agent "Antifrogen N" supplied by Clariant as a cooling water additive. The appropriate level of anti-freeze protection can be provided by choosing the correct mixing ratio. A minimum concentration of 20 % by volume provides anti-freeze protection down to ?10 °C. An Antifrogen/water mixing ratio of 1:2 provides anti-freeze protection down to ?20 °C.
Unpolluted water mixed with a minimum concentration of 20 % by volume of Antifrogen N prevents the growth of microorganisms and the formation of algae.
400 V, 6?pulse
Line voltage, supply system type
400, 415 V 3 AC TT/TN
SINAMICS G180 cabinet units – air-cooled
6SE0180?1BA33?7?A7
6SE0180?1BA34?6?A7
6SE0180?1BA36?3?A7
6SE0180?1BA37?3?A7
6SE0180?1BA38?8?A7
Converter type (air-cooled)
2T3A?87401?200
2T3A?87401?250
2T3A?87401?315
2T3A?87401?400
2T3A?87401?500
SINAMICS G180 cabinet units – liquid-cooled
6SE0170?1BA33?7?A7
6SE0170?1BA34?6?A7
6SE0170?1BA36?3?A7
6SE0170?1BA37?3?A7
6SE0170?1BA38?8?A7
Converter type (liquid-cooled)
2T6A?77401?200
2T6A?77401?250
2T6A?77401?315
2T6A?77401?400
2T6A?77401?500
Electrical data at motor end
Type rating 1)
at 50 Hz 400 V
kW
200
250
315
400
500
at 50 Hz 400 V
hp
268
335
422
536
671
Output voltage2)
V
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
Output current
Continuous current
A
380
460
630
740
910
Short-time current (60 s every 10 minutes) max.
A
470
560
700
900
1110
Overload capability (60 s every 10 minutes) max.
%
24
22
11
22
22
Output power
kVA
263
319
436
513
630
Output frequency, max.
Hz
250
250
250
120
120
Rated clock cycle
kHz
3
3
3
2.4
2.4
adjustable from
kHz
2 ... 5
2 ... 5
2 ... 5
1.5 ... 3.7
1.5 ... 3.7
Power loss 3)
kW
5.6
6.42
8.4
11.9
14.9
Rated efficiency
%
97.4
97.6
97.5
97.2
97.2
Electrical data at line end
Connected load
kVA
249
300
403
476
603
Rated input voltage
V
400
400
400
400
400
Input current
Continuous line current
A
360
433
582
687
871
Short-time line current (60 s) max.
A
445
527
647
836
1062
Line fuse (provided by customer)
gL (A)
400
500
630
800
900
?line
0.931
0.928
0.943
0.942
0.946
Cos ?line
1
1
1
1
1
Radio interference suppression acc. to EN 61800?3
C3 (class A filter)
C3 (class A filter)
C3 (class A filter)
C3 (class A filter)
C3 (class A filter)
Mechanical data for air-cooled cabinet units
Frame size (dimensional drawing classification)
SL2
SL2
SL2
SL21
SL3
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
70
70
73
75
75
Standard converter dimensions
Width
mm
806
806
806
1206
1606
Height4)
mm
2112
2112
2112
2112
2112
Depth
mm
605
605
605
605
605
Coolant requirements
m3/h
1900
1900
1900
2250
3800
Weight, approx.
kg
490
510
530
780
890
Mechanical data for liquid-cooled cabinet units
Frame size (dimensional drawing classification)
SW2
SW2
SW2
SW21
SW3
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
68
68
71
73
73
Standard converter dimensions6)
Width
mm
806
806
806
1206
1806
Height
mm
2202
2202
2202
2202
2202
Depth
mm
605
605
605
605
605
Coolant requirements
l/h
1200
1200
1200
1200
2000
Min. coolant pressure
bar
2.5
2.5
2.5
2.5
2.5
Max. coolant pressure
bar
6
6
6
6
6
Coolant test pressure
bar
10
10
10
10
10
Coolant pressure loss
bar
1.9
1.9
1.9
1.9
1.9
Min. coolant temperature
°C
10
10
10
10
10
Max. coolant temperature
°C
35
35
35
30
35
Weight, approx.
kg
490
510
530
860
920
General mechanical data
Max. cable length between converter and motor with standard insulation
(shielded)
m
3005)
3005)
3005)
3005)
3005)
Line/load connection
L1, L2, L3/U2, V2, W2
For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"
Approvals, according to
NRTL6)
NRTL6)
NRTL6)
NRTL6)
NRTL6)
1) Rated power of a typical 2- to 6-pole standard motor.
2) Typical output voltage dependent on filter and unit type.
3) Maximum power loss with continuous motor current.
4) With IP21 protective top cover (110 mm).
5) Option L10 included (strengthened dv/dt filter; strengthened filter is integrated in unit).
6) On request.
Line voltage, supply system type
400, 415 V 3 AC TT/TN
SINAMICS G180 cabinet units – air-cooled
6SE0180?1BA41?0?A7
6SE0180?1BA41?1?A7
Converter type (air-cooled)
2T3A?87401?560
2T3A?87401?630
SINAMICS G180 cabinet units – liquid-cooled
6SE0170?1BA41?0?A7
6SE0170?1BA41?1?A7
Converter type (liquid-cooled)
2T6A?77401?560
2T6A?77401?630
Electrical data at motor end
Type rating 1)
at 50 Hz 400 V
kW
560
630
at 50 Hz 400 V
hp
751
845
Output voltage2)
V
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
Output current
Continuous current
A
1020
1140
Short-time current (60 s every 10 minutes) max.
A
1230
1370
Overload capability (60 s every 10 minutes) max.
%
21
20
Output power
kVA
707
790
Output frequency, max.
Hz
120
120
Rated clock cycle
kHz
2.4
2.4
adjustable from
kHz
1.5 ... 3.7
1.5 ... 3.7
Power loss 3)
kW
16.7
18.1
Rated efficiency
%
97.2
97.3
Electrical data at line end
Connected load
kVA
676
761
Rated input voltage
V
400
400
Input current
Continuous line current
A
975
1098
Short-time line current (60 s) max.
A
1176
1320
Line fuse (provided by customer)
gL (A)
1000
1250
?line
0.947
0.95
Cos ?line
1
1
Radio interference suppression acc. to EN 61800?3
C3 (class A filter)
C3 (class A filter)
Mechanical data for air-cooled cabinet units
Frame size (dimensional drawing classification)
SL3
SL3
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
75
75
Standard converter dimensions
Width
mm
1606
1606
Height4)
mm
2112
2112
Depth
mm
605
605
Coolant requirements
m3/h
3200
3800
Weight, approx.
kg
900
930
Mechanical data for liquid-cooled cabinet units
Frame size (dimensional drawing classification)
SW3
SW3
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
73
73
Standard converter dimensions6)
Width
mm
1806
1806
Height
mm
2202
2202
Depth
mm
605
605
Coolant requirements
l/h
2000
2000
Min. coolant pressure
bar
2.5
2.5
Max. coolant pressure
bar
6
6
Coolant test pressure
bar
10
10
Coolant pressure loss
bar
1.9
1.9
Min. coolant temperature
°C
10
10
Max. coolant temperature
°C
35
35
Weight, approx.
kg
930
960
General mechanical data
Max. cable length between converter and motor with standard insulation
(shielded)
m
3005)
3005)
Line/load connection
L1, L2, L3/U2, V2, W2
For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"
Approvals, according to
NRTL6)
NRTL6)
1) Rated power of a typical 2- to 6-pole standard motor.
2) Typical output voltage dependent on filter and unit type.
3) Maximum power loss with continuous motor current.
4) With IP21 protective top cover (110 mm).
5) Option L10 included (strengthened dv/dt filter; strengthened filter is integrated in unit).
6) On request.
400 V, 12?pulse
Line voltage, supply system type
400, 415 V 3 AC IT
SINAMICS G180 cabinet units – air-cooled
6SE0180?2BA33?7?A7
6SE0180?2BA34?6?A7
6SE0180?2BA36?3?A7
6SE0180?2BA37?3?A7
6SE0180?2BA38?8?A7
Converter type (air-cooled)
2T3F?87401?200
2T3F?87401?250
2T3F?87401?315
2T3F?87401?400
2T3F?87401?500
SINAMICS G180 cabinet units – liquid-cooled
6SE0170?2BA33?7?A7
6SE0170?2BA34?6?A7
6SE0170?2BA36?3?A7
6SE0170?2BA37?3?A7
6SE0170?2BA38?8?A7
Converter type (liquid-cooled)
2T6F?77401?200
2T6F?77401?250
2T6F?77401?315
2T6F?77401?400
2T6F?77401?500
Electrical data at motor end
Type rating 1)
at 50 Hz 400 V
kW
200
250
315
400
500
at 50 Hz 400 V
hp
268
335
422
536
671
Output voltage2)
V
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
Output current
Continuous current
A
380
460
630
740
910
Short-time current (60 s every 10 minutes) max.
A
470
560
700
900
1110
Overload capability (60 s every 10 minutes) max.
%
24
22
11
22
22
Output power
kVA
263
319
436
513
630
Output frequency, max.
Hz
250
250
250
120
120
Rated clock cycle
kHz
3
3
3
2.4
2.4
adjustable from
kHz
2 ... 5
2 ... 5
2 ... 5
1.5 ... 3.7
1.5 ... 3.7
Power loss 3)
kW
5.6
6.42
8.4
11.9
14.9
Rated efficiency
%
97.4
97.6
97.5
97.2
97.2
Electrical data at line end
Connected load
kVA
249
301
405
477
604
Rated input voltage
V
400
400
400
400
400
Input current
Continuous line current
A
180
217
292
344
436
Short-time line current (60 s) max.
A
223
264
324
418
532
Line fuse (provided by customer)
gL (A)
200
250
400
400
500
?line
0.994
0.994
0.994
0.996
0.996
Cos ?line
1
1
1
1
1
Radio interference suppression acc. to EN 61800?3
C3 (class A filter)
C3 (class A filter)
C3 (class A filter)
C3 (class A filter)
C3 (class A filter)
Mechanical data for air-cooled cabinet units
Frame size (dimensional drawing classification)
SL5
SL5
SL5
SL5
SL6
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
70
70
73
75
75
Standard converter dimensions
Width
mm
1406
1406
1406
1406
1806
Height4)
mm
2112
2112
2112
2112
2112
Depth
mm
605
605
605
605
605
Coolant requirements
m3/h
1900
1900
1900
2250
3800
Weight, approx.
kg
690
710
730
810
920
Mechanical data for liquid-cooled cabinet units
Frame size (dimensional drawing classification)
SW5
SW5
SW5
SW5
SW6
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
68
68
71
73
73
Standard converter dimensions
Width
mm
1406
1406
1406
1406
2006
Height
mm
2202
2202
2202
2202
2202
Depth
mm
605
605
605
605
605
Coolant requirements
l/h
1200
1200
1200
1200
2000
Min. coolant pressure
bar
2.5
2.5
2.5
2.5
2.5
Max. coolant pressure
bar
6
6
6
6
6
Coolant test pressure
bar
10
10
10
10
10
Coolant pressure loss
bar
1.9
1.9
1.9
1.9
1.9
Min. coolant temperature
°C
10
10
10
10
10
Max. coolant temperature
°C
35
35
35
30
35
Weight, approx.
kg
690
710
730
810
950
General mechanical data
Max. cable length between converter and motor with standard insulation
(shielded)
m
3005)
3005)
3005)
3005)
3005)
Line/load connection
L1, L2, L3/U2, V2, W2
For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"
Approvals, according to
NRTL6)
NRTL6)
NRTL6)
NRTL6)
NRTL6)
1) Rated power of a typical 2- to 6-pole standard motor.
2) Typical output voltage dependent on filter and unit type.
3) Maximum power loss with continuous motor current.
4) With IP21 protective top cover (110 mm).
5) Option L10 included (strengthened dv/dt filter; strengthened filter is integrated in unit).
6) On request.
Line voltage, supply system type
400, 415 V 3 AC IT
SINAMICS G180 cabinet units – air-cooled
6SE0180?2BA41?0?A7
6SE0180?2BA41?1?A7
Converter type (air-cooled)
2T3F?87401?560
2T3F?87401?630
SINAMICS G180 cabinet units – liquid-cooled
6SE0170?2BA41?0?A7
6SE0170?2BA41?1?A7
Converter type (liquid-cooled)
2T6F?77401?560
2T6F?77401?630
Electrical data at motor end
Type rating 1)
at 50 Hz 400 V
kW
560
630
at 50 Hz 400 V
hp
751
845
Output voltage2)
V
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
Output current
Continuous current
A
1020
1140
Short-time current (60 s every 10 minutes) max.
A
1230
1370
Overload capability (60 s every 10 minutes) max.
%
21
20
Output power
kVA
707
790
Output frequency, max.
Hz
120
120
Rated clock cycle
kHz
2.4
2.4
adjustable from
kHz
1.5 ... 3.7
1.5 ... 3.7
Power loss 3)
kW
16.7
18.1
Rated efficiency
%
97.2
97.3
Electrical data at line end
Connected load
kVA
676
762
Rated input voltage
V
400
400
Input current
Continuous line current
A
488
550
Short-time line current (60 s) max.
A
588
661
Line fuse (provided by customer)
gL (A)
630
630
?line
0.996
0.997
Cos ?line
1
1
Radio interference suppression acc. to EN 61800?3
C4
C4
Mechanical data for air-cooled cabinet units
Frame size (dimensional drawing classification)
SL6
SL6
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
75
75
Standard converter dimensions
Width
mm
1806
1806
Height4)
mm
2112
2112
Depth
mm
605
605
Coolant requirements
m3/h
3200
3800
Weight, approx.
kg
930
960
Mechanical data for liquid-cooled cabinet units
Frame size (dimensional drawing classification)
SW6
SW6
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
73
73
Standard converter dimensions
Width
mm
2006
2006
Height
mm
2202
2202
Depth
mm
605
605
Coolant requirements
l/h
2000
2000
Min. coolant pressure
bar
2.5
2.5
Max. coolant pressure
bar
6
6
Coolant test pressure
bar
10
10
Coolant pressure loss
bar
1.9
1.9
Min. coolant temperature
°C
10
10
Max. coolant temperature
°C
35
35
Weight, approx.
kg
960
990
General mechanical data
Max. cable length between converter and motor with standard insulation
(shielded)
m
3005)
3005)
Line/load connection
L1, L2, L3/U2, V2, W2
For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"
Approvals, according to
NRTL6)
NRTL6)
1) Rated power of a typical 2- to 6-pole standard motor.
2) Typical output voltage dependent on filter and unit type.
3) Maximum power loss with continuous motor current.
4) With IP21 protective top cover (110 mm).
5) Option L10 included (strengthened dv/dt filter; strengthened filter is integrated in unit).
6) On request.
500 V, 6?pulse
Line voltage, supply system type
400, 415, 460, 500 V 3 AC IT/TT/TN
SINAMICS G180 cabinet units – air-cooled
6SE0180?1BD33?7?A7
6SE0180?1BD34?6?A7
6SE0180?1BD36?3?A7
6SE0180?1BD37?3?A7
6SE0180?1BD38?2?A7
Converter type (air-cooled)
2T3A?87501?250
2T3A?87501?315
2T3A?87501?400
2T3A?87501?500
2T3A?87501?560
SINAMICS G180 cabinet units – liquid-cooled
6SE0170?1BD33?7?A7
6SE0170?1BD34?6?A7
6SE0170?1BD36?3?A7
6SE0170?1BD37?3?A7
6SE0170?1BD38?2?A7
Converter type (liquid-cooled)
2T6A?77501?250
2T6A?77501?315
2T6A?77501?400
2T6A?77501?500
2T6A?77501?560
Electrical data at motor end
Type rating 1)
at 50 Hz 500 V
kW
250
315
400
500
560
at 60 Hz 460 V
hp
309
389
494
617
691
Output voltage2)
V
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
Output current
Continuous current
A
370
460
640
730
820
Short-time current (60 s every 10 minutes) max.
A
450
560
700
900
980
Overload capability (60 s every 10 minutes) max.
%
22
22
9
23
20
Output power
kVA
320
398
554
632
710
Output frequency, max.
Hz
250
250
250
120
120
Rated clock cycle
kHz
3
3
2.4
2.4
2.4
adjustable from
kHz
2 ... 5
2 ... 5
1.5 ... 3.7
1.5 ... 3.7
1.5 ... 3.7
Power loss 3)
kW
6.15
7.39
9.37
12.8
13.7
Rated efficiency
%
97.7
97.8
97.8
97.6
97.7
Electrical data at line end
Connected load
kVA
303
378
515
606
678
Rated input voltage
V
500
500
500
500
500
Input current
Continuous line current
A
350
437
595
700
783
Short-time line current (60 s) max.
A
426
532
651
863
936
Line fuse (provided by customer)
gL (A)
400
500
630
800
800
?line
0.918
0.916
0.936
0.942
0.944
Cos ?line
1
1
1
1
1
Radio interference suppression acc. to EN 61800?34)
C3 (class A filter)
C3 (class A filter)
C3 (class A filter)
C3 (class A filter)
C3 (class A filter)
Mechanical data for air-cooled cabinet units
Frame size (dimensional drawing classification)
SL2
SL2
SL2
SL21
SL3
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
70
73
73
75
75
Standard converter dimensions
Width
mm
806
806
806
1206
1606
Height5)
mm
2112
2112
2112
2112
2112
Depth
mm
605
605
605
605
605
Coolant requirements
m3/h
1900
1900
1900
2250
3200
Weight, approx.
kg
490
510
530
780
890
Mechanical data for liquid-cooled cabinet units
Frame size (dimensional drawing classification)
SW2
SW2
SW2
SW21
SW3
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
68
71
71
73
73
Standard converter dimensions
Width
mm
806
806
806
1206
1806
Height
mm
2202
2202
2202
2202
2202
Depth
mm
605
605
605
605
605
Coolant requirements
l/h
1200
1200
1200
1200
2000
Min. coolant pressure
bar
2.5
2.5
2.5
2.5
2.5
Max. coolant pressure
bar
6
6
6
6
6
Coolant test pressure
bar
10
10
10
10
10
Coolant pressure loss
bar
1.9
1.9
1.9
1.9
1.9
Min. coolant temperature
°C
10
10
10
10
10
Max. coolant temperature
°C
35
35
35
30
35
Weight, approx.
kg
490
510
530
850
920
General mechanical data
Max. cable length between converter and motor with standard insulation
(shielded)
m
2506)
2506)
2506)
2506)
2506)
Line/load connection
L1, L2, L3/U2, V2, W2
For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"
Approvals, according to
NRTL7)
NRTL7)
NRTL7)
NRTL7)
NRTL7)
1) Rated power of a typical 2- to 6-pole standard motor.
2) Typical output voltage dependent on filter and unit type.
3) Maximum power loss with continuous motor current.
4) EMC filter not required for IT system, in which case RI suppression category C4.
5) With IP21 protective top cover (110 mm).
6) Option L10 included (strengthened dv/dt filter; strengthened filter is integrated in unit).
7) On request.
Line voltage, supply system type
400, 415, 460, 500 V 3 AC IT/TT/TN
SINAMICS G180 cabinet units – air-cooled
6SE0180?1BD38?8?A7
6SE0180?1BD41?0?A7
6SE0180?1BD41?1?A7
Converter type (air-cooled)
2T3A?87501?630
2T3A?87501?710
2T3A?87501?800
SINAMICS G180 cabinet units – liquid-cooled
6SE0170?1BD38?8?A7
6SE0170?1BD41?0?A7
6SE0170?1BD41?1?A7
Converter type (liquid-cooled)
2T6A?77501?630
2T6A?77501?710
2T6A?77501?800
Electrical data at motor end
Type rating 1)
at 50 Hz 500 V
kW
630
710
800
at 60 Hz 460 V
hp
777
876
987
Output voltage2)
V
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
Output current
Continuous current
A
920
1030
1150
Short-time current (60 s every 10 minutes) max.
A
1100
1230
1380
Overload capability (60 s every 10 minutes) max.
%
20
19
20
Output power
kVA
797
892
996
Output frequency, max.
Hz
120
120
120
Rated clock cycle
kHz
2.4
2.4
2.4
adjustable from
kHz
1.5 ... 3.7
1.5 ... 3.7
1.5 ... 3.7
Power loss 3)
kW
15.4
18.1
20.3
Rated efficiency
%
97.7
97.6
97.6
Electrical data at line end
Connected load
kVA
767
848
944
Rated input voltage
V
500
500
500
Input current
Continuous line current
A
886
979
1090
Short-time line current (60 s) max.
A
1059
1169
1308
Line fuse (provided by customer)
gL (A)
900
1000
1250
?line
0.946
0.948
0.95
Cos ?line
1
1
1
Radio interference suppression acc. to EN 61800?34)
C3 (class A filter)
C3 (class A filter)
C3 (class A filter)
Mechanical data for air-cooled cabinet units
Frame size (dimensional drawing classification)
SL3
SL3
SL3
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
75
75
75
Standard converter dimensions
Width
mm
1606
1606
1606
Height5)
mm
2112
2112
2112
Depth
mm
605
605
605
Coolant requirements
m3/h
3800
3200
3800
Weight, approx.
kg
900
930
980
Mechanical data for liquid-cooled cabinet units
Frame size (dimensional drawing classification)
SW3
SW3
SW3
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
73
73
73
Standard converter dimensions
Width
mm
1806
1806
1806
Height
mm
2202
2202
2202
Depth
mm
605
605
605
Coolant requirements
l/h
2000
2000
2000
Min. coolant pressure
bar
2.5
2.5
2.5
Max. coolant pressure
bar
6
6
6
Coolant test pressure
bar
10
10
10
Coolant pressure loss
bar
1.9
1.9
1.9
Min. coolant temperature
°C
10
10
10
Max. coolant temperature
°C
35
35
30
Weight, approx.
kg
930
960
1010
General mechanical data
Max. cable length between converter and motor with standard insulation
(shielded)
m
2506)
2506)
2506)
Line/load connection
L1, L2, L3/U2, V2, W2
For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"
Approvals, according to
NRTL7)
NRTL7)
NRTL7)
1) Rated power of a typical 2- to 6-pole standard motor.
2) Typical output voltage dependent on filter and unit type.
3) Maximum power loss with continuous motor current.
4) EMC filter not required for IT system, in which case RI suppression category C4.
5) With IP21 protective top cover (110 mm).
6) Option L10 included (strengthened dv/dt filter; strengthened filter is integrated in unit).
7) On request.
500 V, 12?pulse
Line voltage, supply system type
2 ? 400, 415, 460, 500 V 3 AC IT
SINAMICS G180 cabinet units – air-cooled
6SE0180?2BD33?7?A7
6SE0180?2BD34?6?A7
6SE0180?2BD36?3?A7
6SE0180?2BD37?3?A7
6SE0180?2BD38?2?A7
Converter type (air-cooled)
2T3F?87501?250
2T3F?87501?315
2T3F?87501?400
2T3F?87501?500
2T3F?87501?560
SINAMICS G180 cabinet units – liquid-cooled
6SE0170?2BD33?7?A7
6SE0170?2BD34?6?A7
6SE0170?2BD36?3?A7
6SE0170?2BD37?3?A7
6SE0170?2BD38?2?A7
Converter type (liquid-cooled)
2T6F?77501?250
2T6F?77501?315
2T6F?77501?400
2T6F?77501?500
2T6F?77501?560
Electrical data at motor end
Type rating 1)
at 50 Hz 500 V
kW
250
315
400
500
560
at 60 Hz 460 V
hp
309
389
494
617
691
Output voltage2)
V
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
Output current
Continuous current
A
370
460
640
730
820
Short-time current (60 s every 10 minutes) max.
A
450
560
700
900
980
Overload capability (60 s every 10 minutes) max.
%
22
22
9
23
20
Output power
kVA
320
398
554
632
710
Output frequency, max.
Hz
250
250
250
120
120
Rated clock cycle
kHz
3
3
2.4
2.4
2.4
adjustable from
kHz
2 ... 5
2 ... 5
1.5 ... 3.7
1.5 ... 3.7
1.5 ... 3.7
Power loss 3)
kW
6.15
7.39
9.37
12.8
13.7
Rated efficiency
%
97.7
97.8
97.8
97.6
97.7
Electrical data at line end
Connected load
kVA
303
378
516
606
677
Rated input voltage
V
2 ? 500
2 ? 500
2 ? 500
2 ? 500
2 ? 500
Input current
Continuous line current
A
2 ? 175
2 ? 218
2 ? 298
2 ? 350
2 ? 391
Short-time line current (60 s) max.
A
2 ? 213
2 ? 265
2 ? 326
2 ? 432
2 ? 467
Line fuse (provided by customer)
gL (A)
200
250
400
400
500
?line
0.994
0.994
0.994
0.996
0.996
Cos ?line
1
1
1
1
1
Radio interference suppression acc. to EN 61800?3
C4
C4
C4
C4
C4
Mechanical data for air-cooled cabinet units
Frame size (dimensional drawing classification)
SL5
SL5
SL5
SL5
SL6
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
70
73
73
75
75
Standard converter dimensions
Width
mm
1406
1406
1406
1406
1806
Height4)
mm
2112
2112
2112
2112
2112
Depth
mm
605
605
605
605
605
Coolant requirements
m3/h
1900
1900
1900
2250
3200
Weight, approx.
kg
690
710
730
810
920
Mechanical data for liquid-cooled cabinet units
Frame size (dimensional drawing classification)
SW5
SW5
SW5
SW5
SW6
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
68
71
71
73
73
Standard converter dimensions
Width
mm
1406
1406
1406
1406
2006
Height
mm
2202
2202
2202
2202
2202
Depth
mm
605
605
605
605
605
Coolant requirements
l/h
1200
1200
1200
1200
2000
Min. coolant pressure
bar
2.5
2.5
2.5
2.5
2.5
Max. coolant pressure
bar
6
6
6
6
6
Coolant test pressure
bar
10
10
10
10
10
Coolant pressure loss
bar
1.9
1.9
1.9
1.9
1.9
Min. coolant temperature
°C
10
10
10
10
10
Max. coolant temperature
°C
35
35
35
30
35
Weight, approx.
kg
690
710
730
810
950
General mechanical data
Max. cable length between converter and motor with standard insulation
(shielded)
m
2505)
2505)
2505)
2505)
2505)
Line/load connection
L1, L2, L3/U2, V2, W2
For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"
Approvals, according to
NRTL6)
NRTL6)
NRTL6)
NRTL6)
NRTL6)
1) Rated power of a typical 2- to 6-pole standard motor.
2) Typical output voltage dependent on filter and unit type.
3) Maximum power loss with continuous motor current.
4) With IP21 protective top cover (110 mm).
5) Option L10 included (strengthened dv/dt filter; strengthened filter is integrated in unit).
6) On request.
Line voltage, supply system type
2 ? 400, 415, 460, 500 V 3 AC IT
SINAMICS G180 cabinet units – air-cooled
6SE0180?2BD38?8?A7
6SE0180?2BD41?0?A7
6SE0180?2BD41?1?A7
Converter type (air-cooled)
2T3F?87501?630
2T3F?87501?710
2T3F?87501?800
SINAMICS G180 cabinet units – liquid-cooled
6SE0170?2BD38?8?A7
6SE0170?2BD41?0?A7
6SE0170?2BD41?1?A7
Converter type (liquid-cooled)
2T6F?77501?630
2T6F?77501?710
2T6F?77501?800
Electrical data at motor end
Type rating 1)
at 50 Hz 500 V
kW
630
710
800
at 60 Hz 460 V
hp
777
876
987
Output voltage2)
V
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
Output current
Continuous current
A
920
1030
1150
Short-time current (60 s every 10 minutes) max.
A
1100
1230
1380
Overload capability (60 s every 10 minutes) max.
%
20
19
20
Output power
kVA
797
892
996
Output frequency, max.
Hz
120
120
120
Rated clock cycle
kHz
2.4
2.4
2.4
adjustable from
kHz
1.5 ... 3.7
1.5 ... 3.7
1.5 ... 3.7
Power loss 3)
kW
15.4
18.1
20.3
Rated efficiency
%
97.7
97.6
97.6
Electrical data at line end
Connected load
kVA
767
849
944
Rated input voltage
V
2 ? 500
2 ? 500
2 ? 500
Input current
Continuous line current
A
2 ? 443
2 ? 490
2 ? 545
Short-time line current (60 s) max.
A
2 ? 530
2 ? 585
2 ? 654
Line fuse (provided by customer)
gL (A)
500
630
630
?line
0.996
0.996
0.997
Cos ?line
1
1
1
Radio interference suppression acc. to EN 61800?3
C4
C4
C4
Mechanical data for air-cooled cabinet units
Frame size (dimensional drawing classification)
SL6
SL6
SL6
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
75
75
75
Standard converter dimensions
Width
mm
1806
1806
1806
Height4)
mm
2112
2112
2112
Depth
mm
605
605
605
Coolant requirements
m3/h
3800
3200
3800
Weight, approx.
kg
930
960
1010
Mechanical data for liquid-cooled cabinet units
Frame size (dimensional drawing classification)
SW6
SW6
SW6
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
73
73
73
Standard converter dimensions
Width
mm
2006
2006
2006
Height
mm
2202
2202
2202
Depth
mm
605
605
605
Coolant requirements
l/h
2000
2000
2000
Min. coolant pressure
bar
2.5
2.5
2.5
Max. coolant pressure
bar
6
6
6
Coolant test pressure
bar
10
10
10
Coolant pressure loss
bar
1.9
1.9
1.9
Min. coolant temperature
°C
10
10
10
Max. coolant temperature
°C
35
35
30
Weight, approx.
kg
960
990
1040
General mechanical data
Max. cable length between converter and motor with standard insulation
(shielded)
m
2505)
2505)
2505)
Line/load connection
L1, L2, L3/U2, V2, W2
For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"
Approvals, according to
NRTL6)
NRTL6)
NRTL6)
1) Rated power of a typical 2- to 6-pole standard motor.
2) Typical output voltage dependent on filter and unit type.
3) Maximum power loss with continuous motor current.
4) With IP21 protective top cover (110 mm).
5) Option L10 included (strengthened dv/dt filter; strengthened filter is integrated in unit).
6) On request
690 V, 6?pulse
Line voltage, supply system type
400, 415, 460, 500, 575, 690 V 3 AC TT/TN or IT
SINAMICS G180 cabinet units – air-cooled
6SE0180?1B?33?2?A7
6SE0180?1B?33?6?A7
6SE0180?1B?34?2?A7
6SE0180?1B?35?2?A7
6SE0180?1B?35?7?A7
Converter type (air-cooled)
2T3A?87601?250
2T3A?87601?315
2T3A?87601?400
2T3A?87601?500
2T3A?87601?560
SINAMICS G180 cabinet units – liquid-cooled
6SE0170?1B?33?2?A7
6SE0170?1B?33?6?A7
6SE0170?1B?34?2?A7
6SE0170?1B?35?2?A7
6SE0170?1B?35?7?A7
Converter type (liquid-cooled)
2T6A?77601?250
2T6A?77601?315
2T6A?77601?400
2T6A?77601?500
2T6A?77601?560
Electrical data at motor end
Type rating 1)
at 50 Hz 690 V
kW
250
315
400
500
560
at 60 Hz 575 V
hp
279
352
447
559
626
Output voltage2)
V
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
Output current
Continuous current
A
270
340
440
530
590
Short-time current (60 s every 10 minutes) max.
A
320
410
510
640
710
Overload capability (60 s every 10 minutes) max.
%
19
21
16
21
20
Output power
kVA
323
406
526
633
705
Output frequency, max.
Hz
250
250
250
120
120
Rated clock cycle
kHz
3
3
2.4
2.4
2.4
adjustable from
kHz
2 ... 5
2 ... 5
1.5 ... 3.7
1.5 ... 3.7
1.5 ... 3.7
Power loss 3)
kW
6.15
7.73
9.37
12.2
13.7
Rated efficiency
%
97.7
97.7
97.8
97.7
97.7
Electrical data at line end
Connected load
kVA
312
391
502
608
676
Rated input voltage
V
690
690
690
690
690
Input current
Continuous line current
A
261
327
420
509
566
Short-time line current (60 s) max.
A
309
394
487
615
681
Line fuse (provided by customer)
gL (A)
315
400
500
630
630
?line
0.901
0.905
0.91
0.939
0.94
Cos ?line
1
1
1
1
1
Radio interference suppression acc. to EN 61800?34)
C3 (class A filter)
C3 (class A filter)
C3 (class A filter)
C3 (class A filter)
C3 (class A filter)
Mechanical data for air-cooled cabinet units
Frame size (dimensional drawing classification)
SL2
SL2
SL2
SL21
SL3
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
70
70
70
75
75
Standard converter dimensions
Width
mm
806
806
806
1206
1606
Height5)
mm
2112
2112
2112
2112
2112
Depth
mm
605
605
605
605
605
Coolant requirements
m3/h
1900
1900
1900
2650
3200
Weight, approx.
kg
490
510
530
780
890
Mechanical data for liquid-cooled cabinet units
Frame size (dimensional drawing classification)
SW2
SW2
SW2
SW21
SW3
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
68
68
68
73
73
Standard converter dimensions
Width
mm
806
806
806
1206
1806
Height
mm
2202
2202
2202
2202
2202
Depth
mm
605
605
605
605
605
Coolant requirements
l/h
1200
1200
1200
1200
2000
Min. coolant pressure
bar
2.5
2.5
2.5
2.5
2.5
Max. coolant pressure
bar
6
6
6
6
6
Coolant test pressure
bar
10
10
10
10
10
Coolant pressure loss
bar
1.9
1.9
1.9
1.9
1.9
Min. coolant temperature
°C
10
10
10
10
10
Max. coolant temperature
°C
35
35
35
30
35
Weight, approx.
kg
490
510
530
850
920
General mechanical data
Max. cable length between converter and motor with standard insulation
(shielded)
m
100/2506)
100/250 6)
100/2506)
100/2506)
100/2507)
Line/load connection
L1, L2, L3/U2, V2, W2
For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"
Approvals, according to
NRTL8)
NRTL8)
NRTL8)
NRTL8)
NRTL8)
1) Rated power of a typical 2- to 6-pole standard motor.
2) Typical output voltage dependent on filter and unit type.
3) Maximum power loss with continuous motor current.
4) EMC filter not required for IT system, in which case RI suppression category C4.
5) With IP21 protective top cover (110 mm).
6) Value is applicable with option L10 (strengthened dv/dt filter; filter is integrated in additional 400 mm cabinet).
7) Value is applicable with option L10 (strengthened dv/dt filter; filter is integrated in unit).
8) On request; the voltage range for NRTL units ends at max. 600 V.
Line voltage, supply system type
400, 415, 460, 500, 575, 690 V 3 AC TT/TN or IT
SINAMICS G180 cabinet units – air-cooled
6SE0180?1B?36?4?A7
6SE0180?1B?37?1?A7
6SE0180?1B?37?7?A7
6SE0180?1B?41?0?A7
6SE0180?1B?41?1?A7
Converter type (air-cooled)
2T3A?87601?630
2T3A?87601?710
2T3A?87601?800
2T3A?87601?909
2T3A?87601?910
SINAMICS G180 cabinet units – liquid-cooled
6SE0170?1B?36?4?A7
6SE0170?1B?37?1?A7
6SE0170?1B?37?7?A7
6SE0170?1B?41?0?A7
6SE0170?1B?41?1?A7
Converter type (liquid-cooled)
2T6A?77601?630
2T6A?77601?710
2T6A?77601?800
2T6A?77601?909
2T6A?77601?910
Electrical data at motor end
Type rating 1)
at 50 Hz 690 V
kW
630
710
800
900
1000
at 60 Hz 575 V
hp
704
794
894
1006
1118
Output voltage2)
V
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
Output current
Continuous current
A
660
750
840
950
1040
Short-time current (60 s every 10 minutes) max.
A
800
890
980
1060
1130
Overload capability (60 s every 10 minutes) max.
%
21
19
17
12
9
Output power
kVA
789
896
1004
1135
1243
Output frequency, max.
Hz
120
120
120
120
120
Rated clock cycle
kHz
2.4
2.4
2.4
2.4
2.4
adjustable from
kHz
1.5 ... 3.7
1.5 ... 3.7
1.5 ... 3.7
1.5 ... 3.7
1.5 ... 3.7
Power loss 3)
kW
15.4
16.6
18.7
21
23.3
Rated efficiency
%
97.7
97.8
97.8
97.8
97.8
Electrical data at line end
Connected load
kVA
764
854
956
1078
1165
Rated input voltage
V
690
690
690
690
690
Input current
Continuous line current
A
639
715
800
902
975
Short-time line current (60 s) max.
A
774
848
933
1006
1059
Line fuse (provided by customer)
gL (A)
800
800
900
1000
1000
?line
0.942
0.944
0.945
0.947
0.949
Cos ?line
1
1
1
1
1
Radio interference suppression acc. to EN 61800?34)
C3 (class A filter)
C3 (class A filter)
C3 (class A filter)
C3 (class A filter)
C3 (class A filter)
Mechanical data for air-cooled cabinet units
Frame size (dimensional drawing classification)
SL3
SL3
SL3
SL3
SL3
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
75
75
75
75
75
Standard converter dimensions
Width
mm
1606
1606
1606
1606
1606
Height5)
mm
2112
2112
2112
2112
2112
Depth
mm
605
605
605
605
605
Coolant requirements
m3/h
3200
3800
3200
3800
3800
Weight, approx.
kg
890
900
930
980
1030
Mechanical data for liquid-cooled cabinet units
Frame size (dimensional drawing classification)
SW3
SW3
SW3
SW3
SW3
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
73
73
73
73
73
Standard converter dimensions
Width
mm
1806
1806
1806
1806
1806
Height
mm
2202
2202
2202
2202
2202
Depth
mm
605
605
605
605
605
Coolant requirements
l/h
2000
2000
2000
2000
2000
Min. coolant pressure
bar
2.5
2.5
2.5
2.5
2.5
Max. coolant pressure
bar
6
6
6
6
6
Coolant test pressure
bar
10
10
10
10
10
Coolant pressure loss
bar
1.9
1.9
1.9
1.9
1.9
Min. coolant temperature
°C
10
10
10
10
10
Max. coolant temperature
°C
35
35
35
30
28
Weight, approx.
kg
920
930
960
1010
1060
General mechanical data
Max. cable length between converter and motor with standard insulation
(shielded)
m
100/2506)
100/2506)
100/2507)
100/2507)
100/2507)
Line/load connection
L1, L2, L3/U2, V2, W2
For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"
Approvals, according to
NRTL8)
NRTL8)
NRTL8)
NRTL8)
NRTL8)
1) Rated power of a typical 2- to 6-pole standard motor.
2) Typical output voltage dependent on filter and unit type.
3) Maximum power loss with continuous motor current.
4) EMC filter not required for IT system, in which case RI suppression category C4.
5) With IP21 protective top cover (110 mm).
6) Value is applicable with option L10 (strengthened dv/dt filter; filter is integrated in unit).
7) Value is applicable with option L10 (strengthened dv/dt filter; filter is integrated in additional 600 mm cabinet).
8) On request; the voltage range for NRTL units ends at max. 600 V.
Line voltage, supply system type
400, 415, 460, 500, 575, 690 V 3 AC TT/TN or IT
SINAMICS G180 cabinet units – air-cooled
6SE0180?1C?41?2?A7
6SE0180?1C?41?3?A7
6SE0180?1C?41?5?A7
6SE0180?1C?41?7?A7
6SE0180?1C?42?0?A7
Converter type (air-cooled)
2T3A?87602?912
2T3A?87602?913
2T3A?87602?915
2T3A?87602?917
2T3A?87602?919
SINAMICS G180 cabinet units – liquid-cooled
6SE0170?1C?41?2?A7
6SE0170?1C?41?3?A7
6SE0170?1C?41?5?A7
6SE0170?1C?41?7?A7
6SE0170?1C?42?0?A7
Converter type (liquid-cooled)
2T6A?77602?912
2T6A?77602?913
2T6A?77602?915
2T6A?77602?917
2T6A?77602?919
Electrical data at motor end
Type rating 1)
at 50 Hz 690 V
kW
1200
1300
1500
1700
1900
at 60 Hz 575 V
hp
1341
1453
1676
1900
2123
Output voltage2)
V
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
Output current
Continuous current
A
1260
1430
1600
1810
1980
Short-time current (60 s every 10 minutes) max.
A
1520
1700
1870
2020
2150
Overload capability (60 s every 10 minutes) max.
%
21
19
17
12
9
Output power
kVA
1506
1709
1912
2163
2366
Output frequency, max.
Hz
120
120
120
120
120
Rated clock cycle
kHz
2.4
2.4
2.4
2.4
2.4
adjustable from
kHz
1.5 ... 3.7
1.5 ... 3.7
1.5 ... 3.7
1.5 ... 3.7
1.5 ... 3.7
Power loss 3)
kW
28.2
33.6
37.5
42.6
46.5
Rated efficiency
%
97.8
97.7
97.7
97.7
97.7
Electrical data at line end
Connected load
kVA
1410
1603
1795
2030
2220
Rated input voltage
V
690
690
690
690
690
Input current
Continuous line current
A
1180
1341
1502
1699
1858
Short-time line current (60 s) max.
A
1424
1594
1756
1896
2018
Line fuse (provided by customer)
gL (A)
1250
1500
1600
1800
2000
?line
0.952
0.954
0.956
0.958
0.96
Cos ?line
1
1
1
1
1
Radio interference suppression acc. to EN 61800?34)
C3 (class A filter)
C3 (class A filter)
C3 (class A filter)
C3 (class A filter)
C3 (class A filter)
Mechanical data for air-cooled cabinet units
Frame size (dimensional drawing classification)
SL4
SL4
SL4
SL4
SL4
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
77
77
77
77
77
Standard converter dimensions
Width
mm
3206
3206
3206
3206
3206
Height5)
mm
2112
2112
2112
2112
2112
Depth
mm
605
605
605
605
605
Coolant requirements
m3/h
6400
7600
6400
7600
7600
Weight, approx.
kg
1780
1800
1860
1960
2060
Mechanical data for liquid-cooled cabinet units
Frame size (dimensional drawing classification)
SW4
SW4
SW4
SW4
SW4
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
75
75
75
75
75
Standard converter dimensions
Width
mm
3606
3606
3606
3606
3606
Height
mm
2202
2202
2202
2202
2202
Depth
mm
605
605
605
605
605
Coolant requirements
l/h
4000
4000
4000
4000
4000
Min. coolant pressure
bar
2.5
2.5
2.5
2.5
2.5
Max. coolant pressure
bar
6
6
6
6
6
Coolant test pressure
bar
10
10
10
10
10
Coolant pressure loss
bar
1.9
1.9
1.9
1.9
1.9
Min. coolant temperature
°C
10
10
10
10
10
Max. coolant temperature
°C
35
35
35
30
28
Weight, approx.
kg
1840
1860
1920
2020
2120
General mechanical data
Max. cable length between converter and motor with standard insulation
(shielded)
m
100/2506)
100/2506)
100/2507)
100/2507)
100/2507)
Line/load connection
L1, L2, L3/U2, V2, W2
For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"
Approvals, according to
NRTL8)
NRTL8)
NRTL8)
NRTL8)
NRTL8)
1) Rated power of a typical 2- to 6-pole standard motor.
2) Typical output voltage dependent on filter and unit type.
3) Maximum power loss with continuous motor current.
4) EMC filter not required for IT system, in which case RI suppression category C4.
5) With IP21 protective top cover (110 mm).
6) Value is applicable with option L10 (strengthened dv/dt filter; filter is integrated in unit).
7) Value is applicable with option L10 (strengthened dv/dt filter; filter is integrated in additional 2 x 600 mm cabinet).
8) On request; the voltage range for NRTL units ends at max. 600 V.
690 V, 12?pulse
Line voltage, supply system type
2 ? 400, 415, 460, 500, 575, 690 V 3 AC IT
SINAMICS G180 cabinet units – air-cooled
6SE0180?2BH33?2?A7
6SE0180?2BH33?6?A7
6SE0180?2BH34?2?A7
6SE0180?2BH35?2?A7
6SE0180?2BH35?7?A7
Converter type (air-cooled)
2T3F?87601?250
2T3F?87601?315
2T3F?87601?400
2T3F?87601?500
2T3F?87601?560
SINAMICS G180 cabinet units – liquid-cooled
6SE0170?2BH33?2?A7
6SE0170?2BH33?6?A7
6SE0170?2BH34?2?A7
6SE0170?2BH35?2?A7
6SE0170?2BH35?7?A7
Converter type (liquid-cooled)
2T6F?77601?250
2T6F?77601?315
2T6F?77601?400
2T6F?77601?500
2T6F?77601?560
Electrical data at motor end
Type rating 1)
at 50 Hz 690 V
kW
250
315
400
500
560
at 60 Hz 575 V
hp
279
352
447
559
626
Output voltage2)
V
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
Output current
Continuous current
A
270
340
440
530
590
Short-time current (60 s every 10 minutes) max.
A
320
410
510
640
710
Overload capability (60 s every 10 minutes) max.
%
19
21
16
21
20
Output power
kVA
323
406
526
633
705
Output frequency, max.
Hz
250
250
250
120
120
Rated clock cycle
kHz
3
3
2.4
2.4
2.4
adjustable from
kHz
2 ... 5
2 ... 5
1.5 ... 3.7
1.5 ... 3.7
1.5 ... 3.7
Power loss 3)
kW
6.15
7.73
9.37
12.2
13.7
Rated efficiency
%
97.7
97.7
97.8
97.7
97.7
Electrical data at line end
Connected load
kVA
311
392
502
600
667
Rated input voltage
V
2 ? 690
2 ? 690
2 ? 690
2 ? 690
2 ? 690
Input current
Continuous line current
A
2 ? 130
2 ? 164
2 ? 210
2 ? 251
2 ? 279
Short-time line current (60 s) max.
A
2 ? 154
2 ? 198
2 ? 243
2 ? 303
2 ? 336
Line fuse (provided by customer)
gL (A)
160
200
250
315
315
?line
0.995
0.995
0.995
0.997
0.997
Cos ?line
1
1
1
1
1
Radio interference suppression acc. to EN 61800?3
C4
C4
C4
C4
C4
Mechanical data for air-cooled cabinet units
Frame size (dimensional drawing classification)
SL5
SL5
SL5
SL5
SL6
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
70
70
70
75
75
Standard converter dimensions
Width
mm
1406
1406
1406
1406
1806
Height4)
mm
2112
2112
2112
2112
2112
Depth
mm
605
605
605
605
605
Coolant requirements
m3/h
1900
1900
1900
2650
3200
Weight, approx.
kg
690
710
730
810
920
Mechanical data for liquid-cooled cabinet units
Frame size (dimensional drawing classification)
SW5
SW5
SW5
SW5
SW6
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
68
68
68
73
73
Standard converter dimensions
Width
mm
1406
1406
1406
1406
2006
Height
mm
2202
2202
2202
2202
2202
Depth
mm
605
605
605
605
605
Coolant requirements
l/h
1200
1200
1200
1200
2000
Min. coolant pressure
bar
2.5
2.5
2.5
2.5
2.5
Max. coolant pressure
bar
6
6
6
6
6
Coolant test pressure
bar
10
10
10
10
10
Coolant pressure loss
bar
1.9
1.9
1.9
1.9
1.9
Min. coolant temperature
°C
10
10
10
10
10
Max. coolant temperature
°C
35
35
35
30
35
Weight, approx.
kg
690
710
730
810
950
General mechanical data
Max. cable length between converter and motor with standard insulation
(shielded)
m
100/2505)
100/2505)
100/2505)
100/2505)
100/2506)
Line/load connection
L1, L2, L3/U2, V2, W2
For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"
Approvals, according to
NRTL7)
NRTL7)
NRTL7)
NRTL7)
NRTL7)
1) Rated power of a typical 2- to 6-pole standard motor.
2) Typical output voltage dependent on filter and unit type.
3) Maximum power loss with continuous motor current.
4) With IP21 protective top cover (110 mm).
5) Value is applicable with option L10 (strengthened dv/dt filter; filter is integrated in additional 400 mm cabinet).
6) Value is applicable with option L10 (strengthened dv/dt filter; filter is integrated in unit).
7) On request; the voltage range for NRTL units ends at max. 600 V.
Line voltage, supply system type
2 ? 400, 415, 460, 500, 575, 690 V 3 AC IT
SINAMICS G180 cabinet units – air-cooled
6SE0180?2BH36?4?A7
6SE0180?2BH37?1?A7
6SE0180?2BH37?7?A7
6SE0180?2BH41?0?A7
6SE0180?2BH41?1?A7
Converter type (air-cooled)
2T3F?87601?630
2T3F?87601?710
2T3F?87601?800
2T3F?87601?909
2T3F?87601?910
SINAMICS G180 cabinet units – liquid-cooled
6SE0170?2BH36?4?A7
6SE0170?2BH37?1?A7
6SE0170?2BH37?7?A7
6SE0170?2BH41?0?A7
6SE0170?2BH41?1?A7
Converter type (liquid-cooled)
2T6F?77601?630
2T6F?77601?710
2T6F?77601?800
2T6F?77601?909
2T6F?77601?910
Electrical data at motor end
Type rating 1)
at 50 Hz 690 V
kW
630
710
800
900
1000
at 60 Hz 575 V
hp
704
794
894
1006
1118
Output voltage2)
V
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
Output current
Continuous current
A
660
750
840
950
1040
Short-time current (60 s every 10 minutes) max.
A
800
890
980
1060
1130
Overload capability (60 s every 10 minutes) max.
%
21
19
17
12
9
Output power
kVA
789
896
1004
1135
1243
Output frequency, max.
Hz
120
120
120
120
120
Rated clock cycle
kHz
2.4
2.4
2.4
2.4
2.4
adjustable from
kHz
1.5 ... 3.7
1.5 ... 3.7
1.5 ... 3.7
1.5 ... 3.7
1.5 ... 3.7
Power loss 3)
kW
15.4
16.6
18.7
21
23.3
Rated efficiency
%
97.7
97.8
97.8
97.8
97.8
Electrical data at line end
Connected load
kVA
755
848
949
1071
1159
Rated input voltage
V
2 ? 690
2 ? 690
2 ? 690
2 ? 690
2 ? 690
Input current
Continuous line current
A
2 ? 316
2 ? 355
2 ? 397
2 ? 448
2 ? 485
Short-time line current (60 s) max.
A
2 ? 383
2 ? 421
2 ? 463
2 ? 500
2 ? 527
Line fuse (provided by customer)
gL (A)
400
400
500
500
630
?line
0.997
0.997
0.997
0.997
0.997
Cos ?line
1
1
1
1
1
Radio interference suppression acc. to EN 61800?3
C4
C4
C4
C4
C4
Mechanical data for air-cooled cabinet units
Frame size (dimensional drawing classification)
SL6
SL6
SL6
SL6
SL6
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
75
75
75
75
75
Standard converter dimensions
Width
mm
1806
1806
1806
1806
1806
Height4)
mm
2112
2112
2112
2112
2112
Depth
mm
605
605
605
605
605
Coolant requirements
m3/h
3200
3800
3200
3800
3800
Weight, approx.
kg
920
930
960
1010
1060
Mechanical data for liquid-cooled cabinet units
Frame size (dimensional drawing classification)
SW6
SW6
SW6
SW6
SW6
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
73
73
73
73
73
Standard converter dimensions
Width
mm
2006
2006
2006
2006
2006
Height
mm
2202
2202
2202
2202
2202
Depth
mm
605
605
605
605
605
Coolant requirements
l/h
2000
2000
2000
2000
2000
Min. coolant pressure
bar
2.5
2.5
2.5
2.5
2.5
Max. coolant pressure
bar
6
6
6
6
6
Coolant test pressure
bar
10
10
10
10
10
Coolant pressure loss
bar
1.9
1.9
1.9
1.9
1.9
Min. coolant temperature
°C
10
10
10
10
10
Max. coolant temperature
°C
35
35
35
30
28
Weight, approx.
kg
950
960
990
1040
1090
General mechanical data
Max. cable length between converter and motor with standard insulation
(shielded)
m
100/2505)
100/2505)
100/2506)
100/2506)
100/2506)
Line/load connection
L1, L2, L3/U2, V2, W2
For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"
Approvals, according to
NRTL7)
NRTL7)
NRTL7)
NRTL7)
NRTL7)
1) Rated power of a typical 2- to 6-pole standard motor.
2) Typical output voltage dependent on filter and unit type.
3) Maximum power loss with continuous motor current.
4) With IP21 protective top cover (110 mm).
5) Value is applicable with option L10 (strengthened dv/dt filter; filter is integrated in unit).
6) Value is applicable with option L10 (strengthened dv/dt filter; filter is integrated in additional 600 mm cabinet).
7) On request; the voltage range for NRTL units ends at max. 600 V.
Line voltage, supply system type
2 ? 400, 415, 460, 500, 575, 690 V 3 AC IT
SINAMICS G180 cabinet units – air-cooled
6SE0180?2CH41?2?A7
6SE0180?2CH41?3?A7
6SE0180?2CH41?5?A7
6SE0180?2CH41?7?A7
6SE0180?2CH42?0?A7
Converter type (air-cooled)
2T3F?87602?912
2T3F?87602?913
2T3F?87602?915
2T3F?87602?917
2T3F?87602?919
SINAMICS G180 cabinet units – liquid-cooled
6SE0170?2CH41?2?A7
6SE0170?2CH41?3?A7
6SE0170?2CH41?5?A7
6SE0170?2CH41?7?A7
6SE0170?2CH42?0?A7
Converter type (liquid-cooled)
2T6F?77602?912
2T6F?77602?913
2T6F?77602?915
2T6F?77602?917
2T6F?77602?919
Electrical data at motor end
Type rating 1)
at 50 Hz 690 V
kW
1200
1300
1500
1700
1900
at 60 Hz 575 V
hp
1341
1453
1676
1900
2123
Output voltage2)
V
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
Output current
Continuous current
A
1260
1430
1600
1810
1980
Short-time current (60 s every 10 minutes) max.
A
1520
1700
1870
2020
2150
Overload capability (60 s every 10 minutes) max.
%
21
19
17
12
9
Output power
kVA
1506
1709
1912
2163
2366
Output frequency, max.
Hz
120
120
120
120
120
Rated clock cycle
kHz
2.4
2.4
2.4
2.4
2.4
adjustable from
kHz
1.5 ... 3.7
1.5 ... 3.7
1.5 ... 3.7
1.5 ... 3.7
1.5 ... 3.7
Power loss 3)
kW
28.2
33.6
37.5
42.6
46.5
Rated efficiency
%
97.8
97.7
97.7
97.7
97.7
Electrical data at line end
Connected load
kVA
1405
1597
1781
2010
2194
Rated input voltage
V
2 ? 690
2 ? 690
2 ? 690
2 ? 690
2 ? 690
Input current
Continuous line current
A
2 ? 588
2 ? 668
2 ? 745
2 ? 841
2 ? 918
Short-time line current (60 s) max.
A
2 ? 709
2 ? 794
2 ? 871
2 ? 939
2 ? 997
Line fuse (provided by customer)
gL (A)
800
800
900
1000
1250
?line
0.997
0.997
0.997
0.997
0.997
Cos ?line
1
1
1
1
1
Radio interference suppression acc. to EN 61800?3
C4
C4
C4
C4
C4
Mechanical data for air-cooled cabinet units
Frame size (dimensional drawing classification)
SL4
SL4
SL4
SL4
SL4
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
77
77
77
77
77
Standard converter dimensions
Width
mm
3206
3206
3206
3206
3206
Height4)
mm
2112
2112
2112
2112
2112
Depth
mm
605
605
605
605
605
Coolant requirements
m3/h
6400
7600
6400
7600
7600
Weight, approx.
kg
1780
1800
1860
1960
2060
Mechanical data for liquid-cooled cabinet units
Frame size (dimensional drawing classification)
SW4
SW4
SW4
SW4
SW4
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
75
75
75
75
75
Standard converter dimensions
Width
mm
3606
3606
3606
3606
3606
Height
mm
2202
2202
2202
2202
2202
Depth
mm
605
605
605
605
605
Coolant requirements
l/h
4000
4000
4000
4000
4000
Min. coolant pressure
bar
2.5
2.5
2.5
2.5
2.5
Max. coolant pressure
bar
6
6
6
6
6
Coolant test pressure
bar
10
10
10
10
10
Coolant pressure loss
bar
1.9
1.9
1.9
1.9
1.9
Min. coolant temperature
°C
10
10
10
10
10
Max. coolant temperature
°C
35
35
35
30
28
Weight, approx.
kg
1840
1860
1920
2020
2120
General mechanical data
Max. cable length between converter and motor with standard insulation
(shielded)
m
100/2505)
100/2505)
100/2506)
100/2506)
100/2506)
Line/load connection
L1, L2, L3/U2, V2, W2
For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"
Approvals, according to
NRTL7)
NRTL7)
NRTL7)
NRTL7)
NRTL7)
1) Rated power of a typical 2- to 6-pole standard motor.
2) Typical output voltage dependent on filter and unit type.
3) Maximum power loss with continuous motor current.
4) With IP21 protective top cover (110 mm).
5) Value is applicable with option L10 (strengthened dv/dt filter; filter is integrated in unit).
6) Value is applicable with option L10 (strengthened dv/dt filter; filter is integrated in additional 2 x 600 mm cabinet).
7) On request; the voltage range for NRTL units ends at max. 600 V.
Line voltage, supply system type
2 ? 400, 415, 460, 500, 575, 690 V 3 AC IT
SINAMICS G180 cabinet units – air-cooled
6SE0180?2DH42?2?A7
6SE0180?2DH42?4?A7
6SE0180?2DH42?7?A7
6SE0180?2DH43?0?A7
6SE0180?2EH43?2?A7
Converter type (air-cooled)
2T3F?87603?920
2T3F?87603?923
2T3F?87603?926
2T3F?87603?929
2T3F?87604?931
SINAMICS G180 cabinet units – liquid-cooled
6SE0170?2DH42?2?A7
6SE0170?2DH42?4?A7
6SE0170?2DH42?7?A7
6SE0170?2DH43?0?A7
6SE0170?2EH43?2?A7
Converter type (liquid-cooled)
2T6F?77603?920
2T6F?77603?923
2T6F?77603?926
2T6F?77603?929
2T6F?77604?931
Electrical data at motor end
Type rating 1)
at 50 Hz 690 V
kW
2000
2300
2600
2900
3100
at 60 Hz 575 V
hp
2235
2570
2906
3241
3465
Output voltage2)
V
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
Output current
Continuous current
A
2140
2400
2710
2970
3200
Short-time current (60 s every 10 minutes) max.
A
2540
2800
3030
3230
3730
Overload capability (60 s every 10 minutes) max.
%
19
17
12
9
17
Output power
kVA
2558
2868
3239
3549
3824
Output frequency, max.
Hz
120
120
120
120
120
Rated clock cycle
kHz
2.4
2.4
2.4
2.4
2.4
adjustable from
kHz
1.5 ... 3.7
1.5 ... 3.7
1.5 ... 3.7
1.5 ... 3.7
1.5 ... 3.7
Power loss 3)
kW
50.9
57.2
64.5
73.9
77.3
Rated efficiency
%
97.7
97.7
97.7
97.6
97.7
Electrical data at line end
Connected load
kVA
2369
2648
2983
3272
3516
Rated input voltage
V
2 ? 690
2 ? 690
2 ? 690
2 ? 690
2 ? 690
Input current
Continuous line current
A
2 ? 991
2 ? 1108
2 ? 1248
2 ? 1369
2 ? 1471
Short-time line current (60 s) max.
A
2 ? 1176
2 ? 1293
2 ? 1395
2 ? 1489
2 ? 1715
Line fuse (provided by customer)
gL (A)
1250
1250
1500
1600
1800
?line
0.997
0.997
0.997
0.997
0.997
Cos ?line
1
1
1
1
1
Radio interference suppression acc. to EN 61800?3
C4
C4
C4
C4
C4
Mechanical data for air-cooled cabinet units
Frame size (dimensional drawing classification)
SL7
SL7
SL7
SL7
SL8
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
78
78
78
78
79
Standard converter dimensions
Width
mm
4806
4806
4806
4806
6406
Height4)
mm
2112
2112
2112
2112
2112
Depth
mm
605
605
605
605
605
Coolant requirements
m3/h
11400
9600
11400
11400
12800
Weight, approx.
kg
2700
2790
2940
3090
3720
Mechanical data for liquid-cooled cabinet units
Frame size (dimensional drawing classification)
SW7
SW7
SW7
SW7
SW8
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
76
76
76
76
77
Standard converter dimensions
Width
mm
5206
5206
5206
5206
7006
Height
mm
2202
2202
2202
2202
2202
Depth
mm
605
605
605
605
605
Coolant requirements
l/h
6000
6000
6000
6000
8000
Min. coolant pressure
bar
2.5
2.5
2.5
2.5
2.5
Max. coolant pressure
bar
6
6
6
6
6
Coolant test pressure
bar
10
10
10
10
10
Coolant pressure loss
bar
1.9
1.9
1.9
1.9
1.9
Min. coolant temperature
°C
10
10
10
10
10
Max. coolant temperature
°C
35
35
30
28
35
Weight, approx.
kg
2750
2850
2850
3100
3850
General mechanical data
Max. cable length between converter and motor with standard insulation
(shielded)
m
100/2505)
100/2506)
100/2506)
100/2506)
100/2507)
Line/load connection
L1, L2, L3/U2, V2, W2
For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"
Approvals, according to
NRTL8)
NRTL8)
NRTL8)
NRTL8)
NRTL8)
1) Rated power of a typical 2- to 6-pole standard motor.
2) Typical output voltage dependent on filter and unit type.
3) Maximum power loss with continuous motor current.
4) With IP21 protective top cover (110 mm).
5) Value is applicable with option L10 (strengthened dv/dt filter; filter is integrated in unit).
6) Value is applicable with option L10 (strengthened dv/dt filter; filter is integrated in additional 3 x 600 mm cabinet).
7) Value is applicable with option L10 (strengthened dv/dt filter; filter is integrated in additional 4 x 600 mm cabinet).
8) On request; the voltage range for NRTL units ends at max. 600 V.
Line voltage, supply system type
2 ? 400, 415, 460, 500, 575, 690 V 3 AC IT
SINAMICS G180 cabinet units – air-cooled
6SE0180?2EH43?6?A7
6SE0180?2EH44?0?A7
Converter type (air-cooled)
2T3F?87604?935
2T3F?87604?939
SINAMICS G180 cabinet units – liquid-cooled
6SE0170?2EH43?6?A7
6SE0170?2EH44?0?A7
Converter type (liquid-cooled)
2T6F?77604?935
2T6F?77604?939
Electrical data at motor end
Type rating 1)
at 50 Hz 690 V
kW
3500
3900
at 60 Hz 575 V
hp
3912
4359
Output voltage2)
V
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
Output current
Continuous current
A
3610
3960
Short-time current (60 s every 10 minutes) max.
A
4030
4300
Overload capability (60 s every 10 minutes) max.
%
12
9
Output power
kVA
4314
4732
Output frequency, max.
Hz
120
120
Rated clock cycle
kHz
2.4
2.4
adjustable from
kHz
1.5 ... 3.7
1.5 ... 3.7
Power loss 3)
kW
87.3
99.7
Rated efficiency
%
97.7
97.6
Electrical data at line end
Connected load
kVA
3956
4336
Rated input voltage
V
2 ? 690
2 ? 690
Input current
Continuous line current
A
2 ? 1655
2 ? 1814
Short-time line current (60 s) max.
A
2 ? 1848
2 ? 1970
Line fuse (provided by customer)
gL (A)
2000
2000
?line
0.997
0.997
Cos ?line
1
1
Radio interference suppression acc. to EN 61800?3
C4
C4
Mechanical data for air-cooled cabinet units
Frame size (dimensional drawing classification)
SL8
SL8
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
79
79
Standard converter dimensions
Width
mm
6406
6406
Height4)
mm
2112
2112
Depth
mm
605
605
Coolant requirements
m3/h
15200
15200
Weight, approx.
kg
3920
4120
Mechanical data for liquid-cooled cabinet units
Frame size (dimensional drawing classification)
SW8
SW8
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
77
77
Standard converter dimensions
Width
mm
7006
7006
Height
mm
2202
2202
Depth
mm
605
605
Coolant requirements
l/h
8000
8000
Min. coolant pressure
bar
2.5
2.5
Max. coolant pressure
bar
6
6
Coolant test pressure
bar
10
10
Coolant pressure loss
bar
1.9
1.9
Min. coolant temperature
°C
10
10
Max. coolant temperature
°C
30
28
Weight, approx.
kg
4050
4250
General mechanical data
Max. cable length between converter and motor with standard insulation
(shielded)
m
100/2505)
100/2505)
Line/load connection
L1, L2, L3/U2, V2, W2
For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"
Approvals, according to
NRTL6)
NRTL6)
1) Rated power of a typical 2- to 6-pole standard motor.
2) Typical output voltage dependent on filter and unit type.
3) Maximum power loss with continuous motor current.
4) With IP21 protective top cover (110 mm).
5) Value is applicable with option L10 (strengthened dv/dt filter; filter is integrated in additional 4 x 600 mm cabinet).
6) On request; the voltage range for NRTL units ends at max. 600 V.
690 V, 18?pulse
Line voltage, supply system type
3 ? 400, 415, 460, 500, 575, 690 V 3 AC IT
SINAMICS G180 cabinet units – air-cooled
6SE0180?3DH42?2?A7
6SE0180?3DH42?4?A7
6SE0180?3DH42?7?A7
6SE0180?3DH43?0?A7
6SE0180?3HH44?3?A7
Converter type (air-cooled)
2T3K?87603?920
2T3K?87603?923
2T3K?87603?926
2T3K?87603?929
2T3K?87606?941
SINAMICS G180 cabinet units – liquid-cooled
6SE0170?3DH42?2?A7
6SE0170?3DH42?4?A7
6SE0170?3DH42?7?A7
6SE0170?3DH43?0?A7
6SE0170?3HH44?3?A7
Converter type (liquid-cooled)
2T6K?77603?920
2T6K?77603?923
2T6K?77603?926
2T6K?77603?929
2T6K?77606?941
Electrical data at motor end
Type rating 1)
at 50 Hz 690 V
kW
2000
2300
2600
2900
4100
at 60 Hz 575 V
hp
2235
2570
2906
3241
4582
Output voltage2)
V
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
Output current
Continuous current
A
2140
2400
2710
2970
4290
Short-time current (60 s every 10 minutes) max.
A
2540
2800
3030
3230
5100
Overload capability (60 s every 10 minutes) max.
%
19
17
12
9
19
Output power
kVA
2558
2868
3239
3549
5127
Output frequency, max.
Hz
120
120
120
120
120
Rated clock cycle
kHz
2.4
2.4
2.4
2.4
2.4
adjustable from
kHz
1.5 ... 3.7
1.5 ... 3.7
1.5 ... 3.7
1.5 ... 3.7
1.5 ... 3.7
Power loss 3)
kW
50.9
57.2
64.5
73.9
102
Rated efficiency
%
97.7
97.7
97.7
97.6
97.7
Electrical data at line end
Connected load
kVA
2369
2648
2983
3272
4692
Rated input voltage
V
3 ? 690
3 ? 690
3 ? 690
3 ? 690
3 ? 690
Input current
Continuous line current
A
3 ? 661
3 ? 739
3 ? 832
3 ? 912
3 ? 1308
Short-time line current (60 s) max.
A
3 ? 785
3 ? 862
3 ? 930
3 ? 992
3 ? 1555
Line fuse (provided by customer)
gL (A)
800
900
1000
1250
1500
?line
1
1
1
1
1
Cos ?line
1
1
1
1
1
Radio interference suppression acc. to EN 61800?3
C4
C4
C4
C4
C4
Mechanical data for air-cooled cabinet units
Frame size (dimensional drawing classification)
SL7
SL7
SL7
SL7
SL11
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
78
78
78
78
79
Standard converter dimensions
Width
mm
4806
4806
4806
4806
10206
Height4)
mm
2112
2112
2112
2112
2112
Depth
mm
605
605
605
605
605
Coolant requirements
m3/h
11400
9600
11400
11400
23150
Weight, approx.
kg
2750
2840
2990
3140
5750
Mechanical data for liquid-cooled cabinet units
Frame size (dimensional drawing classification)
SW7
SW7
SW7
SW7
–5)
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
76
76
76
76
77
Standard converter dimensions
Width
mm
5206
5206
5206
5206
–5)
Height
mm
2202
2202
2202
2202
–5)
Depth
mm
605
605
605
605
–5)
Coolant requirements
l/h
6000
6000
6000
6000
12000
Min. coolant pressure
bar
2.5
2.5
2.5
2.5
2.5
Max. coolant pressure
bar
6
6
6
6
6
Coolant test pressure
bar
10
10
10
10
10
Coolant pressure loss
bar
1.9
1.9
1.9
1.9
1.9
Min. coolant temperature
°C
10
10
10
10
10
Max. coolant temperature
°C
35
35
30
28
35
Weight, approx.
kg
2830
2920
3070
3220
5910
General mechanical data
Max. cable length between converter and motor with standard insulation
(shielded)
m
100/2506)
100/2507)
100/2507)
100/2507)
100/2506)
Line/load connection
L1, L2, L3/U2, V2, W2
For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"
Approvals, according to
NRTL8)
NRTL8)
NRTL8)
NRTL8)
NRTL8)
1) Rated power of a typical 2- to 6-pole standard motor.
2) Typical output voltage dependent on filter and unit type.
3) Maximum power loss with continuous motor current.
4) With IP21 protective top cover (110 mm).
5) Dimensions on request.
6) Value is applicable with option L10 (strengthened dv/dt filter; filter is integrated in unit).
7) Value is applicable with option L10 (strengthened dv/dt filter; filter is integrated in additional 3 x 600 mm cabinet).
8) On request; the voltage range for NRTL units ends at max. 600 V.
Line voltage, supply system type
3 ? 400, 415, 460, 500, 575, 690 V 3 AC IT
SINAMICS G180 cabinet units – air-cooled
6SE0180?3HH44?8?A7
6SE0180?3HH45?4?A7
6SE0180?3HH46?0?A7
Converter type (air-cooled)
2T3K?87606?947
2T3K?87606?953
2T3K?87606?958
SINAMICS G180 cabinet units – liquid-cooled
6SE0170?3HH44?8?A7
6SE0170?3HH45?4?A7
6SE0170?3HH46?0?A7
Converter type (liquid-cooled)
2T6K?77606?947
2T6K?77606?953
2T6K?77606?958
Electrical data at motor end
Type rating 1)
at 50 Hz 690 V
kW
4700
5300
5800
at 60 Hz 575 V
hp
5253
5923
6482
Output voltage2)
V
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
Output current
Continuous current
A
4800
5420
5940
Short-time current (60 s every 10 minutes) max.
A
5610
6040
6450
Overload capability (60 s every 10 minutes) max.
%
17
11
9
Output power
kVA
5736
6477
7099
Output frequency, max.
Hz
120
120
120
Rated clock cycle
kHz
2.4
2.4
2.4
adjustable from
kHz
1.5 ... 3.7
1.5 ... 3.7
1.5 ... 3.7
Power loss 3)
kW
110
118
129
Rated efficiency
%
97.8
97.9
97.9
Electrical data at line end
Connected load
kVA
5244
5916
6482
Rated input voltage
V
3 ? 690
3 ? 690
3 ? 690
Input current
Continuous line current
A
3 ? 1462
3 ? 1651
3 ? 1809
Short-time line current (60 s) max.
A
3 ? 1709
3 ? 1840
3 ? 1964
Line fuse (provided by customer)
gL (A)
1800
2000
2000 ... 2500
?line
1
1
1
Cos ?line
1
1
1
Radio interference suppression acc. to EN 61800?3
C4
C4
C4
Mechanical data for air-cooled cabinet units
Frame size (dimensional drawing classification)
SL11
SL11
SL11
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
79
79
79
Standard converter dimensions
Width
mm
10206
10206
10206
Height4)
mm
2112
2112
2112
Depth
mm
605
605
605
Coolant requirements
m3/h
19550
23150
23150
Weight, approx.
kg
5930
6230
6530
Mechanical data for liquid-cooled cabinet units
Frame size (dimensional drawing classification)
–5)
–5)
–5)
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
77
77
77
Standard converter dimensions
Width
mm
–5)
–5)
–5)
Height
mm
–5)
–5)
–5)
Depth
mm
–5)
–5)
–5)
Coolant requirements
l/h
12000
12000
12000
Min. coolant pressure
bar
2.5
2.5
2.5
Max. coolant pressure
bar
6
6
6
Coolant test pressure
bar
10
10
10
Coolant pressure loss
bar
1.9
1.9
1.9
Min. coolant temperature
°C
10
10
10
Max. coolant temperature
°C
38
30
28
Weight, approx.
kg
6090
6390
6690
General mechanical data
Max. cable length between converter and motor with standard insulation
(shielded)
m
100/2506)
100/2506)
100/2506)
Line/load connection
L1, L2, L3/U2, V2, W2
For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"
Approvals, according to
NRTL7)
NRTL7)
NRTL7)
1) Rated power of a typical 2- to 6-pole standard motor.
2) Typical output voltage dependent on filter and unit type.
3) Maximum power loss with continuous motor current.
4) With IP21 protective top cover (110 mm).
5) Dimensions on request.
6) Value is applicable with option L10 (strengthened dv/dt filter; filter is integrated in additional 6 x 600 mm cabinet).
7) On request; the voltage range for NRTL units ends at max. 600 V.
690 V, 24?pulse
Line voltage, supply system type
4 ? 400, 415, 460, 500, 575, 690 V 3 AC IT
SINAMICS G180 cabinet units – air-cooled
6SE0180?4CH41?2?A7
6SE0180?4CH41?3?A7
6SE0180?4CH41?5?A7
6SE0180?4CH41?7?A7
6SE0180?4CH42?0?A7
Converter type (air-cooled)
2T3L?87602?912
2T3L?87602?913
2T3L?87602?915
2T3L?87602?917
2T3L?87602?919
SINAMICS G180 cabinet units – liquid-cooled
6SE0170?4CH41?2?A7
6SE0170?4CH41?3?A7
6SE0170?4CH41?5?A7
6SE0170?4CH41?7?A7
6SE0170?4CH42?0?A7
Converter type (liquid-cooled)
2T6L?77602?912
2T6L?77602?913
2T6L?77602?915
2T6L?77602?917
2T6L?77602?919
Electrical data at motor end
Type rating 1)
at 50 Hz 690 V
kW
1200
1300
1500
1700
1900
at 60 Hz 575 V
hp
1341
1453
1676
1900
2123
Output voltage2)
V
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
Output current
Continuous current
A
1260
1430
1600
1810
1980
Short-time current (60 s every 10 minutes) max.
A
1520
1700
1870
2020
2150
Overload capability (60 s every 10 minutes) max.
%
21
19
17
12
9
Output power
kVA
1506
1709
1912
2163
2366
Output frequency, max.
Hz
120
120
120
120
120
Rated clock cycle
kHz
2.4
2.4
2.4
2.4
2.4
adjustable from
kHz
1.5 ... 3.7
1.5 ... 3.7
1.5 ... 3.7
1.5 ... 3.7
1.5 ... 3.7
Power loss 3)
kW
28.2
33.6
37.5
42.6
46.5
Rated efficiency
%
97.8
97.7
97.7
97.7
97.7
Electrical data at line end
Connected load
kVA
1405
1597
1781
2010
2194
Rated input voltage
V
4 ? 690
4 ? 690
4 ? 690
4 ? 690
4 ? 690
Input current
Continuous line current
A
4 ? 294
4 ? 333
4 ? 372
4 ? 421
4 ? 459
Short-time line current (60 s) max.
A
4 ? 355
4 ? 396
4 ? 435
4 ? 470
4 ? 498
Line fuse (provided by customer)
gL (A)
400
400
500
500
630
?line
1
1
1
1
1
Cos ?line
1
1
1
1
1
Radio interference suppression acc. to EN 61800?3
C4
C4
C4
C4
C4
Mechanical data for air-cooled cabinet units
Frame size (dimensional drawing classification)
SL9
SL9
SL9
SL9
SL9
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
77
77
77
77
77
Standard converter dimensions
Width
mm
3606
3606
3606
3606
3606
Height4)
mm
2112
2112
2112
2112
2112
Depth
mm
605
605
605
605
605
Coolant requirements
m3/h
6400
7600
6400
7600
7600
Weight, approx.
kg
1830
1850
1910
2010
2110
Mechanical data for liquid-cooled cabinet units
Frame size (dimensional drawing classification)
SW9
SW9
SW9
SW9
SW9
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
75
75
75
75
75
Standard converter dimensions
Width
mm
4406
4406
4406
4406
4406
Height
mm
2202
2202
2202
2202
2202
Depth
mm
605
605
605
605
605
Coolant requirements
l/h
4000
4000
4000
4000
4000
Min. coolant pressure
bar
2.5
2.5
2.5
2.5
2.5
Max. coolant pressure
bar
6
6
6
6
6
Coolant test pressure
bar
10
10
10
10
10
Coolant pressure loss
bar
1.9
1.9
1.9
1.9
1.9
Min. coolant temperature
°C
10
10
10
10
10
Max. coolant temperature
°C
35
35
35
30
28
Weight, approx.
kg
1930
1950
2010
2100
2160
General mechanical data
Max. cable length between converter and motor with standard insulation
(shielded)
m
100/2505)
100/2505)
100/2506)
100/2506)
100/2506)
Line/load connection
L1, L2, L3/U2, V2, W2
For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"
Approvals, according to
NRTL7)
NRTL7)
NRTL7)
NRTL7)
NRTL7)
1) Rated power of a typical 2- to 6-pole standard motor.
2) Typical output voltage dependent on filter and unit type.
3) Maximum power loss with continuous motor current.
4) With IP21 protective top cover (110 mm).
5) Value is applicable with option L10 (strengthened dv/dt filter; filter is integrated in unit).
6) Value is applicable with option L10 (strengthened dv/dt filter; filter is integrated in additional 600 mm cabinet).
7) On request; the voltage range for NRTL units ends at max. 600 V.
Line voltage, supply system type
4 ? 400, 415, 460, 500, 575, 690 V 3 AC IT
SINAMICS G180 cabinet units – air-cooled
6SE0180?4EH43?2?A7
6SE0180?4EH43?6?A7
6SE0180?4EH44?0?A7
6SE0180?4HH44?3?A7
6SE0180?4HH44?8?A7
Converter type (air-cooled)
2T3L?87604?931
2T3L?87604?935
2T3L?87604?939
2T3L?87606?941
2T3L?87606?947
SINAMICS G180 cabinet units – liquid-cooled
6SE0170?4EH43?2?A7
6SE0170?4EH43?6?A7
6SE0170?4EH44?0?A7
6SE0170?4HH44?3?A7
6SE0170?4HH44?8?A7
Converter type (liquid-cooled)
2T6L?77604?931
2T6L?77604?935
2T6L?77604?939
2T6L?77606?941
2T6L?77606?947
Electrical data at motor end
Type rating 1)
at 50 Hz 690 V
kW
3100
3500
3900
4100
4700
at 60 Hz 575 V
hp
3465
3912
4359
4582
5253
Output voltage2)
V
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
Output current
Continuous current
A
3200
3610
3960
4290
4800
Short-time current (60 s every 10 minutes) max.
A
3730
4030
4300
5100
5610
Overload capability (60 s every 10 minutes) max.
%
17
12
9
19
17
Output power
kVA
3824
4314
4732
5127
5736
Output frequency, max.
Hz
120
120
120
120
120
Rated clock cycle
kHz
2.4
2.4
2.4
2.4
2.4
adjustable from
kHz
1.5 ... 3.7
1.5 ... 3.7
1.5 ... 3.7
1.5 ... 3.7
1.5 ... 3.7
Power loss 3)
kW
77.3
87.3
99.7
102
110
Rated efficiency
%
97.7
97.7
97.6
97.7
97.8
Electrical data at line end
Connected load
kVA
3516
3956
4336
4692
5244
Rated input voltage
V
4 ? 690
4 ? 690
4 ? 690
4 ? 690
4 ? 690
Input current
Continuous line current
A
4 ? 735
4 ? 828
4 ? 906
4 ? 982
4 ? 1098
Short-time line current (60 s) max.
A
4 ? 857
4 ? 924
4 ? 984
4 ? 1167
4 ? 1283
Line fuse (provided by customer)
gL (A)
900
1000
1000 ... 1250
1250
1250 ... 1500
?line
1
1
1
1
1
Cos ?line
1
1
1
1
1
Radio interference suppression acc. to EN 61800?3
C4
C4
C4
C4
C4
Mechanical data for air-cooled cabinet units
Frame size (dimensional drawing classification)
SL10
SL10
SL10
SL12
SL12
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
79
79
79
79
79
Standard converter dimensions
Width
mm
7206
7206
7206
11406
11406
Height4)
mm
2112
2112
2112
2112
2112
Depth
mm
605
605
605
605
605
Coolant requirements
m3/h
12800
15200
15200
23150
19550
Weight, approx.
kg
3760
3970
4170
5750
5930
Mechanical data for liquid-cooled cabinet units
Frame size (dimensional drawing classification)
SW10
SW10
SW10
–5)
–5)
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
77
77
77
77
77
Standard converter dimensions
Width
mm
7806
7806
7806
–5)
–5)
Height
mm
2202
2202
2202
–5)
–5)
Depth
mm
605
605
605
–5)
–5)
Coolant requirements
l/h
8000
8000
8000
12000
12000
Min. coolant pressure
bar
2.5
2.5
2.5
2.5
2.5
Max. coolant pressure
bar
6
6
6
6
6
Coolant test pressure
bar
10
10
10
10
10
Coolant pressure loss
bar
1.9
1.9
1.9
1.9
1.9
Min. coolant temperature
°C
10
10
10
10
10
Max. coolant temperature
°C
35
30
28
35
38
Weight, approx.
kg
3860
4070
4270
5910
6090
General mechanical data
Max. cable length between converter and motor with standard insulation
(shielded)
m
100/2506)
100/2506)
100/2506)
100/2507)
100/2508)
Line/load connection
L1, L2, L3/U2, V2, W2
For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"
Approvals, according to
NRTL9)
NRTL9)
NRTL9)
NRTL9)
NRTL9)
1) Rated power of a typical 2- to 6-pole standard motor.
2) Typical output voltage dependent on filter and unit type.
3) Maximum power loss with continuous motor current.
4) With IP21 protective top cover (110 mm).
5) Dimensions on request.
6) With option L10 (strengthened dv/dt filter) the filter is integrated in additional 4 ? 600 mm cabinet.
7) Value is applicable with option L10 (strengthened dv/dt filter; filter is integrated in unit).
8) Value is applicable with option L10 (strengthened dv/dt filter; filter is integrated in additional 6 x 600 mm cabinet).
9) On request; the voltage range for NRTL units ends at max. 600 V.
Line voltage, supply system type
4 ? 400, 415, 460, 500, 575, 690 V 3 AC IT
SINAMICS G180 cabinet units – air-cooled
6SE0180?4HH45?4?A7
6SE0180?4HH46?0nA7
Converter type (air-cooled)
2T3L?87606?953
2T3L?87606?958
SINAMICS G180 cabinet units – liquid-cooled
6SE0170?4HH45?4?A7
6SE0170?4HH46?0?A7
Converter type (liquid-cooled)
2T6L?77606?953
2T6L?77606?958
Electrical data at motor end
Type rating 1)
at 50 Hz 690 V
kW
5300
5800
at 60 Hz 575 V
hp
5923
6482
Output voltage2)
V
0 ... 0.98 ? Vline
0 ... 0.98 ? Vline
Output current
Continuous current
A
5420
5940
Short-time current (60 s every 10 minutes) max.
A
6040
6450
Overload capability (60 s every 10 minutes) max.
%
11
9
Output power
kVA
6477
7099
Output frequency, max.
Hz
120
120
Rated clock cycle
kHz
2.4
2.4
adjustable from
kHz
1.5 ... 3.7
1.5 ... 3.7
Power loss 3)
kW
118
129
Rated efficiency
%
97.9
97.9
Electrical data at line end
Connected load
kVA
5916
6482
Rated input voltage
V
4 ? 690
4 ? 690
Input current
Continuous line current
A
4 ? 1237
4 ? 1357
Short-time line current (60 s) max.
A
4 ? 1378
4 ? 1474
Line fuse (provided by customer)
gL (A)
1500
1500 ... 1800
?line
1
1
Cos ?line
1
1
Radio interference suppression acc. to EN 61800?3
C4
C4
Mechanical data for air-cooled cabinet units
Frame size (dimensional drawing classification)
SL12
SL12
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
79
79
Standard converter dimensions
Width
mm
11406
11406
Height4)
mm
2112
2112
Depth
mm
605
605
Coolant requirements
m3/h
23150
23150
Weight, approx.
kg
6230
6530
Mechanical data for liquid-cooled cabinet units
Frame size (dimensional drawing classification)
–5)
–5)
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
77
77
Standard converter dimensions
Width
mm
–5)
–5)
Height
mm
–5)
–5)
Depth
mm
–5)
–5)
Coolant requirements
l/h
12000
12000
Min. coolant pressure
bar
2.5
2.5
Max. coolant pressure
bar
6
6
Coolant test pressure
bar
10
10
Coolant pressure loss
bar
1.9
1.9
Min. coolant temperature
°C
10
10
Max. coolant temperature
°C
30
28
Weight, approx.
kg
6390
6690
General mechanical data
Max. cable length between converter and motor with standard insulation
(shielded)
m
100/2506)
100/2506)
Line/load connection
L1, L2, L3/U2, V2, W2
For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"
Approvals, according to
NRTL7)
NRTL7)
1) Rated power of a typical 2- to 6-pole standard motor.
2) Typical output voltage dependent on filter and unit type.
3) Maximum power loss with continuous motor current.
4) With IP21 protective top cover (110 mm).
5) Dimensions on request.
6) Value is applicable with option L10 (strengthened dv/dt filter; filter is integrated in additional 6 x 600 mm cabinet).
7) On request; the voltage range for NRTL units ends at max. 600 V.
skener.ru
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Àðìàòóðà DENDOR
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Äàò÷èêè è èçìåðèòåëè
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ðåãóëÿòîðû è ðåãèñòðàòîðû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ïíåâìàòè÷åñêîå îáîðóäîâàíèå
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Êðàíû è Êëàïàíû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Èçìåðèòåëüíûå ïðèáîðû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ñèñòåìû áåñïðîâîäíîãî óïðàâëåíèÿ «óìíûé äîì»
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Áåñêîíòàêòíûå âûêëþ÷àòåëè Êîíå÷íûå âûêëþ÷àòåëè Îïòè÷åñêèå äàò÷èêè Ýíêîäåðû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FS - Óñòàíîâêà óìÿã÷åíèÿ
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FK - Óñòàíîâêà îáåçæåëåçèâàíèÿ