General technical data

Coolant temperature and installation altitude

Current derating

The permissible coolant temperatures and installation altitudes for SINAMICS DC MASTER Cabinet as well as the associated maximum permissible load in continuous operation can be taken from the following table (the load is specified as a % of the rated DC current).

Note:

The rated DC current of the drive cabinets corresponds to the rated DC current of the DC converters installed in them. The degree of protection and cooling type of the drive cabinets as well as the coolant temperature and installation altitude influence the max. permissible load in continuous operation. In practice, the rated current of the DC motor lies significantly below the rated DC current of the next largest converter in order to be able to fully utilize the high overload capability of the motor. The derating factors below should be taken into account for the particular application.

Example:
Rated current of the DC motor 450 A, coolant temperature 40 °C, installation altitude of the drive cabinet 2 000 m, selected rated DC current of the converter 600 A, derating factor 81 %.

Result:
The maximum permissible load of the drive cabinet in continuous operation is 486 A, and is therefore sufficient for the motor.

  

Maximum permissible load of the drive cabinets in continuous operation
(load specified as a % of the rated DC current)

  

Installation altitude above sea level
(The derating factors for intermediate values can be obtained through interpolation.)

Ambient or coolant temperature

Units

1 000 m

2 000 m

3 000 m

4 000 m

5 000 m

from 1500 A â‡’


   â‡“

⇒


   â‡“

⇒


   â‡“

⇒


   â‡“

⇒


   â‡“

from 950 A â‡’


   â‡“

⇒


   â‡“

⇒


   â‡“

⇒


   â‡“

⇒


   â‡“

from 720 A â‡’


   â‡“

⇒


   â‡“

⇒


   â‡“

⇒


   â‡“

⇒


   â‡“

from 210 A â‡’


   â‡“

⇒


   â‡“

⇒


   â‡“

⇒


   â‡“

⇒


   â‡“

up to 125 A â‡’


   â‡“

⇒
   â‡“

⇒
   â‡“

⇒
   â‡“

⇒
   â‡“

Degree of protection IP20 up to IP21

25 °C

 

100%

100%

100%

100%

100%

100%

96%

93%

97%

93%

96%

86%

83%

87%

83%

86%

76%

73%

77%

73%

78%

68%

65%

69%

65%

30 °C

 

100%

100%

100%

100%

100%

100%

91%

88%

92%

88%

90%

81%

78%

82%

78%

80%

71%

68%

72%

68%

     

35 °C

 

100%

100%

95%

99%

95%

94%

86%

83%

87%

83%

84%

76%

73%

77%

73%

          

40 °C

 

100%

95%

90%

94%

90%

88%

81%

78%

82%

78%

               

45 °C

 

94%

90%

85%

89%

85%

82%

76%

73%

77%

73%

               

50 °C

 

88%

                        

Degree of protection IP23, IP43, IP54

25 °C

 

100%

100%

100%

100%

100%

100%

98%

96%

98%

98%

96%

88%

86%

88%

88%

86%

78%

76%

78%

78%

78%

70%

68%

70%

70%

30 °C

 

100%

100%

100%

100%

100%

100%

93%

91%

93%

93%

90%

83%

81%

83%

83%

80%

73%

71%

73%

73%

     

35 °C

 

100%

100%

98%

100%

100%

94%

88%

86%

88%

88%

84%

78%

76%

78%

78%

          

40 °C

 

100%

95%

93%

95%

95%

88%

83%

81%

83%

83%

               

45 °C

 

94%

90%

88%

90%

90%

82%

78%

76%

78%

78%

               

50 °C

 

88%

                        


Voltage derating

The cabinets can be operated up to an installation altitude of 4 000 m above sea level with the specified rated supply voltages. The line supply voltages may have overvoltage category III with respect to ground. For installation altitudes above 4 000 m, in some cases, it will be necessary to reduce the supply voltage or ensure that overvoltage category II is maintained. Detailed information is provided in the Operating Instructions.

Installation location

In their basic version (IP20), SINAMICS DC MASTER Cabinet drive cabinets are intended for use in closed electrical rooms (according to EN 61800-5-1).

These rooms must be dry and dust free, in order to prevent deposits of dirt accumulating, which in conjunction with moisture, could result in a conductive connection between live parts.

In plants, frequently electrical operating rooms have central power and fresh air supplies, which fulfill these requirements. If this is not the case, then the drive cabinet must be ordered with a higher degree of protection by specifying the appropriate options (M21, M23, M43, M54 and M58).

Relevant standards

EN 50274

Low-voltage switchgear and controlgear assemblies: Protection against electric shock – protection against accidental, direct contact with dangerous live parts, option M60 provides additional touch protection in accordance with BGV A3

EN 60529

Degrees of protection provided by the enclosures (IP code)

EN 61800-3

Adjustable speed electrical power drive systems, Part 3 – EMC product standard including specific test methods

EN 61800‑5‑1

Adjustable speed electrical power drive systems – Part 5‑1: Requirements regarding safety – electrical, thermal, and energy requirements

EN 62477‑1 (product standard, combines safety-relevant standards such as IEC 61800‑5‑1, IEC 60204‑1)

Safety requirements for power semiconductor converter systems – Part 1: General information

EN 60204‑1 (VDE 0113‑1) where applicable

Safety of machinery – Electrical equipment of machines – Part 1: General requirements

The following standards are applicable for the SINAMICS DC MASTER DC Converter chassis units

EN 60146‑1‑1; EN 61800‑5‑1; IEC 62103 (identical with EN 50178). Additional information is provided in Catalog D 23.1.

Electrical data

Overvoltage category

Category ll according to EN 61800‑5‑1 within line supply circuits
Category lll according to EN 61800‑5‑1 for line supply circuits with respect to the surroundings (other line supply circuits, enclosure, electronics)

Overvoltage strength

Class 1 acc. to EN 50178

Radio interference suppression

SINAMICS DC MASTER Cabinet are operated in industrial environments and fulfill the requirements of EN 61800‑3, Categories C3 and C4. Radio interference suppression filters are required for use in Category C2 (option L00)

Auxiliary power supply

400 V 3 AC at 50 Hz, optional: 60 Hz and/or other voltages

Overload capability

x Ã— In 1.8

Mechanical data

Degree of protection

IP20 according to EN 60529; optional: IP21, IP23, IP43 and IP54

Protection class

Class 1 acc. to EN 61140

Cooling type

Increased air cooling with integrated fan 0 up to 55 °C; the derating depends on the ambient temperature and installation altitude; see the table on the current derating

Closed-loop control constancy

  • for pulse encoder operation and digital setpoint

Δn = 0.006 % of the rated motor speed

  • for analog tachometer and analog setpoint 1)

Δn = 0.1 % of the rated motor speed

Environmental compatibility

Materials free of hazardous substances have been used for all of the essential parts. Only very few materials containing halogens are used for cable insulation and cable ducts (alternative designs available on request). All of the materials correspond to the RoHS criteria, with the exception of the backup battery in the AOP30. Environmental compatibility is also a key criterion in selecting supplier parts.

Environmental conditions

Permissible ambient temperature during storage and transport

–25 ... +70 °C

Permissible humidity

Relative air humidity ≤ 95 % (75 % at 17 °C as annual average, 95 % at 24 °C max., condensation is not permissible)

Climate class

3K3 according to EN 60721‑3‑3

Insulation

Pollution degree 2 according to EN 61800‑5‑1
Condensation not permissible

Installation altitude

≤ 1 000 m above sea level (100 % load capability)
> 1 000 ... 5 000 m above sea level (see under "Coolant temperature and installation altitude")

Mechanical stability

Storage

Transport

Operation

Vibratory load

1M2 according to EN 60721‑3‑1
(toppling not permissible)

1.5 mm at 2 ... 9 Hz, 5 m/s2 at 9 ... 200 Hz
acc. to EN 60721‑3‑2
(toppling not permissible)

3M2 according to EN 60721-3-3

Shock load

1M2 according to EN 60721‑3‑1
(toppling not permissible)

40 m/s2 at 11 ms acc. to
acc. to EN 60721‑3‑2
(toppling not permissible)

3M2 according to EN 60721-3-3

Approvals

Version according to UL

A converter cabinet design according to UL can be ordered by specifying option U09. Certification must be separately carried out.

Marine version

With option M66, the cabinet is provided in a marine design for onboard applications. Certification by the appropriate authorities must be carried out separately.



1) Conditions:
The closed-loop control (PI control) constancy is referred to the rated motor speed and applies when the SINAMICS DC MASTER is in the warm operating condition. This is based on the following preconditions:

  • Temperature changes of ± 10 °C
  • Line supply voltage changes of +10 %/–5 % of the rated input voltage
  • Temperature coefficient of tachometer generator with temperature compensation: 0.15 every 10 °C (for analog tachometer generator only)
  • Constant setpoint

Notes on dimensioning the fault current and insulation monitoring:

The basic version does not include any fault current monitoring devices. However, these can be ordered as option (L82 for grounded line supplies). Insulation monitoring according to the applicable regulations must be provided for operation in non-grounded IT line supplies. Options L87 or L88 are available to realize this.

Notes on touch protection:

In the standard version of the SINAMICS DC MASTER Cabinet, in compliance with the current standards, finger and back of hand protection is ensured when the cabinet doors are open. With option M60 "Additional touch protection", the drive cabinets are equipped with additional touch protection corresponding to BGV A3.

Notes on the armature circuit busbars:

Aluminum armature busbars are used for cabinets with rated DC currents of 1 500, 1 600, 1 900, 2 000 and 2 200 A. When selecting option M11, nickel-plated copper busbars are supplied.

SINAMICS DC MASTER Cabinet for 400 V 3 AC, 60 to 210 A, two-quadrant operation
  

Type

  

6RM8025-
6DS22‑0AA0

6RM8028-
6DS22‑0AA0

6RM8031-
6DS22‑0AA0

6RM8075-
6DS22‑0AA0

Rated armature supply voltage

V

3 AC 400 (+15 %/–20 %)

Rated armature input current

A

49.8

74.7

103.75

174.3

Cooling air requirement

m³/h

800

800

800

800

Sound pressure level

dB (A)

72

72

72

72

Rated frequency

Hz

45 ... 65

45 ... 65

45 ... 65

45 ... 65

Rated DC voltage

V

485

485

485

485

Rated DC current

A

60

90

125

210

Overload capability

x Ã— In

1.8

1.8

1.8

1.8

Rated power

kW

29.1

43.65

60.625

101.85

Power loss at rated DC current

W

463

592

691

1 152

Rated DC field voltage

V

max. 325

max. 325

max. 325

max. 325

Rated DC field current

A

10

10

10

15

Max. connection cross-sections 1)

     
  • Line connection (3 phases and PE)

Number Ã— mm2

1 Ã— 16

1 Ã— 25

1 Ã— 50

1 Ã— 95

  • Armature circuit connection

Number Ã— mm2

1 Ã— 16

1 Ã— 25

1 Ã— 50

1 Ã— 95

  • Field circuit connection

Number Ã— mm2

1 Ã— 1.5

1 Ã— 1.5

1 Ã— 1.5

1 Ã— 2.5

  • Auxiliary power supply

mm2

2.5

2.5

2.5

4

Max. permissible fusing on the customer's side
(NH fuse gL/gG)

     
  • Power connections

A

63

80

125

200

    • Max. permissible short-circuit current

kA

50 2)

50 2)

50 2)

50 3)

  • Auxiliary power supply

A

16

16

16

25

    • Max. permissible short-circuit current

kA

30

30

30

30

Normal ambient temperature in operation

°C

See the table on installation altitude and ambient temperature

Dimensions

     
  • Width

mm

600

600

600

600

  • Height

mm

2 326

2 326

2 326

2 326

  • Depth

mm

600

600

600

600

Size

 

BC

BC

BC

BC

Weight, approx.

kg

233

233

240

263



1) With cable lugs according to DIN 46234 or DIN 46235; for units from 2 600 to 3 000 A, motor cables are only directly connected at the DC converter using cable lugs according to DIN 46234.

2) With option L00 (radio interference suppression filter), the maximum permissible short-circuit current is reduced to 43 kA.

3) With option L00 (radio interference suppression filter), the maximum permissible short-circuit current is reduced to 25 kA.

SINAMICS DC MASTER Cabinet for 400 V 3 AC, 280 to 850 A, two-quadrant operation
  

Type

  

6RM8078-
6DS22‑0AA0

6RM8081-
6DS22‑0AA0

6RM8085-
6DS22‑0AA0

6RM8087-
6DS22‑0AA0

Rated armature supply voltage

V

3 AC 400 (+15 %/–20 %)

Rated armature input current

A

232.4

332

498

705.5

Cooling air requirement

m³/h

800

600

600

600

Sound pressure level

dB (A)

72

74

74

74

Rated frequency

Hz

45 ... 65

45 ... 65

45 ... 65

45 ... 65

Rated DC voltage

V

485

485

485

485

Rated DC current

A

280

400

600

850

Overload capability

x Ã— In

1.8

1.8

1.8

1.8

Rated power

kW

135.8

194

291

412.25

Power loss at rated DC current

W

1 482

2 131

2 884

3 759

Rated DC field voltage

V

max. 325

max. 325

max. 325

max. 325

Rated DC field current

A

15

25

25

30

Max. connection cross-sections 1)

     
  • Line connection (3 phases and PE)

Number Ã— mm2

1 Ã— 120

1 Ã— 185

2 Ã— 150

2 Ã— 240

  • Armature circuit connection

Number Ã— mm2

2 Ã— 50

1 Ã— 185

2 Ã— 150

4 Ã— 95

  • Field circuit connection

Number Ã— mm2

1 Ã— 2.5

1 Ã— 4

1 Ã— 4

1 Ã— 4

  • Auxiliary power supply

mm2

4

10

10

16

Max. permissible fusing on the customer's side
(NH fuse gL/gG)

     
  • Power connections

A

250

355

500

710

    • Max. permissible short-circuit current

kA

50 2)

50

50

50

  • Auxiliary power supply

A

25

50

50

63

    • Max. permissible short-circuit current

kA

30

30

30

30

Normal ambient temperature in operation

°C

See the table on installation altitude and ambient temperature

Dimensions

     
  • Width

mm

600

800

800

1 200

  • Height

mm

2 326

2 200

2 200

2 200

  • Depth

mm

600

600

600

600

Size

 

BC

CC

CC

DC

Weight, approx.

kg

273

320

340

490



1) With cable lugs according to DIN 46234 or DIN 46235; for units from 2 600 to 3 000 A, motor cables are only directly connected at the DC converter using cable lugs according to DIN 46234.

2) With option L00 (radio interference suppression filter), the maximum permissible short-circuit current is reduced to 25 kA.

SINAMICS DC MASTER Cabinet for 400 V 3 AC, 1 200 to 3 000 A, two-quadrant operation
  

Type

  

6RM8091-
6DS22‑0AA0

6RM8093-
4DS22‑0AA0

6RM8095-
4DS22‑0AA0

6RM8098-
4DS22‑0AA0

Rated armature supply voltage

V

3 AC 400 (+15 %/–20 %)

Rated armature input current

A

996

1 328

1 660

2 490

Cooling air requirement

m³/h

1 000

3 000

3 000

3 000

Sound pressure level

dB (A)

76

78

78

78

Rated frequency

Hz

45 ... 65

45 ... 65

45 ... 65

45 ... 65

Rated DC voltage

V

485

485

485

485

Rated DC current

A

1 200

1 600

2 000

3 000

Overload capability

x Ã— In

1.8

1.8

1.8

1.8

Rated power

kW

582

776

970

1 455

Power loss at rated DC current

W

4 697

6 430

7 618

11 747

Rated DC field voltage

V

max. 390

max. 390

max. 390

max. 390

Rated DC field current

A

30

40

40

40

Max. connection cross-sections 1)

     
  • Line connection (3 phases and PE)

Number Ã— mm2

4 Ã— 150

6 Ã— 150

6 Ã— 185

8 Ã— 240

  • Armature circuit connection

Number Ã— mm2

4 Ã— 185

8 Ã— 95

8 Ã— 150

8 Ã— 240

  • Field circuit connection

Number Ã— mm2

1 Ã— 4

1 Ã— 6

1 Ã— 6

1 Ã— 6

  • Auxiliary power supply

mm2

16

35

35

35

Max. permissible fusing on the customer's side
(NH fuse gL/gG)

     
  • Power connections

A

 2)

 2)

 2)

 2)

    • Max. permissible short-circuit current

kA

65

75

75

75

  • Auxiliary power supply

A

63

100

100

100

    • Max. permissible short-circuit current

kA

30

50

50

50

Normal ambient temperature in operation

°C

See the table on installation altitude and ambient temperature

Dimensions

     
  • Width

mm

1 200

1 400

1 400

1 400

  • Height

mm

2 200

2 200

2 200

2 200

  • Depth

mm

600

600

600

600

Size

 

DC

EC

EC

EC

Weight, approx.

kg

570

760

800

930



1) With cable lugs according to DIN 46234 or DIN 46235; for units from 2 600 to 3 000 A, motor cables are only directly connected at the DC converter using cable lugs according to DIN 46234.

2) It must be ensured that the maximum permissible short-circuit current at the supply switch of the drive cabinet is not exceeded.

SINAMICS DC MASTER Cabinet for 480 V 3 AC, 60 to 280 A, two-quadrant operation
  

Type

  

6RM8025-
6FS22‑0AA0

6RM8028-
6FS22‑0AA0

6RM8031-
6FS22‑0AA0

6RM8075-
6FS22‑0AA0

6RM8078-
6FS22‑0AA0

Rated armature supply voltage

V

3 AC 480 (+10 %/–20 %)

Rated armature input current

A

49.8

74.7

103.75

174.3

232.4

Cooling air requirement

m³/h

800

800

800

800

800

Sound pressure level

dB (A)

72

72

72

72

72

Rated frequency

Hz

45 ... 65

45 ... 65

45 ... 65

45 ... 65

45 ... 65

Rated DC voltage

V

575

575

575

575

575

Rated DC current

A

60

90

125

210

280

Overload capability

x Ã— In

1.8

1.8

1.8

1.8

1.8

Rated power

kW

34.5

51.75

71.875

120.75

161

Power loss at rated DC current

W

512

614

713

1 225

1 481

Rated DC field voltage

V

max. 390

max. 390

max. 390

max. 390

max. 390

Rated DC field current

A

10

10

10

15

15

Max. connection cross-sections 1)

 

 

 

 

 

 

  • Line connection (3 phases and PE)

Number Ã— mm2

1 Ã— 16

1 Ã— 25

1 Ã— 50

1 Ã— 95

1 Ã— 120

  • Armature circuit connection

Number Ã— mm2

1 Ã— 16

1 Ã— 25

1 Ã— 50

1 Ã— 95

2 Ã— 50

  • Field circuit connection

Number Ã— mm2

1 Ã— 1.5

1 Ã— 1.5

1 Ã— 1.5

1 Ã— 2.5

1 Ã— 2.5

  • Auxiliary power supply

mm2

2.5

2.5

2.5

4

4

Max. permissible fusing on the customer's side
(NH fuse gL/gG)

      
  • Power connections

A

63

80

125

200

250

    • Max. permissible short-circuit current

kA

50 2)

50 2)

50 2)

50 3)

50 3)

  • Auxiliary power supply

A

16

16

16

25

25

    • Max. permissible short-circuit current

kA

30

30

30

30

30

Normal ambient temperature in operation

°C

See the table on installation altitude and ambient temperature

Dimensions

      
  • Width

mm

600

600

600

600

600

  • Height

mm

2 326

2 326

2 326

2 326

2 326

  • Depth

mm

600

600

600

600

600

Size

 

BC

BC

BC

BC

BC

Weight, approx.

kg

233

238

240

273

273



1) With cable lugs according to DIN 46234 or DIN 46235; for units from 2 600 to 3 000 A, motor cables are only directly connected at the DC converter using cable lugs according to DIN 46234.

2) With option L00 (radio interference suppression filter), the maximum permissible short-circuit current is reduced to 43 kA.

3) With option L00 (radio interference suppression filter), the maximum permissible short-circuit current is reduced to 25 kA.

SINAMICS DC MASTER Cabinet for 480 V 3 AC, 450 to 1 200 A, two-quadrant operation
  

Type

  

6RM8082-
6FS22‑0AA0

6RM8085-
6FS22‑0AA0

6RM8087-
6FS22‑0AA0

6RM8091-
6FS22‑0AA0

Rated armature supply voltage

V

3 AC 480 (+10 %/–20 %)

Rated armature input current

A

373.5

498

705.5

996

Cooling air requirement

m³/h

600

600

600

1 000

Sound pressure level

dB (A)

74

74

74

76

Rated frequency

Hz

45 ... 65

45 ... 65

45 ... 65

45 ... 65

Rated DC voltage

V

575

575

575

575

Rated DC current

A

450

600

850

1 200

Overload capability

x Ã— In

1.8

1.8

1.8

1.8

Rated power

kW

258.75

345

488.75

690

Power loss at rated DC current

W

2 377

3 097

3 983

4 857

Rated DC field voltage

V

max. 390

max. 390

max. 390

max. 390

Rated DC field current

A

25

25

30

30

Max. connection cross-sections 1)

     
  • Line connection (3 phases and PE)

Number Ã— mm2

2 Ã— 120

2 Ã— 150

2 Ã— 240

4 Ã— 150

  • Armature circuit connection

Number Ã— mm2

2 Ã— 95

2 Ã— 150

4 Ã— 95

4 Ã— 185

  • Field circuit connection

Number Ã— mm2

1 Ã— 4

1 Ã— 4

1 Ã— 4

1 Ã— 4

  • Auxiliary power supply

mm2

10

10

16

16

Max. permissible fusing on the customer's side
(NH fuse gL/gG)

     
  • Power connections

A

400

500

710

 2)

    • Max. permissible short-circuit current

kA

50

50

50

65

  • Auxiliary power supply

A

50

50

63

63

    • Max. permissible short-circuit current

kA

30

30

30

30

Normal ambient temperature in operation

°C

See the table on installation altitude and ambient temperature

Dimensions

     
  • Width

mm

800

800

1 200

1 200

  • Height

mm

2 200

2 200

2 200

2 200

  • Depth

mm

600

600

600

600

Size

 

CC

CC

DC

DC

Weight, approx.

kg

340

355

500

570



1) With cable lugs according to DIN 46234 or DIN 46235; for units from 2 600 to 3 000 A, motor cables are only directly connected at the DC converter using cable lugs according to DIN 46234.

2) It must be ensured that the maximum permissible short-circuit current at the supply switch of the drive cabinet is not exceeded.

SINAMICS DC MASTER Cabinet for 575 V 3 AC, 60 to 400 A, two-quadrant operation
  

Type

  

6RM8025-
6GS22‑0AA0

6RM8031-
6GS22‑0AA0

6RM8075-
6GS22‑0AA0

6RM8081-
6GS22‑0AA0

Rated armature supply voltage

V

3 AC 575 (+10 %/–20 %)

Rated armature input current

A

49.8

103.75

174.3

332

Cooling air requirement

m³/h

800

800

800

600

Sound pressure level

dB (A)

72

72

72

74

Rated frequency

Hz

45 ... 65

45 ... 65

45 ... 65

45 ... 65

Rated DC voltage

V

690

690

690

690

Rated DC current

A

60

125

210

400

Overload capability

x Ã— In

1.8

1.8

1.8

1.8

Rated power

kW

41.4

86.25

144.9

276

Power loss at rated DC current

W

487

762

1 284

2 439

Rated DC field voltage

V

max. 390

max. 390

max. 390

max. 390

Rated DC field current

A

10

10

15

25

Max. connection cross-sections 1)

     
  • Line connection (3 phases and PE)

Number Ã— mm2

1 Ã— 16

1 Ã— 50

1 Ã— 95

1 Ã— 185

  • Armature circuit connection

Number Ã— mm2

1 Ã— 16

1 Ã— 50

1 Ã— 95

1 Ã— 185

  • Field circuit connection

Number Ã— mm2

1 Ã— 1.5

1 Ã— 1.5

1 Ã— 2.5

1 Ã— 4

  • Auxiliary power supply

mm2

2.5

2.5

4

10

Max. permissible fusing on the customer's side
(NH fuse gL/gG)

     
  • Power connections

A

63

125

200

355

    • Max. permissible short-circuit current

kA

50 2)

50 2)

50 3)

50

  • Auxiliary power supply

A

16

16

25

50

    • Max. permissible short-circuit current

kA

30

30

30

30

Normal ambient temperature in operation

°C

See the table on installation altitude and ambient temperature

Dimensions

     
  • Width

mm

600

600

600

800

  • Height

mm

2 326

2 326

2 326

2 200

  • Depth

mm

600

600

600

600

Size

 

BC

BC

BC

CC

Weight, approx.

kg

233

240

273

335



1) With cable lugs according to DIN 46234 or DIN 46235; for units from 2 600 to 3 000 A, motor cables are only directly connected at the DC converter using cable lugs according to DIN 46234.

2) With option L00 (radio interference suppression filter), the maximum permissible short-circuit current is reduced to 43 kA.

3) With option L00 (radio interference suppression filter), the maximum permissible short-circuit current is reduced to 25 kA.

SINAMICS DC MASTER Cabinet for 575 V 3 AC, 600 to 1 600 A, two-quadrant operation
  

Type

  

6RM8085-
6GS22‑0AA0

6RM8087-
6GS22‑0AA0

6RM8090-
6GS22‑0AA0

6RM8093-
4GS22‑0AA0

Rated armature supply voltage

V

3 AC 575 (+10 %/–20 %)

Rated armature input current

A

498

664

913

1 328

Cooling air requirement

m³/h

600

600

1 000

3 000

Sound pressure level

dB (A)

74

74

76

78

Rated frequency

Hz

45 ... 65

45 ... 65

45 ... 65

45 ... 65

Rated DC voltage

V

690

690

690

690

Rated DC current

A

600

800

1 100

1 600

Overload capability

x Ã— In

1.8

1.8

1.8

1.8

Rated power

kW

414

552

759

1 104

Power loss at rated DC current

W

3 190

3 932

4 583

6 988

Rated DC field voltage

V

max. 390

max. 390

max. 390

max. 390

Rated DC field current

A

25

30

30

40

Max. connection cross-sections 1)

     
  • Line connection (3 phases and PE)

Number Ã— mm2

2 Ã— 150

2 Ã— 240

4 Ã— 150

6 Ã— 150

  • Armature circuit connection

Number Ã— mm2

2 Ã— 150

4 Ã— 95

4 Ã— 120

8 Ã— 95

  • Field circuit connection

Number Ã— mm2

1 Ã— 4

1 Ã— 4

1 Ã— 4

1 Ã— 6

  • Auxiliary power supply

mm2

10

16

16

35

Max. permissible fusing on the customer's side
(NH fuse gL/gG)

     
  • Power connections

A

500

710

 2)

 2)

    • Max. permissible short-circuit current

kA

50

50

65

75

  • Auxiliary power supply

A

50

63

63

100

    • Max. permissible short-circuit current

kA

30

30

30

50

Normal ambient temperature in operation

°C

See the table on installation altitude and ambient temperature

Dimensions

     
  • Width

mm

800

1 200

1 200

1 400

  • Height

mm

2 200

2 200

2 200

2 200

  • Depth

mm

600

600

600

600

Size

 

CC

DC

DC

EC

Weight, approx.

kg

355

515

600

775



1) With cable lugs according to DIN 46234 or DIN 46235; for units from 2 600 to 3 000 A, motor cables are only directly connected at the DC converter using cable lugs according to DIN 46234.

2) It must be ensured that the maximum permissible short-circuit current at the supply switch of the drive cabinet is not exceeded.

SINAMICS DC MASTER Cabinet for 575 V 3 AC, 2 000 to 2 800 A, two-quadrant operation
  

Type

  

6RM8095-
4GS22‑0AA0

6RM8096-
4GS22‑0AA0

6RM8097-
4GS22‑0AA0

Rated armature supply voltage

V

3 AC 575 (+10 %/–20 %)

Rated armature input current

A

1 660

1 826

2 324

Cooling air requirement

m³/h

3 000

3 000

3 000

Sound pressure level

dB (A)

78

78

78

Rated frequency

Hz

45 ... 65

45 ... 65

45 ... 65

Rated DC voltage

V

690

690

690

Rated DC current

A

2 000

2 200

2 800

Overload capability

x Ã— In

1.8

1.8

1.8

Rated power

kW

1 380

1 518

1 932

Power loss at rated DC current

W

8 090

8 408

11 937

Rated DC field voltage

V

max. 390

max. 390

max. 390

Rated DC field current

A

40

40

40

Max. connection cross-sections 1)

    
  • Line connection (3 phases and PE)

Number Ã— mm2

6 Ã— 185

8 Ã— 150

8 Ã— 240

  • Armature circuit connection

Number Ã— mm2

8 Ã— 150

8 Ã— 185

8 Ã— 240

  • Field circuit connection

Number Ã— mm2

1 Ã— 6

1 Ã— 6

1 Ã— 6

  • Auxiliary power supply

mm2

35

35

35

Max. permissible fusing on the customer's side
(NH fuse gL/gG)

    
  • Power connections

A

 2)

 2)

 2)

    • Max. permissible short-circuit current

kA

75

75

75

  • Auxiliary power supply

A

100

100

100

    • Max. permissible short-circuit current

kA

50

50

50

Normal ambient temperature in operation

°C

See the table on installation altitude and ambient temperature

Dimensions

    
  • Width

mm

1 400

1 400

1 400

  • Height

mm

2 200

2 200

2 200

  • Depth

mm

600

600

600

Size

 

EC

EC

EC

Weight, approx.

kg

830

930

1 010



1) With cable lugs according to DIN 46234 or DIN 46235; for units from 2 600 to 3 000 A, motor cables are only directly connected at the DC converter using cable lugs according to DIN 46234.

2) It must be ensured that the maximum permissible short-circuit current at the supply switch of the drive cabinet is not exceeded.

SINAMICS DC MASTER Cabinet for 690 V 3 AC, 720 to 2 600 A, two-quadrant operation
  

Type

  

6RM8086-
6KS22‑0AA0

6RM8090-
6KS22‑0AA0

6RM8093-
4KS22‑0AA0

6RM8095-
4KS22‑0AA0

6RM8097-
4KS22‑0AA0

Rated armature supply voltage

V

3 AC 690 (+10 %/–20 %)

Rated armature input current

A

597.6

830

1 245

1 660

2 158

Cooling air requirement

m³/h

600

1 000

3 000

3 000

3 000

Sound pressure level

dB (A)

74

76

78

78

78

Rated frequency

Hz

45 ... 65

45 ... 65

45 ... 65

45 ... 65

45 ... 65

Rated DC voltage

V

830

830

830

830

830

Rated DC current

A

720

1 000

1 500

2 000

2 600

Overload capability

x Ã— In

1.8

1.8

1.8

1.8

1.8

Rated power

kW

597.6

830

1 245

1 660

2 158

Power loss at rated DC current

W

4 012

4 642

7 627

9 175

12 007

Rated DC field voltage

V

max. 390

max. 390

max. 390

max. 390

max. 390

Rated DC field current

A

30

30

40

40

40

Max. connection cross-sections 1)

      
  • Line connection (3 phases and PE)

Number Ã— mm2

2 Ã— 240

4 Ã— 120

6 Ã— 120

6 Ã— 185

8 Ã— 240

  • Armature circuit connection

Number Ã— mm2

4 Ã— 95

4 Ã— 120

8 Ã— 95

8 Ã— 150

8 Ã— 240

  • Field circuit connection

Number Ã— mm2

1 Ã— 4

1 Ã— 4

1 Ã— 6

1 Ã— 6

1 Ã— 6

  • Auxiliary power supply

mm2

16

16

35

35

35

Max. permissible fusing on the customer's side
(NH fuse gL/gG)

      
  • Power connections

A

630

 2)

 2)

 2)

 2)

    • Max. permissible short-circuit current

kA

50

65

75

75

75

  • Auxiliary power supply

A

63

63

100

100

100

    • Max. permissible short-circuit current

kA

30

30

50

50

50

Normal ambient temperature in operation

°C

See the table on installation altitude and ambient temperature

Dimensions

      
  • Width

mm

1 200

1 200

1 400

1 400

1 600

  • Height

mm

2 200

2 200

2 200

2 200

2 200

  • Depth

mm

600

600

600

600

600

Size

 

DC

DC

EC

EC

FC

Weight, approx.

kg

515

600

795

830

1 050



1) With cable lugs according to DIN 46234 or DIN 46235; for units from 2 600 to 3 000 A, motor cables are only directly connected at the DC converter using cable lugs according to DIN 46234.

2) It must be ensured that the maximum permissible short-circuit current at the supply switch of the drive cabinet is not exceeded.

SINAMICS DC MASTER Cabinet for 830 V 3 AC, 950 to 1 900 A and 950 V 3 AC, 2 200 A, two-quadrant operation
  

Type

  

6RM8088-
6LS22‑0AA0

6RM8093-
4LS22‑0AA0

6RM8095-
4LS22‑0AA0

6RM8096-
4MS22‑0AA0

Rated armature supply voltage

V

3 AC 830 (+10 %/–20 %)

3 AC 950 (+15 %/–20 %)

Rated armature input current

A

788.5

1 245

1 577

1 826

Cooling air requirement

m³/h

1 000

3 000

3 000

3 000

Sound pressure level

dB (A)

76

78

78

78

Rated frequency

Hz

45 ... 65

45 ... 65

45 ... 65

45 ... 65

Rated DC voltage

V

1 000

1 000

1 000

1 140

Rated DC current

A

950

1 500

1 900

2 200

Overload capability

x Ã— In

1.8

1.8

1.8

1.8

Rated power

kW

950

1 500

1 900

2 508

Power loss at rated DC current

W

4 911

8 039

9 986

12 957

Rated DC field voltage

V

max. 390

max. 390

max. 390

max. 390

Rated DC field current

A

30

40

40

40

Max. connection cross-sections 1)

     
  • Line connection (3 phases and PE)

Number Ã— mm2

4 Ã— 120

6 Ã— 120

6 Ã— 185

8 Ã— 150

  • Armature circuit connection

Number Ã— mm2

4 Ã— 120

8 Ã— 95

8 Ã— 150

8 Ã— 185

  • Field circuit connection

Number Ã— mm2

1 Ã— 4

1 Ã— 6

1 Ã— 6

1 Ã— 6

  • Auxiliary power supply

mm2

16

35

35

35

Max. permissible fusing on the customer's side
(NH fuse gL/gG)

     
  • Power connections

A

 2)

 2)

 2)

 2)

    • Max. permissible short-circuit current

kA

50

50

50

50

  • Auxiliary power supply

A

63

100

100

100

    • Max. permissible short-circuit current

kA

30

50

50

50

Normal ambient temperature in operation

°C

See the table on installation altitude and ambient temperature

Dimensions

     
  • Width

mm

1 200

1 400

1 400

1 600

  • Height

mm

2 200

2 200

2 200

2 200

  • Depth

mm

600

600

600

600

Size

 

DC

EC

EC

FC

Weight, approx.

kg

600

825

905

1 050



1) With cable lugs according to DIN 46234 or DIN 46235; for units from 2 600 to 3 000 A, motor cables are only directly connected at the DC converter using cable lugs according to DIN 46234.

2) It must be ensured that the maximum permissible short-circuit current at the supply switch of the drive cabinet is not exceeded.

SINAMICS DC MASTER Cabinet for 400 V 3 AC, 15 to 90 A, four-quadrant operation
  

Type

  

6RM8013-
6DV62‑0AA0

6RM8018-
6DV62‑0AA0

6RM8025-
6DV62‑0AA0

6RM8028-
6DV62‑0AA0

Rated armature supply voltage

V

3 AC 400 (+15 %/–20 %)

Rated armature input current

A

12

25

50

75

Cooling air requirement

m³/h

800

800

800

800

Sound pressure level

dB (A)

72

72

72

72

Rated frequency

Hz

45 ... 65

45 ... 65

45 ... 65

45 ... 65

Rated DC voltage

V

420

420

420

420

Rated DC current

A

15

30

60

90

Overload capability

x Ã— In

1.8

1.8

1.8

1.8

Rated power

kW

6.3

12.6

25.2

37.8

Power loss at rated DC current

W

292

372

485

587

Rated DC field voltage

V

max. 325

max. 325

max. 325

max. 325

Rated DC field current

A

3

5

10

10

Max. connection cross-sections 1)

     
  • Line connection (3 phases and PE)

Number Ã— mm2

1 Ã— 2.5

1 Ã— 6

1 Ã— 16

1 Ã— 25

  • Armature circuit connection

Number Ã— mm2

1 Ã— 2.5

1 Ã— 6

1 Ã— 16

1 Ã— 25

  • Field circuit connection

Number Ã— mm2

1 Ã— 1.5

1 Ã— 1.5

1 Ã— 1.5

1 Ã— 1.5

  • Auxiliary power supply

mm2

2.5

2.5

2.5

2.5

Max. permissible fusing on the customer's side
(NH fuse gL/gG)

     
  • Power connections

A

20

32

63

80

    • Max. permissible short-circuit current

kA

50 2)

50 2)

50 2)

50 2)

  • Auxiliary power supply

A

16

16

16

16

    • Max. permissible short-circuit current

kA

30

30

30

30

Normal ambient temperature in operation

°C

See the table on installation altitude and ambient temperature

Dimensions

     
  • Width

mm

600

600

600

600

  • Height

mm

2 326

2 326

2 326

2 326

  • Depth

mm

600

600

600

600

Size

 

BC

BC

BC

BC

Weight, approx.

kg

233

213

233

233



1) With cable lugs according to DIN 46234 or DIN 46235; for units from 2 600 to 3 000 A, motor cables are only directly connected at the DC converter using cable lugs according to DIN 46234.

2) With option L00 (radio interference suppression filter), the maximum permissible short-circuit current is reduced to 43 kA.

SINAMICS DC MASTER Cabinet for 400 V 3 AC, 125 to 400 A, four-quadrant operation
  

Type

  

6RM8031-
6DV62‑0AA0

6RM8075-
6DV62‑0AA0

6RM8078-
6DV62‑0AA0

6RM8081-
6DV62‑0AA0

Rated armature supply voltage

V

3 AC 400 (+15 %/–20 %)

Rated armature input current

A

104

174

232

332

Cooling air requirement

m³/h

800

800

800

600

Sound pressure level

dB (A)

72

72

72

74

Rated frequency

Hz

45 ... 65

45 ... 65

45 ... 65

45 ... 65

Rated DC voltage

V

420

420

420

420

Rated DC current

A

125

210

280

400

Overload capability

x Ã— In

1.8

1.8

1.8

1.8

Rated power

kW

52.5

88.2

117.6

168

Power loss at rated DC current

W

726

1 202

1 557

2 226

Rated DC field voltage

V

max. 325

max. 325

max. 325

max. 325

Rated DC field current

A

10

15

15

25

Max. connection cross-sections 1)

     
  • Line connection (3 phases and PE)

Number Ã— mm2

1 Ã— 50

1 Ã— 95

1 Ã— 120

1 Ã— 185

  • Armature circuit connection

Number Ã— mm2

1 Ã— 50

1 Ã— 95

2 Ã— 50

1 Ã— 185

  • Field circuit connection

Number Ã— mm2

1 Ã— 1.5

1 Ã— 2.5

1 Ã— 2.5

1 Ã— 4

  • Auxiliary power supply

mm2

2.5

4

4

10

Max. permissible fusing on the customer's side
(NH fuse gL/gG)

     
  • Power connections

A

125

200

250

355

    • Max. permissible short-circuit current

kA

50 2)

50 3)

50 3)

50

  • Auxiliary power supply

A

16

25

25

50

    • Max. permissible short-circuit current

kA

30

30

30

30

Normal ambient temperature in operation

°C

See the table on installation altitude and ambient temperature

Dimensions

     
  • Width

mm

600

600

600

800

  • Height

mm

2 326

2 326

2 326

2 200

  • Depth

mm

600

600

600

600

Size

 

BC

BC

BC

CC

Weight, approx.

kg

240

263

273

320



1) With cable lugs according to DIN 46234 or DIN 46235; for units from 2 600 to 3 000 A, motor cables are only directly connected at the DC converter using cable lugs according to DIN 46234.

2) With option L00 (radio interference suppression filter), the maximum permissible short-circuit current is reduced to 43 kA.

3) With option L00 (radio interference suppression filter), the maximum permissible short-circuit current is reduced to 25 kA.

SINAMICS DC MASTER Cabinet for 400 V 3 AC, 600 to 1 600 A, four-quadrant operation
  

Type

  

6RM8085-
6DV62‑0AA0

6RM8087-
6DV62‑0AA0

6RM8091-
6DV62‑0AA0

6RM8093-
4DV62‑0AA0

Rated armature supply voltage

V

3 AC 400 (+15 %/–20 %)

Rated armature input current

A

498

706

996

1 328

Cooling air requirement

m³/h

600

600

1 000

3 000

Sound pressure level

dB (A)

74

74

76

78

Rated frequency

Hz

45 ... 65

45 ... 65

45 ... 65

45 ... 65

Rated DC voltage

V

420

420

420

420

Rated DC current

A

600

850

1 200

1 600

Overload capability

x Ã— In

1.8

1.8

1.8

1.8

Rated power

kW

252

357

504

672

Power loss at rated DC current

W

2 984

3 939

4 697

6 430

Rated DC field voltage

V

max. 325

max. 325

max. 390

max. 390

Rated DC field current

A

25

30

30

40

Max. connection cross-sections 1)

     
  • Line connection (3 phases and PE)

Number Ã— mm2

2 Ã— 150

2 Ã— 240

4 Ã— 150

6 Ã— 150

  • Armature circuit connection

Number Ã— mm2

2 Ã— 150

4 Ã— 95

4 Ã— 185

8 Ã— 95

  • Field circuit connection

Number Ã— mm2

1 Ã— 4

1 Ã— 4

1 Ã— 4

1 Ã— 6

  • Auxiliary power supply

mm2

10

16

16

35

Max. permissible fusing on the customer's side
(NH fuse gL/gG)

     
  • Power connections

A

500

710

 2)

 2)

    • Max. permissible short-circuit current

kA

50

50

65

75

  • Auxiliary power supply

A

50

63

63

100

    • Max. permissible short-circuit current

kA

30

30

30

50

Normal ambient temperature in operation

°C

See the table on installation altitude and ambient temperature

Dimensions

     
  • Width

mm

800

1 200

1 200

1 400

  • Height

mm

2 200

2 200

2 200

2 200

  • Depth

mm

600

600

600

600

Size

 

CC

DC

DC

EC

Weight, approx.

kg

340

490

570

780



1) With cable lugs according to DIN 46234 or DIN 46235; for units from 2 600 to 3 000 A, motor cables are only directly connected at the DC converter using cable lugs according to DIN 46234.

2) It must be ensured that the maximum permissible short-circuit current at the supply switch of the drive cabinet is not exceeded.

SINAMICS DC MASTER Cabinet for 400 V 3 AC, 2 000 to 3 000 A, four-quadrant operation
  

Type

  

6RM8095-
4DV62‑0AA0

6RM8098-
4DV62‑0AA0

Rated armature supply voltage

V

3 AC 400 (+15 %/–20 %)

Rated armature input current

A

1 660

2 490

Cooling air requirement

m³/h

3 000

3 000

Sound pressure level

dB (A)

78

78

Rated frequency

Hz

45 ... 65

45 ... 65

Rated DC voltage

V

420

420

Rated DC current

A

2 000

3 000

Overload capability

x Ã— In

1.8

1.8

Rated power

kW

840

1 260

Power loss at rated DC current

W

7 618

11 747

Rated DC field voltage

V

max. 390

max. 390

Rated DC field current

A

40

40

Max. connection cross-sections 1)

   
  • Line connection (3 phases and PE)

Number Ã— mm2

6 Ã— 185

8 Ã— 240

  • Armature circuit connection

Number Ã— mm2

8 Ã— 150

8 Ã— 240

  • Field circuit connection

Number Ã— mm2

1 Ã— 6

1 Ã— 6

  • Auxiliary power supply

mm2

35

35

Max. permissible fusing on the customer's side
(NH fuse gL/gG)

   
  • Power connections

A

 2)

 2)

    • Max. permissible short-circuit current

kA

75

75

  • Auxiliary power supply

A

100

100

    • Max. permissible short-circuit current

kA

50

50

Normal ambient temperature in operation

°C

See the table on installation altitude and ambient temperature

Dimensions

   
  • Width

mm

1 400

1 400

  • Height

mm

2 200

2 200

  • Depth

mm

600

600

Size

 

EC

EC

Weight, approx.

kg

820

950



1) With cable lugs according to DIN 46234 or DIN 46235; for units from 2 600 to 3 000 A, motor cables are only directly connected at the DC converter using cable lugs according to DIN 46234.

2) It must be ensured that the maximum permissible short-circuit current at the supply switch of the drive cabinet is not exceeded.

SINAMICS DC MASTER Cabinet for 480 V 3 AC, 15 to 90 A, four-quadrant operation
  

Type

  

6RM8013-
6FV62‑0AA0

6RM8018-
6FV62‑0AA0

6RM8025-
6FV62‑0AA0

6RM8028-
6FV62‑0AA0

Rated armature supply voltage

V

3 AC 480 (+10 %/–20 %)

Rated armature input current

A

12

25

50

75

Cooling air requirement

m³/h

800

800

800

800

Sound pressure level

dB (A)

72

72

72

72

Rated frequency

Hz

45 ... 65

45 ... 65

45 ... 65

45 ... 65

Rated DC voltage

V

500

500

500

500

Rated DC current

A

15

30

60

90

Overload capability

x Ã— In

1.8

1.8

1.8

1.8

Rated power

kW

6.3

15

30

45

Power loss at rated DC current

W

292

377

534

609

Rated DC field voltage

V

max. 390

max. 390

max. 390

max. 390

Rated DC field current

A

3

5

10

10

Max. connection cross-sections 1)

     
  • Line connection (3 phases and PE)

Number Ã— mm2

1 Ã— 2.5

1 Ã— 6

1 Ã— 16

1 Ã— 25

  • Armature circuit connection

Number Ã— mm2

1 Ã— 2.5

1 Ã— 6

1 Ã— 16

1 Ã— 25

  • Field circuit connection

Number Ã— mm2

1 Ã— 1.5

1 Ã— 1.5

1 Ã— 1.5

1 Ã— 1.5

  • Auxiliary power supply

mm2

2.5

2.5

2.5

2.5

Max. permissible fusing on the customer's side
(NH fuse gL/gG)

     
  • Power connections

A

20

32

63

80

    • Max. permissible short-circuit current

kA

50 2)

50 2)

50 2)

50 2)

  • Auxiliary power supply

A

16

16

16

16

    • Max. permissible short-circuit current

kA

30

30

30

30

Normal ambient temperature in operation

°C

See the table on installation altitude and ambient temperature

Dimensions

     
  • Width

mm

600

600

600

600

  • Height

mm

2 326

2 326

2 326

2 326

  • Depth

mm

600

600

600

600

Size

 

BC

BC

BC

BC

Weight, approx.

kg

210

215

233

238



1) With cable lugs according to DIN 46234 or DIN 46235; for units from 2 600 to 3 000 A, motor cables are only directly connected at the DC converter using cable lugs according to DIN 46234.

2) With option L00 (radio interference suppression filter), the maximum permissible short-circuit current is reduced to 43 kA.

SINAMICS DC MASTER Cabinet for 480 V 3 AC, 125 to 450 A, four-quadrant operation
  

Type

  

6RM8031-
6FV62‑0AA0

6RM8075-
6FV62‑0AA0

6RM8078-
6FV62‑0AA0

6RM8082-
6FV62‑0AA0

Rated armature supply voltage

V

3 AC 480 (+10 %/–20 %)

Rated armature input current

A

104

174

232

374

Cooling air requirement

m³/h

800

800

800

600

Sound pressure level

dB (A)

72

72

72

74

Rated frequency

Hz

45 ... 65

45 ... 65

45 ... 65

45 ... 65

Rated DC voltage

V

500

500

500

500

Rated DC current

A

125

210

280

450

Overload capability

x Ã— In

1.8

1.8

1.8

1.8

Rated power

kW

62.5

105

140

225

Power loss at rated DC current

W

748

1 275

1 556

2 467

Rated DC field voltage

V

max. 390

max. 390

max. 390

max. 390

Rated DC field current

A

10

15

15

25

Max. connection cross-sections 1)

     
  • Line connection (3 phases and PE)

Number Ã— mm2

1 Ã— 50

1 Ã— 95

1 Ã— 120

2 Ã— 120

  • Armature circuit connection

Number Ã— mm2

1 Ã— 50

1 Ã— 95

2 Ã— 50

2 Ã— 95

  • Field circuit connection

Number Ã— mm2

1 Ã— 1.5

1 Ã— 2.5

1 Ã— 2.5

1 Ã— 4

  • Auxiliary power supply

mm2

2.5

4

4

10

Max. permissible fusing on the customer's side
(NH fuse gL/gG)

     
  • Power connections

A

125

200

250

400

    • Max. permissible short-circuit current

kA

50 2)

50 3)

50 3)

50

  • Auxiliary power supply

A

16

25

25

50

    • Max. permissible short-circuit current

kA

30

30

30

30

Normal ambient temperature in operation

°C

See the table on installation altitude and ambient temperature

Dimensions

     
  • Width

mm

600

600

600

800

  • Height

mm

2 326

2 326

2 326

2 200

  • Depth

mm

600

600

600

600

Size

 

BC

BC

BC

CC

Weight, approx.

kg

240

273

273

340



1) With cable lugs according to DIN 46234 or DIN 46235; for units from 2 600 to 3 000 A, motor cables are only directly connected at the DC converter using cable lugs according to DIN 46234.

2) With option L00 (radio interference suppression filter), the maximum permissible short-circuit current is reduced to 43 kA.

3) With option L00 (radio interference suppression filter), the maximum permissible short-circuit current is reduced to 25 kA.

SINAMICS DC MASTER Cabinet for 480 V 3 AC, 600 to 1 200 A, four-quadrant operation
  

Type

  

6RM8085-
6FV62‑0AA0

6RM8087-
6FV62‑0AA0

6RM8091-
6FV62‑0AA0

Rated armature supply voltage

V

3 AC 480 (+10 %/–20 %)

Rated armature input current

A

498

706

996

Cooling air requirement

m³/h

600

600

1 000

Sound pressure level

dB (A)

74

74

76

Rated frequency

Hz

45 ... 65

45 ... 65

45 ... 65

Rated DC voltage

V

500

500

500

Rated DC current

A

600

850

1 200

Overload capability

x Ã— In

1.8

1.8

1.8

Rated power

kW

300

425

600

Power loss at rated DC current

W

3 197

4 303

4 857

Rated DC field voltage

V

max. 390

max. 390

max. 390

Rated DC field current

A

25

30

30

Max. connection cross-sections 1)

    
  • Line connection (3 phases and PE)

Number Ã— mm2

2 Ã— 150

2 Ã— 240

4 Ã— 150

  • Armature circuit connection

Number Ã— mm2

2 Ã— 150

4 Ã— 95

4 Ã— 185

  • Field circuit connection

Number Ã— mm2

1 Ã— 4

1 Ã— 4

1 Ã— 4

  • Auxiliary power supply

mm2

10

16

16

Max. permissible fusing on the customer's side
(NH fuse gL/gG)

    
  • Power connections

A

500

710

 2)

    • Max. permissible short-circuit current

kA

50

50

65

  • Auxiliary power supply

A

50

63

63

    • Max. permissible short-circuit current

kA

30

30

30

Normal ambient temperature in operation

°C

See the table on installation altitude and ambient temperature

Dimensions

    
  • Width

mm

800

1 200

1 200

  • Height

mm

2 200

2 200

2 200

  • Depth

mm

600

600

600

Size

 

CC

DC

DC

Weight, approx.

kg

355

500

570



1) With cable lugs according to DIN 46234 or DIN 46235; for units from 2 600 to 3 000 A, motor cables are only directly connected at the DC converter using cable lugs according to DIN 46234.

2) It must be ensured that the maximum permissible short-circuit current at the supply switch of the drive cabinet is not exceeded.

SINAMICS DC MASTER Cabinet for 575 V 3 AC, 60 to 400 A, four-quadrant operation
  

Type

  

6RM8025-
6GV62‑0AA0

6RM8031-
6GV62‑0AA0

6RM8075-
6GV62‑0AA0

6RM8081-
6GV62‑0AA0

Rated armature supply voltage

V

3 AC 575 (+10 %/–20 %)

Rated armature input current

A

50

104

174

332

Cooling air requirement

m³/h

800

800

800

600

Sound pressure level

dB (A)

72

72

72

74

Rated frequency

Hz

45 ... 65

45 ... 65

45 ... 65

45 ... 65

Rated DC voltage

V

600

600

600

600

Rated DC current

A

60

125

210

400

Overload capability

x Ã— In

1.8

1.8

1.8

1.8

Rated power

kW

36

75

126

240

Power loss at rated DC current

W

509

797

1 320

2 534

Rated DC field voltage

V

max. 390

max. 390

max. 390

max. 390

Rated DC field current

A

10

10

15

25

Max. connection cross-sections 1)

     
  • Line connection (3 phases and PE)

Number Ã— mm2

1 Ã— 16

1 Ã— 50

1 Ã— 95

1 Ã— 185

  • Armature circuit connection

Number Ã— mm2

1 Ã— 16

1 Ã— 50

1 Ã— 95

1 Ã— 185

  • Field circuit connection

Number Ã— mm2

1 Ã— 1.5

1 Ã— 2.5

1 Ã— 2.5

1 Ã— 4

  • Auxiliary power supply

mm2

2.5

2.5

4

10

Max. permissible fusing on the customer's side
(NH fuse gL/gG)

     
  • Power connections

A

63

125

200

355

    • Max. permissible short-circuit current

kA

50 2)

50 2)

50 3)

50

  • Auxiliary power supply

A

16

16

25

50

    • Max. permissible short-circuit current

kA

30

30

30

30

Normal ambient temperature in operation

°C

See the table on installation altitude and ambient temperature

Dimensions

     
  • Width

mm

600

600

600

800

  • Height

mm

2 326

2 326

2 326

2 200

  • Depth

mm

600

600

600

600

Size

 

BC

BC

BC

CC

Weight, approx.

kg

233

240

273

335



1) With cable lugs according to DIN 46234 or DIN 46235; for units from 2 600 to 3 000 A, motor cables are only directly connected at the DC converter using cable lugs according to DIN 46234.

2) With option L00 (radio interference suppression filter), the maximum permissible short-circuit current is reduced to 43 kA.

3) With option L00 (radio interference suppression filter), the maximum permissible short-circuit current is reduced to 25 kA.

SINAMICS DC MASTER Cabinet for 575 V 3 AC, 600 to 1 600 A, four-quadrant operation
  

Type

  

6RM8085-
6GV62‑0AA0

6RM8087-
6GV62‑0AA0

6RM8090-
6GV62‑0AA0

6RM8093-
4GV62‑0AA0

Rated armature supply voltage

V

3 AC 575 (+10 %/–20 %)

Rated armature input current

A

498

706

913

1 328

Cooling air requirement

m³/h

600

600

1 000

3 000

Sound pressure level

dB (A)

74

74

76

78

Rated frequency

Hz

45 ... 65

45 ... 65

45 ... 65

45 ... 65

Rated DC voltage

V

600

600

600

600

Rated DC current

A

600

850

1 100

1 600

Overload capability

x Ã— In

1.8

1.8

1.8

1.8

Rated power

kW

360

510

660

960

Power loss at rated DC current

W

3 290

4 112

4 583

6 988

Rated DC field voltage

V

max. 390

max. 390

max. 390

max. 390

Rated DC field current

A

25

30

30

40

Max. connection cross-sections 1)

 

 

 

 

 

  • Line connection (3 phases and PE)

Number Ã— mm2

2 Ã— 150

2 Ã— 240

4 Ã— 150

6 Ã— 150

  • Armature circuit connection

Number Ã— mm2

2 Ã— 150

4 Ã— 95

4 Ã— 120

8 Ã— 95

  • Field circuit connection

Number Ã— mm2

1 Ã— 4

1 Ã— 4

1 Ã— 4

1 Ã— 6

  • Auxiliary power supply

mm2

10

16

16

35

Max. permissible fusing on the customer's side
(NH fuse gL/gG)

     
  • Power connections

A

500

710

 2)

 2)

    • Max. permissible short-circuit current

kA

50

50

65

75

  • Auxiliary power supply

A

50

63

63

100

    • Max. permissible short-circuit current

kA

30

30

30

50

Normal ambient temperature in operation

°C

See the table on installation altitude and ambient temperature

Dimensions

     
  • Width

mm

800

1 200

1 200

1 400

  • Height

mm

2 200

2 200

2 200

2 200

  • Depth

mm

600

600

600

600

Size

 

CC

DC

DC

EC

Weight, approx.

kg

355

515

600

795



1) With cable lugs according to DIN 46234 or DIN 46235; for units from 2 600 to 3 000 A, motor cables are only directly connected at the DC converter using cable lugs according to DIN 46234.

2) It must be ensured that the maximum permissible short-circuit current at the supply switch of the drive cabinet is not exceeded.

SINAMICS DC MASTER Cabinet for 575 V 3 AC, 2 000 to 2 800 A, four-quadrant operation
  

Type

  

6RM8095-
4GV62‑0AA0

6RM8096-
4GV62‑0AA0

6RM8097-
4GV62‑0AA0

Rated armature supply voltage

V

3 AC 575 (+10 %/–20 %)

Rated armature input current

A

1 660

1 826

2 324

Cooling air requirement

m³/h

3 000

3 000

3 000

Sound pressure level

dB (A)

78

78

78

Rated frequency

Hz

45 ... 65

45 ... 65

45 ... 65

Rated DC voltage

V

600

600

600

Rated DC current

A

2 000

2 200

2 800

Overload capability

x Ã— In

1.8

1.8

1.8

Rated power

kW

1 200

1 320

1 680

Power loss at rated DC current

W

8 090

8 408

11 937

Rated DC field voltage

V

max. 390

max. 390

max. 390

Rated DC field current

A

40

40

40

Max. connection cross-sections 1)

    
  • Line connection (3 phases and PE)

Number Ã— mm2

6 Ã— 185

8 Ã— 150

8 Ã— 240

  • Armature circuit connection

Number Ã— mm2

8 Ã— 150

8 Ã— 185

8 Ã— 240

  • Field circuit connection

Number Ã— mm2

1 Ã— 6

1 Ã— 6

1 Ã— 6

  • Auxiliary power supply

mm2

35

35

35

Max. permissible fusing on the customer's side
(NH fuse gL/gG)

    
  • Power connections

A

 2)

 2)

 2)

    • Max. permissible short-circuit current

kA

75

75

75

  • Auxiliary power supply

A

100

100

100

    • Max. permissible short-circuit current

kA

50

50

50

Normal ambient temperature in operation

°C

See the table on installation altitude and ambient temperature

Dimensions

    
  • Width

mm

1 400

1 400

1 400

  • Height

mm

2 200

2 200

2 200

  • Depth

mm

600

600

600

Size

 

EC

EC

EC

Weight, approx.

kg

850

950

1 030



1) With cable lugs according to DIN 46234 or DIN 46235; for units from 2 600 to 3 000 A, motor cables are only directly connected at the DC converter using cable lugs according to DIN 46234.

2) It must be ensured that the maximum permissible short-circuit current at the supply switch of the drive cabinet is not exceeded.

SINAMICS DC MASTER Cabinet for 690 V 3 AC, 760 to 2 600 A, four-quadrant operation
  

Type

  

6RM8086-
6KV62‑0AA0

6RM8090-
6KV62‑0AA0

6RM8093-
4KV62‑0AA0

6RM8095-
4KV62‑0AA0

6RM8097-
4KV62‑0AA0

Rated armature supply voltage

V

3 AC 690 (+10 %/–20 %)

Rated armature input current

A

631

830

1 245

1 660

2 158

Cooling air requirement

m³/h

600

1 000

3 000

3 000

3 000

Sound pressure level

dB (A)

74

76

78

78

78

Rated frequency

Hz

45 ... 65

45 ... 65

45 ... 65

45 ... 65

45 ... 65

Rated DC voltage

V

725

725

725

725

725

Rated DC current

A

760

1 000

1 500

2 000

2 600

Overload capability

x Ã— In

1.8

1.8

1.8

1.8

1.8

Rated power

kW

551

725

1 087.5

1 450

1 885

Power loss at rated DC current

W

4 352

4 642

7 627

9 175

12 007

Rated DC field voltage

V

max. 390

max. 390

max. 390

max. 390

max. 390

Rated DC field current

A

30

30

40

40

40

Max. connection cross-sections 1)

      
  • Line connection (3 phases and PE)

Number Ã— mm2

2 Ã— 240

4 Ã— 120

6 Ã— 120

6 Ã— 185

8 Ã— 240

  • Armature circuit connection

Number Ã— mm2

4 Ã— 95

4 Ã— 120

8 Ã— 95

8 Ã— 150

8 Ã— 240

  • Field circuit connection

Number Ã— mm2

1 Ã— 4

1 Ã— 4

1 Ã— 6

1 Ã— 6

1 Ã— 6

  • Auxiliary power supply

mm2

16

16

35

35

35

Max. permissible fusing on the customer's side
(NH fuse gL/gG)

      
  • Power connections

A

630

 2)

 2)

 2)

 2)

    • Max. permissible short-circuit current

kA

50

65

75

75

75

  • Auxiliary power supply

A

63

63

100

100

100

    • Max. permissible short-circuit current

kA

30

30

50

50

50

Normal ambient temperature in operation

°C

See the table on installation altitude and ambient temperature

Dimensions

      
  • Width

mm

1 200

1 200

1 400

1 400

1 600

  • Height

mm

2 200

2 200

2 200

2 200

2 200

  • Depth

mm

600

600

600

600

600

Size

 

DC

DC

EC

EC

FC

Weight, approx.

kg

515

600

815

850

1 070



1) With cable lugs according to DIN 46234 or DIN 46235; for units from 2 600 to 3 000 A, motor cables are only directly connected at the DC converter using cable lugs according to DIN 46234.

2) It must be ensured that the maximum permissible short-circuit current at the supply switch of the drive cabinet is not exceeded.

SINAMICS DC MASTER Cabinet for 830 V 3 AC, 950 to 1 900 A and 950 V 3 AC, 2 200 V, four-quadrant operation
  

Type

  

6RM8088-
6LV62‑0AA0

6RM8093-
4LV62‑0AA0

6RM8095-
4LV62‑0AA0

6RM8096-
4MV62‑0AA0

Rated armature supply voltage

V

3 AC 830 (+10 %/–20 %)

3 AC 950 (+15%/–20%)

Rated armature input current

A

789

1 245

1 577

1 826

Cooling air requirement

m³/h

1 000

3 000

3 000

3 000

Sound pressure level

dB (A)

76

78

78

78

Rated frequency

Hz

45 ... 65

45 ... 65

45 ... 65

45 ... 65

Rated DC voltage

V

875

875

875

1 000

Rated DC current

A

950

1 500

1 900

2 200

Overload capability

x Ã— In

1.8

1.8

1.8

1.8

Rated power

kW

831.25

1 312.5

1 662.5

2 200

Power loss at rated DC current

W

4 911

8 039

9 986

12 957

Rated DC field voltage

V

max. 390

max. 390

max. 390

max. 390

Rated DC field current

A

30

40

40

40

Max. connection cross-sections 1)

     
  • Line connection (3 phases and PE)

Number Ã— mm2

4 Ã— 120

6 Ã— 120

6 Ã— 185

8 Ã— 150

  • Armature circuit connection

Number Ã— mm2

4 Ã— 150

8 Ã— 95

8 Ã— 150

8 Ã— 185

  • Field circuit connection

Number Ã— mm2

1 Ã— 4

1 Ã— 6

1 Ã— 6

1 Ã— 6

  • Auxiliary power supply

mm2

16

35

35

35

Max. permissible fusing on the customer's side
(NH fuse gL/gG)

     
  • Power connections

A

 2)

 2)

 2)

 2)

    • Max. permissible short-circuit current

kA

50

50

50

50

  • Auxiliary power supply

A

63

100

100

100

    • Max. permissible short-circuit current

kA

30

50

50

50

Normal ambient temperature in operation

°C

See the table on installation altitude and ambient temperature

Dimensions

     
  • Width

mm

1 200

1 400

1 400

1 600

  • Height

mm

2 200

2 200

2 200

2 200

  • Depth

mm

600

600

600

600

Size

 

DC

EC

EC

FC

Weight, approx.

kg

600

845

925

1 070



1) With cable lugs according to DIN 46234 or DIN 46235; for units from 2 600 to 3 000 A, motor cables are only directly connected at the DC converter using cable lugs according to DIN 46234.

2) It must be ensured that the maximum permissible short-circuit current at the supply switch of the drive cabinet is not exceeded.

















skener.ru

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Àðìàòóðà DENDOR

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Äàò÷èêè è èçìåðèòåëè

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ðåãóëÿòîðû è ðåãèñòðàòîðû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ïíåâìàòè÷åñêîå îáîðóäîâàíèå

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Êðàíû è Êëàïàíû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Èçìåðèòåëüíûå ïðèáîðû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ñèñòåìû áåñïðîâîäíîãî óïðàâëåíèÿ «óìíûé äîì»

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Áåñêîíòàêòíûå âûêëþ÷àòåëè Êîíå÷íûå âûêëþ÷àòåëè Îïòè÷åñêèå äàò÷èêè Ýíêîäåðû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FS - Óñòàíîâêà óìÿã÷åíèÿ

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FK - Óñòàíîâêà îáåçæåëåçèâàíèÿ

  © ÎÎÎ "ÑÊ ÝÍÅÐÃÎ" 2007-2022
  (4872) 700-366  skenergo@mail.ru
ßíäåêñ.Ìåòðèêà