General technical data
Coolant temperature and installation altitude
Current derating
The permissible coolant temperatures and installation altitudes for SINAMICS DC MASTER Cabinet as well as the associated maximum permissible load in continuous operation can be taken from the following table (the load is specified as a % of the rated DC current).
Note:
The rated DC current of the drive cabinets corresponds to the rated DC current of the DC converters installed in them. The degree of protection and cooling type of the drive cabinets as well as the coolant temperature and installation altitude influence the max. permissible load in continuous operation. In practice, the rated current of the DC motor lies significantly below the rated DC current of the next largest converter in order to be able to fully utilize the high overload capability of the motor. The derating factors below should be taken into account for the particular application.
Example: Rated current of the DC motor 450 A, coolant temperature 40 °C, installation altitude of the drive cabinet 2 000 m, selected rated DC current of the converter 600 A, derating factor 81 %.
Result: The maximum permissible load of the drive cabinet in continuous operation is 486 A, and is therefore sufficient for the motor.
|
|
Maximum permissible load of the drive cabinets in continuous operation (load specified as a % of the rated DC current)
|
|
|
Installation altitude above sea level (The derating factors for intermediate values can be obtained through interpolation.)
|
Ambient or coolant temperature
|
Units
|
1 000 m
|
2 000 m
|
3 000 m
|
4 000 m
|
5 000 m
|
from 1500 A ?
|
?
|
?
|
?
|
?
|
?
|
?
|
?
|
?
|
?
|
from 950 A ?
|
?
|
?
|
?
|
?
|
?
|
?
|
?
|
?
|
?
|
from 720 A ?
|
?
|
?
|
?
|
?
|
?
|
?
|
?
|
?
|
?
|
from 210 A ?
|
?
|
?
|
?
|
?
|
?
|
?
|
?
|
?
|
?
|
up to 125 A ?
|
?
|
? ?
|
? ?
|
? ?
|
? ?
|
Degree of protection IP20 up to IP21
|
25 °C
|
|
100%
|
100%
|
100%
|
100%
|
100%
|
100%
|
96%
|
93%
|
97%
|
93%
|
96%
|
86%
|
83%
|
87%
|
83%
|
86%
|
76%
|
73%
|
77%
|
73%
|
78%
|
68%
|
65%
|
69%
|
65%
|
30 °C
|
|
100%
|
100%
|
100%
|
100%
|
100%
|
100%
|
91%
|
88%
|
92%
|
88%
|
90%
|
81%
|
78%
|
82%
|
78%
|
80%
|
71%
|
68%
|
72%
|
68%
|
|
|
|
|
|
35 °C
|
|
100%
|
100%
|
95%
|
99%
|
95%
|
94%
|
86%
|
83%
|
87%
|
83%
|
84%
|
76%
|
73%
|
77%
|
73%
|
|
|
|
|
|
|
|
|
|
|
40 °C
|
|
100%
|
95%
|
90%
|
94%
|
90%
|
88%
|
81%
|
78%
|
82%
|
78%
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
45 °C
|
|
94%
|
90%
|
85%
|
89%
|
85%
|
82%
|
76%
|
73%
|
77%
|
73%
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
50 °C
|
|
88%
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Degree of protection IP23, IP43, IP54
|
25 °C
|
|
100%
|
100%
|
100%
|
100%
|
100%
|
100%
|
98%
|
96%
|
98%
|
98%
|
96%
|
88%
|
86%
|
88%
|
88%
|
86%
|
78%
|
76%
|
78%
|
78%
|
78%
|
70%
|
68%
|
70%
|
70%
|
30 °C
|
|
100%
|
100%
|
100%
|
100%
|
100%
|
100%
|
93%
|
91%
|
93%
|
93%
|
90%
|
83%
|
81%
|
83%
|
83%
|
80%
|
73%
|
71%
|
73%
|
73%
|
|
|
|
|
|
35 °C
|
|
100%
|
100%
|
98%
|
100%
|
100%
|
94%
|
88%
|
86%
|
88%
|
88%
|
84%
|
78%
|
76%
|
78%
|
78%
|
|
|
|
|
|
|
|
|
|
|
40 °C
|
|
100%
|
95%
|
93%
|
95%
|
95%
|
88%
|
83%
|
81%
|
83%
|
83%
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
45 °C
|
|
94%
|
90%
|
88%
|
90%
|
90%
|
82%
|
78%
|
76%
|
78%
|
78%
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
50 °C
|
|
88%
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Voltage derating
The cabinets can be operated up to an installation altitude of 4 000 m above sea level with the specified rated supply voltages. The line supply voltages may have overvoltage category III with respect to ground. For installation altitudes above 4 000 m, in some cases, it will be necessary to reduce the supply voltage or ensure that overvoltage category II is maintained. Detailed information is provided in the Operating Instructions.
Installation location
In their basic version (IP20), SINAMICS DC MASTER Cabinet drive cabinets are intended for use in closed electrical rooms (according to EN 61800-5-1).
These rooms must be dry and dust free, in order to prevent deposits of dirt accumulating, which in conjunction with moisture, could result in a conductive connection between live parts.
In plants, frequently electrical operating rooms have central power and fresh air supplies, which fulfill these requirements. If this is not the case, then the drive cabinet must be ordered with a higher degree of protection by specifying the appropriate options (M21, M23, M43, M54 and M58).
Relevant standards
|
EN 50274
|
Low-voltage switchgear and controlgear assemblies: Protection against electric shock – protection against accidental, direct contact with dangerous live parts, option M60 provides additional touch protection in accordance with BGV A3
|
EN 60529
|
Degrees of protection provided by the enclosures (IP code)
|
EN 61800-3
|
Adjustable speed electrical power drive systems, Part 3 – EMC product standard including specific test methods
|
EN 61800?5?1
|
Adjustable speed electrical power drive systems – Part 5?1: Requirements regarding safety – electrical, thermal, and energy requirements
|
EN 62477?1 (product standard, combines safety-relevant standards such as IEC 61800?5?1, IEC 60204?1)
|
Safety requirements for power semiconductor converter systems – Part 1: General information
|
EN 60204?1 (VDE 0113?1) where applicable
|
Safety of machinery – Electrical equipment of machines – Part 1: General requirements
|
The following standards are applicable for the SINAMICS DC MASTER DC Converter chassis units
|
EN 60146?1?1; EN 61800?5?1; IEC 62103 (identical with EN 50178). Additional information is provided in Catalog D 23.1.
|
Electrical data
|
Overvoltage category
|
Category ll according to EN 61800?5?1 within line supply circuits Category lll according to EN 61800?5?1 for line supply circuits with respect to the surroundings (other line supply circuits, enclosure, electronics)
|
Overvoltage strength
|
Class 1 acc. to EN 50178
|
Radio interference suppression
|
SINAMICS DC MASTER Cabinet are operated in industrial environments and fulfill the requirements of EN 61800?3, Categories C3 and C4. Radio interference suppression filters are required for use in Category C2 (option L00)
|
Auxiliary power supply
|
400 V 3 AC at 50 Hz, optional: 60 Hz and/or other voltages
|
Overload capability
|
x ? In 1.8
|
Mechanical data
|
Degree of protection
|
IP20 according to EN 60529; optional: IP21, IP23, IP43 and IP54
|
Protection class
|
Class 1 acc. to EN 61140
|
Cooling type
|
Increased air cooling with integrated fan 0 up to 55 °C; the derating depends on the ambient temperature and installation altitude; see the table on the current derating
|
Closed-loop control constancy
|
- for pulse encoder operation and digital setpoint
|
?
n = 0.006 % of the rated motor speed
|
- for analog tachometer and analog setpoint 1)
|
?
n = 0.1 % of the rated motor speed
|
Environmental compatibility
|
Materials free of hazardous substances have been used for all of the essential parts. Only very few materials containing halogens are used for cable insulation and cable ducts (alternative designs available on request). All of the materials correspond to the RoHS criteria, with the exception of the backup battery in the AOP30. Environmental compatibility is also a key criterion in selecting supplier parts.
|
Environmental conditions
|
Permissible ambient temperature during storage and transport
|
–25 ... +70 °C
|
Permissible humidity
|
Relative air humidity ? 95 % (75 % at 17 °C as annual average, 95 % at 24 °C max., condensation is not permissible)
|
Climate class
|
3K3 according to EN 60721?3?3
|
Insulation
|
Pollution degree 2 according to EN 61800?5?1 Condensation not permissible
|
Installation altitude
|
? 1 000 m above sea level (100 % load capability) > 1 000 ... 5 000 m above sea level (see under "Coolant temperature and installation altitude")
|
Mechanical stability
|
Storage
|
Transport
|
Operation
|
Vibratory load
|
1M2 according to EN 60721?3?1 (toppling not permissible)
|
1.5 mm at 2 ... 9 Hz, 5 m/s2 at 9 ... 200 Hz acc. to EN 60721?3?2 (toppling not permissible)
|
3M2 according to EN 60721-3-3
|
Shock load
|
1M2 according to EN 60721?3?1 (toppling not permissible)
|
40 m/s2 at 11 ms acc. to acc. to EN 60721?3?2 (toppling not permissible)
|
3M2 according to EN 60721-3-3
|
Approvals
|
Version according to UL
|
A converter cabinet design according to UL can be ordered by specifying option U09. Certification must be separately carried out.
|
Marine version
|
With option M66, the cabinet is provided in a marine design for onboard applications. Certification by the appropriate authorities must be carried out separately.
|
1) Conditions: The closed-loop control (PI control) constancy is referred to the rated motor speed and applies when the SINAMICS DC MASTER is in the warm operating condition. This is based on the following preconditions:
- Temperature changes of ± 10 °C
- Line supply voltage changes of +10 %/–5 % of the rated input voltage
- Temperature coefficient of tachometer generator with temperature compensation: 0.15 every 10 °C (for analog tachometer generator only)
- Constant setpoint
Notes on dimensioning the fault current and insulation monitoring:
The basic version does not include any fault current monitoring devices. However, these can be ordered as option (L82 for grounded line supplies). Insulation monitoring according to the applicable regulations must be provided for operation in non-grounded IT line supplies. Options L87 or L88 are available to realize this.
Notes on touch protection:
In the standard version of the SINAMICS DC MASTER Cabinet, in compliance with the current standards, finger and back of hand protection is ensured when the cabinet doors are open. With option M60 "Additional touch protection", the drive cabinets are equipped with additional touch protection corresponding to BGV A3.
Notes on the armature circuit busbars:
Aluminum armature busbars are used for cabinets with rated DC currents of 1 500, 1 600, 1 900, 2 000 and 2 200 A. When selecting option M11, nickel-plated copper busbars are supplied.
SINAMICS DC MASTER Cabinet for 400 V 3 AC, 60 to 210 A, two-quadrant operation
|
|
Type
|
|
|
6RM8025- 6DS22?0AA0
|
6RM8028- 6DS22?0AA0
|
6RM8031- 6DS22?0AA0
|
6RM8075- 6DS22?0AA0
|
Rated armature supply voltage
|
V
|
3 AC 400 (+15 %/–20 %)
|
Rated armature input current
|
A
|
49.8
|
74.7
|
103.75
|
174.3
|
Cooling air requirement
|
m?/h
|
800
|
800
|
800
|
800
|
Sound pressure level
|
dB (A)
|
72
|
72
|
72
|
72
|
Rated frequency
|
Hz
|
45 ... 65
|
45 ... 65
|
45 ... 65
|
45 ... 65
|
Rated DC voltage
|
V
|
485
|
485
|
485
|
485
|
Rated DC current
|
A
|
60
|
90
|
125
|
210
|
Overload capability
|
x ? In
|
1.8
|
1.8
|
1.8
|
1.8
|
Rated power
|
kW
|
29.1
|
43.65
|
60.625
|
101.85
|
Power loss at rated DC current
|
W
|
463
|
592
|
691
|
1 152
|
Rated DC field voltage
|
V
|
max. 325
|
max. 325
|
max. 325
|
max. 325
|
Rated DC field current
|
A
|
10
|
10
|
10
|
15
|
Max. connection cross-sections 1)
|
|
|
|
|
|
- Line connection (3 phases and PE)
|
Number ? mm2
|
1 ? 16
|
1 ? 25
|
1 ? 50
|
1 ? 95
|
- Armature circuit connection
|
Number ? mm2
|
1 ? 16
|
1 ? 25
|
1 ? 50
|
1 ? 95
|
|
Number ? mm2
|
1 ? 1.5
|
1 ? 1.5
|
1 ? 1.5
|
1 ? 2.5
|
|
mm2
|
2.5
|
2.5
|
2.5
|
4
|
Max. permissible fusing on the customer's side (NH fuse gL/gG)
|
|
|
|
|
|
|
A
|
63
|
80
|
125
|
200
|
- Max. permissible short-circuit current
|
kA
|
50 2)
|
50 2)
|
50 2)
|
50 3)
|
|
A
|
16
|
16
|
16
|
25
|
- Max. permissible short-circuit current
|
kA
|
30
|
30
|
30
|
30
|
Normal ambient temperature in operation
|
°C
|
See the table on installation altitude and ambient temperature
|
Dimensions
|
|
|
|
|
|
|
mm
|
600
|
600
|
600
|
600
|
|
mm
|
2 326
|
2 326
|
2 326
|
2 326
|
|
mm
|
600
|
600
|
600
|
600
|
Size
|
|
BC
|
BC
|
BC
|
BC
|
Weight, approx.
|
kg
|
233
|
233
|
240
|
263
|
1) With cable lugs according to DIN 46234 or DIN 46235; for units from 2 600 to 3 000 A, motor cables are only directly connected at the DC converter using cable lugs according to DIN 46234.
2) With option L00 (radio interference suppression filter), the maximum permissible short-circuit current is reduced to 43 kA.
3) With option L00 (radio interference suppression filter), the maximum permissible short-circuit current is reduced to 25 kA.
SINAMICS DC MASTER Cabinet for 400 V 3 AC, 280 to 850 A, two-quadrant operation
|
|
Type
|
|
|
6RM8078- 6DS22?0AA0
|
6RM8081- 6DS22?0AA0
|
6RM8085- 6DS22?0AA0
|
6RM8087- 6DS22?0AA0
|
Rated armature supply voltage
|
V
|
3 AC 400 (+15 %/–20 %)
|
Rated armature input current
|
A
|
232.4
|
332
|
498
|
705.5
|
Cooling air requirement
|
m?/h
|
800
|
600
|
600
|
600
|
Sound pressure level
|
dB (A)
|
72
|
74
|
74
|
74
|
Rated frequency
|
Hz
|
45 ... 65
|
45 ... 65
|
45 ... 65
|
45 ... 65
|
Rated DC voltage
|
V
|
485
|
485
|
485
|
485
|
Rated DC current
|
A
|
280
|
400
|
600
|
850
|
Overload capability
|
x ? In
|
1.8
|
1.8
|
1.8
|
1.8
|
Rated power
|
kW
|
135.8
|
194
|
291
|
412.25
|
Power loss at rated DC current
|
W
|
1 482
|
2 131
|
2 884
|
3 759
|
Rated DC field voltage
|
V
|
max. 325
|
max. 325
|
max. 325
|
max. 325
|
Rated DC field current
|
A
|
15
|
25
|
25
|
30
|
Max. connection cross-sections 1)
|
|
|
|
|
|
- Line connection (3 phases and PE)
|
Number ? mm2
|
1 ? 120
|
1 ? 185
|
2 ? 150
|
2 ? 240
|
- Armature circuit connection
|
Number ? mm2
|
2 ? 50
|
1 ? 185
|
2 ? 150
|
4 ? 95
|
|
Number ? mm2
|
1 ? 2.5
|
1 ? 4
|
1 ? 4
|
1 ? 4
|
|
mm2
|
4
|
10
|
10
|
16
|
Max. permissible fusing on the customer's side (NH fuse gL/gG)
|
|
|
|
|
|
|
A
|
250
|
355
|
500
|
710
|
- Max. permissible short-circuit current
|
kA
|
50 2)
|
50
|
50
|
50
|
|
A
|
25
|
50
|
50
|
63
|
- Max. permissible short-circuit current
|
kA
|
30
|
30
|
30
|
30
|
Normal ambient temperature in operation
|
°C
|
See the table on installation altitude and ambient temperature
|
Dimensions
|
|
|
|
|
|
|
mm
|
600
|
800
|
800
|
1 200
|
|
mm
|
2 326
|
2 200
|
2 200
|
2 200
|
|
mm
|
600
|
600
|
600
|
600
|
Size
|
|
BC
|
CC
|
CC
|
DC
|
Weight, approx.
|
kg
|
273
|
320
|
340
|
490
|
1) With cable lugs according to DIN 46234 or DIN 46235; for units from 2 600 to 3 000 A, motor cables are only directly connected at the DC converter using cable lugs according to DIN 46234.
2) With option L00 (radio interference suppression filter), the maximum permissible short-circuit current is reduced to 25 kA.
SINAMICS DC MASTER Cabinet for 400 V 3 AC, 1 200 to 3 000 A, two-quadrant operation
|
|
Type
|
|
|
6RM8091- 6DS22?0AA0
|
6RM8093- 4DS22?0AA0
|
6RM8095- 4DS22?0AA0
|
6RM8098- 4DS22?0AA0
|
Rated armature supply voltage
|
V
|
3 AC 400 (+15 %/–20 %)
|
Rated armature input current
|
A
|
996
|
1 328
|
1 660
|
2 490
|
Cooling air requirement
|
m?/h
|
1 000
|
3 000
|
3 000
|
3 000
|
Sound pressure level
|
dB (A)
|
76
|
78
|
78
|
78
|
Rated frequency
|
Hz
|
45 ... 65
|
45 ... 65
|
45 ... 65
|
45 ... 65
|
Rated DC voltage
|
V
|
485
|
485
|
485
|
485
|
Rated DC current
|
A
|
1 200
|
1 600
|
2 000
|
3 000
|
Overload capability
|
x ? In
|
1.8
|
1.8
|
1.8
|
1.8
|
Rated power
|
kW
|
582
|
776
|
970
|
1 455
|
Power loss at rated DC current
|
W
|
4 697
|
6 430
|
7 618
|
11 747
|
Rated DC field voltage
|
V
|
max. 390
|
max. 390
|
max. 390
|
max. 390
|
Rated DC field current
|
A
|
30
|
40
|
40
|
40
|
Max. connection cross-sections 1)
|
|
|
|
|
|
- Line connection (3 phases and PE)
|
Number ? mm2
|
4 ? 150
|
6 ? 150
|
6 ? 185
|
8 ? 240
|
- Armature circuit connection
|
Number ? mm2
|
4 ? 185
|
8 ? 95
|
8 ? 150
|
8 ? 240
|
|
Number ? mm2
|
1 ? 4
|
1 ? 6
|
1 ? 6
|
1 ? 6
|
|
mm2
|
16
|
35
|
35
|
35
|
Max. permissible fusing on the customer's side (NH fuse gL/gG)
|
|
|
|
|
|
|
A
|
– 2)
|
– 2)
|
– 2)
|
– 2)
|
- Max. permissible short-circuit current
|
kA
|
65
|
75
|
75
|
75
|
|
A
|
63
|
100
|
100
|
100
|
- Max. permissible short-circuit current
|
kA
|
30
|
50
|
50
|
50
|
Normal ambient temperature in operation
|
°C
|
See the table on installation altitude and ambient temperature
|
Dimensions
|
|
|
|
|
|
|
mm
|
1 200
|
1 400
|
1 400
|
1 400
|
|
mm
|
2 200
|
2 200
|
2 200
|
2 200
|
|
mm
|
600
|
600
|
600
|
600
|
Size
|
|
DC
|
EC
|
EC
|
EC
|
Weight, approx.
|
kg
|
570
|
760
|
800
|
930
|
1) With cable lugs according to DIN 46234 or DIN 46235; for units from 2 600 to 3 000 A, motor cables are only directly connected at the DC converter using cable lugs according to DIN 46234.
2) It must be ensured that the maximum permissible short-circuit current at the supply switch of the drive cabinet is not exceeded.
SINAMICS DC MASTER Cabinet for 480 V 3 AC, 60 to 280 A, two-quadrant operation
|
|
Type
|
|
|
6RM8025- 6FS22?0AA0
|
6RM8028- 6FS22?0AA0
|
6RM8031- 6FS22?0AA0
|
6RM8075- 6FS22?0AA0
|
6RM8078- 6FS22?0AA0
|
Rated armature supply voltage
|
V
|
3 AC 480 (+10 %/–20 %)
|
Rated armature input current
|
A
|
49.8
|
74.7
|
103.75
|
174.3
|
232.4
|
Cooling air requirement
|
m?/h
|
800
|
800
|
800
|
800
|
800
|
Sound pressure level
|
dB (A)
|
72
|
72
|
72
|
72
|
72
|
Rated frequency
|
Hz
|
45 ... 65
|
45 ... 65
|
45 ... 65
|
45 ... 65
|
45 ... 65
|
Rated DC voltage
|
V
|
575
|
575
|
575
|
575
|
575
|
Rated DC current
|
A
|
60
|
90
|
125
|
210
|
280
|
Overload capability
|
x ? In
|
1.8
|
1.8
|
1.8
|
1.8
|
1.8
|
Rated power
|
kW
|
34.5
|
51.75
|
71.875
|
120.75
|
161
|
Power loss at rated DC current
|
W
|
512
|
614
|
713
|
1 225
|
1 481
|
Rated DC field voltage
|
V
|
max. 390
|
max. 390
|
max. 390
|
max. 390
|
max. 390
|
Rated DC field current
|
A
|
10
|
10
|
10
|
15
|
15
|
Max. connection cross-sections 1)
|
|
|
|
|
|
|
- Line connection (3 phases and PE)
|
Number ? mm2
|
1 ? 16
|
1 ? 25
|
1 ? 50
|
1 ? 95
|
1 ? 120
|
- Armature circuit connection
|
Number ? mm2
|
1 ? 16
|
1 ? 25
|
1 ? 50
|
1 ? 95
|
2 ? 50
|
|
Number ? mm2
|
1 ? 1.5
|
1 ? 1.5
|
1 ? 1.5
|
1 ? 2.5
|
1 ? 2.5
|
|
mm2
|
2.5
|
2.5
|
2.5
|
4
|
4
|
Max. permissible fusing on the customer's side (NH fuse gL/gG)
|
|
|
|
|
|
|
|
A
|
63
|
80
|
125
|
200
|
250
|
- Max. permissible short-circuit current
|
kA
|
50 2)
|
50 2)
|
50 2)
|
50 3)
|
50 3)
|
|
A
|
16
|
16
|
16
|
25
|
25
|
- Max. permissible short-circuit current
|
kA
|
30
|
30
|
30
|
30
|
30
|
Normal ambient temperature in operation
|
°C
|
See the table on installation altitude and ambient temperature
|
Dimensions
|
|
|
|
|
|
|
|
mm
|
600
|
600
|
600
|
600
|
600
|
|
mm
|
2 326
|
2 326
|
2 326
|
2 326
|
2 326
|
|
mm
|
600
|
600
|
600
|
600
|
600
|
Size
|
|
BC
|
BC
|
BC
|
BC
|
BC
|
Weight, approx.
|
kg
|
233
|
238
|
240
|
273
|
273
|
1) With cable lugs according to DIN 46234 or DIN 46235; for units from 2 600 to 3 000 A, motor cables are only directly connected at the DC converter using cable lugs according to DIN 46234.
2) With option L00 (radio interference suppression filter), the maximum permissible short-circuit current is reduced to 43 kA.
3) With option L00 (radio interference suppression filter), the maximum permissible short-circuit current is reduced to 25 kA.
SINAMICS DC MASTER Cabinet for 480 V 3 AC, 450 to 1 200 A, two-quadrant operation
|
|
Type
|
|
|
6RM8082- 6FS22?0AA0
|
6RM8085- 6FS22?0AA0
|
6RM8087- 6FS22?0AA0
|
6RM8091- 6FS22?0AA0
|
Rated armature supply voltage
|
V
|
3 AC 480 (+10 %/–20 %)
|
Rated armature input current
|
A
|
373.5
|
498
|
705.5
|
996
|
Cooling air requirement
|
m?/h
|
600
|
600
|
600
|
1 000
|
Sound pressure level
|
dB (A)
|
74
|
74
|
74
|
76
|
Rated frequency
|
Hz
|
45 ... 65
|
45 ... 65
|
45 ... 65
|
45 ... 65
|
Rated DC voltage
|
V
|
575
|
575
|
575
|
575
|
Rated DC current
|
A
|
450
|
600
|
850
|
1 200
|
Overload capability
|
x ? In
|
1.8
|
1.8
|
1.8
|
1.8
|
Rated power
|
kW
|
258.75
|
345
|
488.75
|
690
|
Power loss at rated DC current
|
W
|
2 377
|
3 097
|
3 983
|
4 857
|
Rated DC field voltage
|
V
|
max. 390
|
max. 390
|
max. 390
|
max. 390
|
Rated DC field current
|
A
|
25
|
25
|
30
|
30
|
Max. connection cross-sections 1)
|
|
|
|
|
|
- Line connection (3 phases and PE)
|
Number ? mm2
|
2 ? 120
|
2 ? 150
|
2 ? 240
|
4 ? 150
|
- Armature circuit connection
|
Number ? mm2
|
2 ? 95
|
2 ? 150
|
4 ? 95
|
4 ? 185
|
|
Number ? mm2
|
1 ? 4
|
1 ? 4
|
1 ? 4
|
1 ? 4
|
|
mm2
|
10
|
10
|
16
|
16
|
Max. permissible fusing on the customer's side (NH fuse gL/gG)
|
|
|
|
|
|
|
A
|
400
|
500
|
710
|
– 2)
|
- Max. permissible short-circuit current
|
kA
|
50
|
50
|
50
|
65
|
|
A
|
50
|
50
|
63
|
63
|
- Max. permissible short-circuit current
|
kA
|
30
|
30
|
30
|
30
|
Normal ambient temperature in operation
|
°C
|
See the table on installation altitude and ambient temperature
|
Dimensions
|
|
|
|
|
|
|
mm
|
800
|
800
|
1 200
|
1 200
|
|
mm
|
2 200
|
2 200
|
2 200
|
2 200
|
|
mm
|
600
|
600
|
600
|
600
|
Size
|
|
CC
|
CC
|
DC
|
DC
|
Weight, approx.
|
kg
|
340
|
355
|
500
|
570
|
1) With cable lugs according to DIN 46234 or DIN 46235; for units from 2 600 to 3 000 A, motor cables are only directly connected at the DC converter using cable lugs according to DIN 46234.
2) It must be ensured that the maximum permissible short-circuit current at the supply switch of the drive cabinet is not exceeded.
SINAMICS DC MASTER Cabinet for 575 V 3 AC, 60 to 400 A, two-quadrant operation
|
|
Type
|
|
|
6RM8025- 6GS22?0AA0
|
6RM8031- 6GS22?0AA0
|
6RM8075- 6GS22?0AA0
|
6RM8081- 6GS22?0AA0
|
Rated armature supply voltage
|
V
|
3 AC 575 (+10 %/–20 %)
|
Rated armature input current
|
A
|
49.8
|
103.75
|
174.3
|
332
|
Cooling air requirement
|
m?/h
|
800
|
800
|
800
|
600
|
Sound pressure level
|
dB (A)
|
72
|
72
|
72
|
74
|
Rated frequency
|
Hz
|
45 ... 65
|
45 ... 65
|
45 ... 65
|
45 ... 65
|
Rated DC voltage
|
V
|
690
|
690
|
690
|
690
|
Rated DC current
|
A
|
60
|
125
|
210
|
400
|
Overload capability
|
x ? In
|
1.8
|
1.8
|
1.8
|
1.8
|
Rated power
|
kW
|
41.4
|
86.25
|
144.9
|
276
|
Power loss at rated DC current
|
W
|
487
|
762
|
1 284
|
2 439
|
Rated DC field voltage
|
V
|
max. 390
|
max. 390
|
max. 390
|
max. 390
|
Rated DC field current
|
A
|
10
|
10
|
15
|
25
|
Max. connection cross-sections 1)
|
|
|
|
|
|
- Line connection (3 phases and PE)
|
Number ? mm2
|
1 ? 16
|
1 ? 50
|
1 ? 95
|
1 ? 185
|
- Armature circuit connection
|
Number ? mm2
|
1 ? 16
|
1 ? 50
|
1 ? 95
|
1 ? 185
|
|
Number ? mm2
|
1 ? 1.5
|
1 ? 1.5
|
1 ? 2.5
|
1 ? 4
|
|
mm2
|
2.5
|
2.5
|
4
|
10
|
Max. permissible fusing on the customer's side (NH fuse gL/gG)
|
|
|
|
|
|
|
A
|
63
|
125
|
200
|
355
|
- Max. permissible short-circuit current
|
kA
|
50 2)
|
50 2)
|
50 3)
|
50
|
|
A
|
16
|
16
|
25
|
50
|
- Max. permissible short-circuit current
|
kA
|
30
|
30
|
30
|
30
|
Normal ambient temperature in operation
|
°C
|
See the table on installation altitude and ambient temperature
|
Dimensions
|
|
|
|
|
|
|
mm
|
600
|
600
|
600
|
800
|
|
mm
|
2 326
|
2 326
|
2 326
|
2 200
|
|
mm
|
600
|
600
|
600
|
600
|
Size
|
|
BC
|
BC
|
BC
|
CC
|
Weight, approx.
|
kg
|
233
|
240
|
273
|
335
|
1) With cable lugs according to DIN 46234 or DIN 46235; for units from 2 600 to 3 000 A, motor cables are only directly connected at the DC converter using cable lugs according to DIN 46234.
2) With option L00 (radio interference suppression filter), the maximum permissible short-circuit current is reduced to 43 kA.
3) With option L00 (radio interference suppression filter), the maximum permissible short-circuit current is reduced to 25 kA.
SINAMICS DC MASTER Cabinet for 575 V 3 AC, 600 to 1 600 A, two-quadrant operation
|
|
Type
|
|
|
6RM8085- 6GS22?0AA0
|
6RM8087- 6GS22?0AA0
|
6RM8090- 6GS22?0AA0
|
6RM8093- 4GS22?0AA0
|
Rated armature supply voltage
|
V
|
3 AC 575 (+10 %/–20 %)
|
Rated armature input current
|
A
|
498
|
664
|
913
|
1 328
|
Cooling air requirement
|
m?/h
|
600
|
600
|
1 000
|
3 000
|
Sound pressure level
|
dB (A)
|
74
|
74
|
76
|
78
|
Rated frequency
|
Hz
|
45 ... 65
|
45 ... 65
|
45 ... 65
|
45 ... 65
|
Rated DC voltage
|
V
|
690
|
690
|
690
|
690
|
Rated DC current
|
A
|
600
|
800
|
1 100
|
1 600
|
Overload capability
|
x ? In
|
1.8
|
1.8
|
1.8
|
1.8
|
Rated power
|
kW
|
414
|
552
|
759
|
1 104
|
Power loss at rated DC current
|
W
|
3 190
|
3 932
|
4 583
|
6 988
|
Rated DC field voltage
|
V
|
max. 390
|
max. 390
|
max. 390
|
max. 390
|
Rated DC field current
|
A
|
25
|
30
|
30
|
40
|
Max. connection cross-sections 1)
|
|
|
|
|
|
- Line connection (3 phases and PE)
|
Number ? mm2
|
2 ? 150
|
2 ? 240
|
4 ? 150
|
6 ? 150
|
- Armature circuit connection
|
Number ? mm2
|
2 ? 150
|
4 ? 95
|
4 ? 120
|
8 ? 95
|
|
Number ? mm2
|
1 ? 4
|
1 ? 4
|
1 ? 4
|
1 ? 6
|
|
mm2
|
10
|
16
|
16
|
35
|
Max. permissible fusing on the customer's side (NH fuse gL/gG)
|
|
|
|
|
|
|
A
|
500
|
710
|
– 2)
|
– 2)
|
- Max. permissible short-circuit current
|
kA
|
50
|
50
|
65
|
75
|
|
A
|
50
|
63
|
63
|
100
|
- Max. permissible short-circuit current
|
kA
|
30
|
30
|
30
|
50
|
Normal ambient temperature in operation
|
°C
|
See the table on installation altitude and ambient temperature
|
Dimensions
|
|
|
|
|
|
|
mm
|
800
|
1 200
|
1 200
|
1 400
|
|
mm
|
2 200
|
2 200
|
2 200
|
2 200
|
|
mm
|
600
|
600
|
600
|
600
|
Size
|
|
CC
|
DC
|
DC
|
EC
|
Weight, approx.
|
kg
|
355
|
515
|
600
|
775
|
1) With cable lugs according to DIN 46234 or DIN 46235; for units from 2 600 to 3 000 A, motor cables are only directly connected at the DC converter using cable lugs according to DIN 46234.
2) It must be ensured that the maximum permissible short-circuit current at the supply switch of the drive cabinet is not exceeded.
SINAMICS DC MASTER Cabinet for 575 V 3 AC, 2 000 to 2 800 A, two-quadrant operation
|
|
Type
|
|
|
6RM8095- 4GS22?0AA0
|
6RM8096- 4GS22?0AA0
|
6RM8097- 4GS22?0AA0
|
Rated armature supply voltage
|
V
|
3 AC 575 (+10 %/–20 %)
|
Rated armature input current
|
A
|
1 660
|
1 826
|
2 324
|
Cooling air requirement
|
m?/h
|
3 000
|
3 000
|
3 000
|
Sound pressure level
|
dB (A)
|
78
|
78
|
78
|
Rated frequency
|
Hz
|
45 ... 65
|
45 ... 65
|
45 ... 65
|
Rated DC voltage
|
V
|
690
|
690
|
690
|
Rated DC current
|
A
|
2 000
|
2 200
|
2 800
|
Overload capability
|
x ? In
|
1.8
|
1.8
|
1.8
|
Rated power
|
kW
|
1 380
|
1 518
|
1 932
|
Power loss at rated DC current
|
W
|
8 090
|
8 408
|
11 937
|
Rated DC field voltage
|
V
|
max. 390
|
max. 390
|
max. 390
|
Rated DC field current
|
A
|
40
|
40
|
40
|
Max. connection cross-sections 1)
|
|
|
|
|
- Line connection (3 phases and PE)
|
Number ? mm2
|
6 ? 185
|
8 ? 150
|
8 ? 240
|
- Armature circuit connection
|
Number ? mm2
|
8 ? 150
|
8 ? 185
|
8 ? 240
|
|
Number ? mm2
|
1 ? 6
|
1 ? 6
|
1 ? 6
|
|
mm2
|
35
|
35
|
35
|
Max. permissible fusing on the customer's side (NH fuse gL/gG)
|
|
|
|
|
|
A
|
– 2)
|
– 2)
|
– 2)
|
- Max. permissible short-circuit current
|
kA
|
75
|
75
|
75
|
|
A
|
100
|
100
|
100
|
- Max. permissible short-circuit current
|
kA
|
50
|
50
|
50
|
Normal ambient temperature in operation
|
°C
|
See the table on installation altitude and ambient temperature
|
Dimensions
|
|
|
|
|
|
mm
|
1 400
|
1 400
|
1 400
|
|
mm
|
2 200
|
2 200
|
2 200
|
|
mm
|
600
|
600
|
600
|
Size
|
|
EC
|
EC
|
EC
|
Weight, approx.
|
kg
|
830
|
930
|
1 010
|
1) With cable lugs according to DIN 46234 or DIN 46235; for units from 2 600 to 3 000 A, motor cables are only directly connected at the DC converter using cable lugs according to DIN 46234.
2) It must be ensured that the maximum permissible short-circuit current at the supply switch of the drive cabinet is not exceeded.
SINAMICS DC MASTER Cabinet for 690 V 3 AC, 720 to 2 600 A, two-quadrant operation
|
|
Type
|
|
|
6RM8086- 6KS22?0AA0
|
6RM8090- 6KS22?0AA0
|
6RM8093- 4KS22?0AA0
|
6RM8095- 4KS22?0AA0
|
6RM8097- 4KS22?0AA0
|
Rated armature supply voltage
|
V
|
3 AC 690 (+10 %/–20 %)
|
Rated armature input current
|
A
|
597.6
|
830
|
1 245
|
1 660
|
2 158
|
Cooling air requirement
|
m?/h
|
600
|
1 000
|
3 000
|
3 000
|
3 000
|
Sound pressure level
|
dB (A)
|
74
|
76
|
78
|
78
|
78
|
Rated frequency
|
Hz
|
45 ... 65
|
45 ... 65
|
45 ... 65
|
45 ... 65
|
45 ... 65
|
Rated DC voltage
|
V
|
830
|
830
|
830
|
830
|
830
|
Rated DC current
|
A
|
720
|
1 000
|
1 500
|
2 000
|
2 600
|
Overload capability
|
x ? In
|
1.8
|
1.8
|
1.8
|
1.8
|
1.8
|
Rated power
|
kW
|
597.6
|
830
|
1 245
|
1 660
|
2 158
|
Power loss at rated DC current
|
W
|
4 012
|
4 642
|
7 627
|
9 175
|
12 007
|
Rated DC field voltage
|
V
|
max. 390
|
max. 390
|
max. 390
|
max. 390
|
max. 390
|
Rated DC field current
|
A
|
30
|
30
|
40
|
40
|
40
|
Max. connection cross-sections 1)
|
|
|
|
|
|
|
- Line connection (3 phases and PE)
|
Number ? mm2
|
2 ? 240
|
4 ? 120
|
6 ? 120
|
6 ? 185
|
8 ? 240
|
- Armature circuit connection
|
Number ? mm2
|
4 ? 95
|
4 ? 120
|
8 ? 95
|
8 ? 150
|
8 ? 240
|
|
Number ? mm2
|
1 ? 4
|
1 ? 4
|
1 ? 6
|
1 ? 6
|
1 ? 6
|
|
mm2
|
16
|
16
|
35
|
35
|
35
|
Max. permissible fusing on the customer's side (NH fuse gL/gG)
|
|
|
|
|
|
|
|
A
|
630
|
– 2)
|
– 2)
|
– 2)
|
– 2)
|
- Max. permissible short-circuit current
|
kA
|
50
|
65
|
75
|
75
|
75
|
|
A
|
63
|
63
|
100
|
100
|
100
|
- Max. permissible short-circuit current
|
kA
|
30
|
30
|
50
|
50
|
50
|
Normal ambient temperature in operation
|
°C
|
See the table on installation altitude and ambient temperature
|
Dimensions
|
|
|
|
|
|
|
|
mm
|
1 200
|
1 200
|
1 400
|
1 400
|
1 600
|
|
mm
|
2 200
|
2 200
|
2 200
|
2 200
|
2 200
|
|
mm
|
600
|
600
|
600
|
600
|
600
|
Size
|
|
DC
|
DC
|
EC
|
EC
|
FC
|
Weight, approx.
|
kg
|
515
|
600
|
795
|
830
|
1 050
|
1) With cable lugs according to DIN 46234 or DIN 46235; for units from 2 600 to 3 000 A, motor cables are only directly connected at the DC converter using cable lugs according to DIN 46234.
2) It must be ensured that the maximum permissible short-circuit current at the supply switch of the drive cabinet is not exceeded.
SINAMICS DC MASTER Cabinet for 830 V 3 AC, 950 to 1 900 A and 950 V 3 AC, 2 200 A, two-quadrant operation
|
|
Type
|
|
|
6RM8088- 6LS22?0AA0
|
6RM8093- 4LS22?0AA0
|
6RM8095- 4LS22?0AA0
|
6RM8096- 4MS22?0AA0
|
Rated armature supply voltage
|
V
|
3 AC 830 (+10 %/–20 %)
|
3 AC 950 (+15 %/–20 %)
|
Rated armature input current
|
A
|
788.5
|
1 245
|
1 577
|
1 826
|
Cooling air requirement
|
m?/h
|
1 000
|
3 000
|
3 000
|
3 000
|
Sound pressure level
|
dB (A)
|
76
|
78
|
78
|
78
|
Rated frequency
|
Hz
|
45 ... 65
|
45 ... 65
|
45 ... 65
|
45 ... 65
|
Rated DC voltage
|
V
|
1 000
|
1 000
|
1 000
|
1 140
|
Rated DC current
|
A
|
950
|
1 500
|
1 900
|
2 200
|
Overload capability
|
x ? In
|
1.8
|
1.8
|
1.8
|
1.8
|
Rated power
|
kW
|
950
|
1 500
|
1 900
|
2 508
|
Power loss at rated DC current
|
W
|
4 911
|
8 039
|
9 986
|
12 957
|
Rated DC field voltage
|
V
|
max. 390
|
max. 390
|
max. 390
|
max. 390
|
Rated DC field current
|
A
|
30
|
40
|
40
|
40
|
Max. connection cross-sections 1)
|
|
|
|
|
|
- Line connection (3 phases and PE)
|
Number ? mm2
|
4 ? 120
|
6 ? 120
|
6 ? 185
|
8 ? 150
|
- Armature circuit connection
|
Number ? mm2
|
4 ? 120
|
8 ? 95
|
8 ? 150
|
8 ? 185
|
|
Number ? mm2
|
1 ? 4
|
1 ? 6
|
1 ? 6
|
1 ? 6
|
|
mm2
|
16
|
35
|
35
|
35
|
Max. permissible fusing on the customer's side (NH fuse gL/gG)
|
|
|
|
|
|
|
A
|
– 2)
|
– 2)
|
– 2)
|
– 2)
|
- Max. permissible short-circuit current
|
kA
|
50
|
50
|
50
|
50
|
|
A
|
63
|
100
|
100
|
100
|
- Max. permissible short-circuit current
|
kA
|
30
|
50
|
50
|
50
|
Normal ambient temperature in operation
|
°C
|
See the table on installation altitude and ambient temperature
|
Dimensions
|
|
|
|
|
|
|
mm
|
1 200
|
1 400
|
1 400
|
1 600
|
|
mm
|
2 200
|
2 200
|
2 200
|
2 200
|
|
mm
|
600
|
600
|
600
|
600
|
Size
|
|
DC
|
EC
|
EC
|
FC
|
Weight, approx.
|
kg
|
600
|
825
|
905
|
1 050
|
1) With cable lugs according to DIN 46234 or DIN 46235; for units from 2 600 to 3 000 A, motor cables are only directly connected at the DC converter using cable lugs according to DIN 46234.
2) It must be ensured that the maximum permissible short-circuit current at the supply switch of the drive cabinet is not exceeded.
SINAMICS DC MASTER Cabinet for 400 V 3 AC, 15 to 90 A, four-quadrant operation
|
|
Type
|
|
|
6RM8013- 6DV62?0AA0
|
6RM8018- 6DV62?0AA0
|
6RM8025- 6DV62?0AA0
|
6RM8028- 6DV62?0AA0
|
Rated armature supply voltage
|
V
|
3 AC 400 (+15 %/–20 %)
|
Rated armature input current
|
A
|
12
|
25
|
50
|
75
|
Cooling air requirement
|
m?/h
|
800
|
800
|
800
|
800
|
Sound pressure level
|
dB (A)
|
72
|
72
|
72
|
72
|
Rated frequency
|
Hz
|
45 ... 65
|
45 ... 65
|
45 ... 65
|
45 ... 65
|
Rated DC voltage
|
V
|
420
|
420
|
420
|
420
|
Rated DC current
|
A
|
15
|
30
|
60
|
90
|
Overload capability
|
x ? In
|
1.8
|
1.8
|
1.8
|
1.8
|
Rated power
|
kW
|
6.3
|
12.6
|
25.2
|
37.8
|
Power loss at rated DC current
|
W
|
292
|
372
|
485
|
587
|
Rated DC field voltage
|
V
|
max. 325
|
max. 325
|
max. 325
|
max. 325
|
Rated DC field current
|
A
|
3
|
5
|
10
|
10
|
Max. connection cross-sections 1)
|
|
|
|
|
|
- Line connection (3 phases and PE)
|
Number ? mm2
|
1 ? 2.5
|
1 ? 6
|
1 ? 16
|
1 ? 25
|
- Armature circuit connection
|
Number ? mm2
|
1 ? 2.5
|
1 ? 6
|
1 ? 16
|
1 ? 25
|
|
Number ? mm2
|
1 ? 1.5
|
1 ? 1.5
|
1 ? 1.5
|
1 ? 1.5
|
|
mm2
|
2.5
|
2.5
|
2.5
|
2.5
|
Max. permissible fusing on the customer's side (NH fuse gL/gG)
|
|
|
|
|
|
|
A
|
20
|
32
|
63
|
80
|
- Max. permissible short-circuit current
|
kA
|
50 2)
|
50 2)
|
50 2)
|
50 2)
|
|
A
|
16
|
16
|
16
|
16
|
- Max. permissible short-circuit current
|
kA
|
30
|
30
|
30
|
30
|
Normal ambient temperature in operation
|
°C
|
See the table on installation altitude and ambient temperature
|
Dimensions
|
|
|
|
|
|
|
mm
|
600
|
600
|
600
|
600
|
|
mm
|
2 326
|
2 326
|
2 326
|
2 326
|
|
mm
|
600
|
600
|
600
|
600
|
Size
|
|
BC
|
BC
|
BC
|
BC
|
Weight, approx.
|
kg
|
233
|
213
|
233
|
233
|
1) With cable lugs according to DIN 46234 or DIN 46235; for units from 2 600 to 3 000 A, motor cables are only directly connected at the DC converter using cable lugs according to DIN 46234.
2) With option L00 (radio interference suppression filter), the maximum permissible short-circuit current is reduced to 43 kA.
SINAMICS DC MASTER Cabinet for 400 V 3 AC, 125 to 400 A, four-quadrant operation
|
|
Type
|
|
|
6RM8031- 6DV62?0AA0
|
6RM8075- 6DV62?0AA0
|
6RM8078- 6DV62?0AA0
|
6RM8081- 6DV62?0AA0
|
Rated armature supply voltage
|
V
|
3 AC 400 (+15 %/–20 %)
|
Rated armature input current
|
A
|
104
|
174
|
232
|
332
|
Cooling air requirement
|
m?/h
|
800
|
800
|
800
|
600
|
Sound pressure level
|
dB (A)
|
72
|
72
|
72
|
74
|
Rated frequency
|
Hz
|
45 ... 65
|
45 ... 65
|
45 ... 65
|
45 ... 65
|
Rated DC voltage
|
V
|
420
|
420
|
420
|
420
|
Rated DC current
|
A
|
125
|
210
|
280
|
400
|
Overload capability
|
x ? In
|
1.8
|
1.8
|
1.8
|
1.8
|
Rated power
|
kW
|
52.5
|
88.2
|
117.6
|
168
|
Power loss at rated DC current
|
W
|
726
|
1 202
|
1 557
|
2 226
|
Rated DC field voltage
|
V
|
max. 325
|
max. 325
|
max. 325
|
max. 325
|
Rated DC field current
|
A
|
10
|
15
|
15
|
25
|
Max. connection cross-sections 1)
|
|
|
|
|
|
- Line connection (3 phases and PE)
|
Number ? mm2
|
1 ? 50
|
1 ? 95
|
1 ? 120
|
1 ? 185
|
- Armature circuit connection
|
Number ? mm2
|
1 ? 50
|
1 ? 95
|
2 ? 50
|
1 ? 185
|
|
Number ? mm2
|
1 ? 1.5
|
1 ? 2.5
|
1 ? 2.5
|
1 ? 4
|
|
mm2
|
2.5
|
4
|
4
|
10
|
Max. permissible fusing on the customer's side (NH fuse gL/gG)
|
|
|
|
|
|
|
A
|
125
|
200
|
250
|
355
|
- Max. permissible short-circuit current
|
kA
|
50 2)
|
50 3)
|
50 3)
|
50
|
|
A
|
16
|
25
|
25
|
50
|
- Max. permissible short-circuit current
|
kA
|
30
|
30
|
30
|
30
|
Normal ambient temperature in operation
|
°C
|
See the table on installation altitude and ambient temperature
|
Dimensions
|
|
|
|
|
|
|
mm
|
600
|
600
|
600
|
800
|
|
mm
|
2 326
|
2 326
|
2 326
|
2 200
|
|
mm
|
600
|
600
|
600
|
600
|
Size
|
|
BC
|
BC
|
BC
|
CC
|
Weight, approx.
|
kg
|
240
|
263
|
273
|
320
|
1) With cable lugs according to DIN 46234 or DIN 46235; for units from 2 600 to 3 000 A, motor cables are only directly connected at the DC converter using cable lugs according to DIN 46234.
2) With option L00 (radio interference suppression filter), the maximum permissible short-circuit current is reduced to 43 kA.
3) With option L00 (radio interference suppression filter), the maximum permissible short-circuit current is reduced to 25 kA.
SINAMICS DC MASTER Cabinet for 400 V 3 AC, 600 to 1 600 A, four-quadrant operation
|
|
Type
|
|
|
6RM8085- 6DV62?0AA0
|
6RM8087- 6DV62?0AA0
|
6RM8091- 6DV62?0AA0
|
6RM8093- 4DV62?0AA0
|
Rated armature supply voltage
|
V
|
3 AC 400 (+15 %/–20 %)
|
Rated armature input current
|
A
|
498
|
706
|
996
|
1 328
|
Cooling air requirement
|
m?/h
|
600
|
600
|
1 000
|
3 000
|
Sound pressure level
|
dB (A)
|
74
|
74
|
76
|
78
|
Rated frequency
|
Hz
|
45 ... 65
|
45 ... 65
|
45 ... 65
|
45 ... 65
|
Rated DC voltage
|
V
|
420
|
420
|
420
|
420
|
Rated DC current
|
A
|
600
|
850
|
1 200
|
1 600
|
Overload capability
|
x ? In
|
1.8
|
1.8
|
1.8
|
1.8
|
Rated power
|
kW
|
252
|
357
|
504
|
672
|
Power loss at rated DC current
|
W
|
2 984
|
3 939
|
4 697
|
6 430
|
Rated DC field voltage
|
V
|
max. 325
|
max. 325
|
max. 390
|
max. 390
|
Rated DC field current
|
A
|
25
|
30
|
30
|
40
|
Max. connection cross-sections 1)
|
|
|
|
|
|
- Line connection (3 phases and PE)
|
Number ? mm2
|
2 ? 150
|
2 ? 240
|
4 ? 150
|
6 ? 150
|
- Armature circuit connection
|
Number ? mm2
|
2 ? 150
|
4 ? 95
|
4 ? 185
|
8 ? 95
|
|
Number ? mm2
|
1 ? 4
|
1 ? 4
|
1 ? 4
|
1 ? 6
|
|
mm2
|
10
|
16
|
16
|
35
|
Max. permissible fusing on the customer's side (NH fuse gL/gG)
|
|
|
|
|
|
|
A
|
500
|
710
|
– 2)
|
– 2)
|
- Max. permissible short-circuit current
|
kA
|
50
|
50
|
65
|
75
|
|
A
|
50
|
63
|
63
|
100
|
- Max. permissible short-circuit current
|
kA
|
30
|
30
|
30
|
50
|
Normal ambient temperature in operation
|
°C
|
See the table on installation altitude and ambient temperature
|
Dimensions
|
|
|
|
|
|
|
mm
|
800
|
1 200
|
1 200
|
1 400
|
|
mm
|
2 200
|
2 200
|
2 200
|
2 200
|
|
mm
|
600
|
600
|
600
|
600
|
Size
|
|
CC
|
DC
|
DC
|
EC
|
Weight, approx.
|
kg
|
340
|
490
|
570
|
780
|
1) With cable lugs according to DIN 46234 or DIN 46235; for units from 2 600 to 3 000 A, motor cables are only directly connected at the DC converter using cable lugs according to DIN 46234.
2) It must be ensured that the maximum permissible short-circuit current at the supply switch of the drive cabinet is not exceeded.
SINAMICS DC MASTER Cabinet for 400 V 3 AC, 2 000 to 3 000 A, four-quadrant operation
|
|
Type
|
|
|
6RM8095- 4DV62?0AA0
|
6RM8098- 4DV62?0AA0
|
Rated armature supply voltage
|
V
|
3 AC 400 (+15 %/–20 %)
|
Rated armature input current
|
A
|
1 660
|
2 490
|
Cooling air requirement
|
m?/h
|
3 000
|
3 000
|
Sound pressure level
|
dB (A)
|
78
|
78
|
Rated frequency
|
Hz
|
45 ... 65
|
45 ... 65
|
Rated DC voltage
|
V
|
420
|
420
|
Rated DC current
|
A
|
2 000
|
3 000
|
Overload capability
|
x ? In
|
1.8
|
1.8
|
Rated power
|
kW
|
840
|
1 260
|
Power loss at rated DC current
|
W
|
7 618
|
11 747
|
Rated DC field voltage
|
V
|
max. 390
|
max. 390
|
Rated DC field current
|
A
|
40
|
40
|
Max. connection cross-sections 1)
|
|
|
|
- Line connection (3 phases and PE)
|
Number ? mm2
|
6 ? 185
|
8 ? 240
|
- Armature circuit connection
|
Number ? mm2
|
8 ? 150
|
8 ? 240
|
|
Number ? mm2
|
1 ? 6
|
1 ? 6
|
|
mm2
|
35
|
35
|
Max. permissible fusing on the customer's side (NH fuse gL/gG)
|
|
|
|
|
A
|
– 2)
|
– 2)
|
- Max. permissible short-circuit current
|
kA
|
75
|
75
|
|
A
|
100
|
100
|
- Max. permissible short-circuit current
|
kA
|
50
|
50
|
Normal ambient temperature in operation
|
°C
|
See the table on installation altitude and ambient temperature
|
Dimensions
|
|
|
|
|
mm
|
1 400
|
1 400
|
|
mm
|
2 200
|
2 200
|
|
mm
|
600
|
600
|
Size
|
|
EC
|
EC
|
Weight, approx.
|
kg
|
820
|
950
|
1) With cable lugs according to DIN 46234 or DIN 46235; for units from 2 600 to 3 000 A, motor cables are only directly connected at the DC converter using cable lugs according to DIN 46234.
2) It must be ensured that the maximum permissible short-circuit current at the supply switch of the drive cabinet is not exceeded.
SINAMICS DC MASTER Cabinet for 480 V 3 AC, 15 to 90 A, four-quadrant operation
|
|
Type
|
|
|
6RM8013- 6FV62?0AA0
|
6RM8018- 6FV62?0AA0
|
6RM8025- 6FV62?0AA0
|
6RM8028- 6FV62?0AA0
|
Rated armature supply voltage
|
V
|
3 AC 480 (+10 %/–20 %)
|
Rated armature input current
|
A
|
12
|
25
|
50
|
75
|
Cooling air requirement
|
m?/h
|
800
|
800
|
800
|
800
|
Sound pressure level
|
dB (A)
|
72
|
72
|
72
|
72
|
Rated frequency
|
Hz
|
45 ... 65
|
45 ... 65
|
45 ... 65
|
45 ... 65
|
Rated DC voltage
|
V
|
500
|
500
|
500
|
500
|
Rated DC current
|
A
|
15
|
30
|
60
|
90
|
Overload capability
|
x ? In
|
1.8
|
1.8
|
1.8
|
1.8
|
Rated power
|
kW
|
6.3
|
15
|
30
|
45
|
Power loss at rated DC current
|
W
|
292
|
377
|
534
|
609
|
Rated DC field voltage
|
V
|
max. 390
|
max. 390
|
max. 390
|
max. 390
|
Rated DC field current
|
A
|
3
|
5
|
10
|
10
|
Max. connection cross-sections 1)
|
|
|
|
|
|
- Line connection (3 phases and PE)
|
Number ? mm2
|
1 ? 2.5
|
1 ? 6
|
1 ? 16
|
1 ? 25
|
- Armature circuit connection
|
Number ? mm2
|
1 ? 2.5
|
1 ? 6
|
1 ? 16
|
1 ? 25
|
|
Number ? mm2
|
1 ? 1.5
|
1 ? 1.5
|
1 ? 1.5
|
1 ? 1.5
|
|
mm2
|
2.5
|
2.5
|
2.5
|
2.5
|
Max. permissible fusing on the customer's side (NH fuse gL/gG)
|
|
|
|
|
|
|
A
|
20
|
32
|
63
|
80
|
- Max. permissible short-circuit current
|
kA
|
50 2)
|
50 2)
|
50 2)
|
50 2)
|
|
A
|
16
|
16
|
16
|
16
|
- Max. permissible short-circuit current
|
kA
|
30
|
30
|
30
|
30
|
Normal ambient temperature in operation
|
°C
|
See the table on installation altitude and ambient temperature
|
Dimensions
|
|
|
|
|
|
|
mm
|
600
|
600
|
600
|
600
|
|
mm
|
2 326
|
2 326
|
2 326
|
2 326
|
|
mm
|
600
|
600
|
600
|
600
|
Size
|
|
BC
|
BC
|
BC
|
BC
|
Weight, approx.
|
kg
|
210
|
215
|
233
|
238
|
1) With cable lugs according to DIN 46234 or DIN 46235; for units from 2 600 to 3 000 A, motor cables are only directly connected at the DC converter using cable lugs according to DIN 46234.
2) With option L00 (radio interference suppression filter), the maximum permissible short-circuit current is reduced to 43 kA.
SINAMICS DC MASTER Cabinet for 480 V 3 AC, 125 to 450 A, four-quadrant operation
|
|
Type
|
|
|
6RM8031- 6FV62?0AA0
|
6RM8075- 6FV62?0AA0
|
6RM8078- 6FV62?0AA0
|
6RM8082- 6FV62?0AA0
|
Rated armature supply voltage
|
V
|
3 AC 480 (+10 %/–20 %)
|
Rated armature input current
|
A
|
104
|
174
|
232
|
374
|
Cooling air requirement
|
m?/h
|
800
|
800
|
800
|
600
|
Sound pressure level
|
dB (A)
|
72
|
72
|
72
|
74
|
Rated frequency
|
Hz
|
45 ... 65
|
45 ... 65
|
45 ... 65
|
45 ... 65
|
Rated DC voltage
|
V
|
500
|
500
|
500
|
500
|
Rated DC current
|
A
|
125
|
210
|
280
|
450
|
Overload capability
|
x ? In
|
1.8
|
1.8
|
1.8
|
1.8
|
Rated power
|
kW
|
62.5
|
105
|
140
|
225
|
Power loss at rated DC current
|
W
|
748
|
1 275
|
1 556
|
2 467
|
Rated DC field voltage
|
V
|
max. 390
|
max. 390
|
max. 390
|
max. 390
|
Rated DC field current
|
A
|
10
|
15
|
15
|
25
|
Max. connection cross-sections 1)
|
|
|
|
|
|
- Line connection (3 phases and PE)
|
Number ? mm2
|
1 ? 50
|
1 ? 95
|
1 ? 120
|
2 ? 120
|
- Armature circuit connection
|
Number ? mm2
|
1 ? 50
|
1 ? 95
|
2 ? 50
|
2 ? 95
|
|
Number ? mm2
|
1 ? 1.5
|
1 ? 2.5
|
1 ? 2.5
|
1 ? 4
|
|
mm2
|
2.5
|
4
|
4
|
10
|
Max. permissible fusing on the customer's side (NH fuse gL/gG)
|
|
|
|
|
|
|
A
|
125
|
200
|
250
|
400
|
- Max. permissible short-circuit current
|
kA
|
50 2)
|
50 3)
|
50 3)
|
50
|
|
A
|
16
|
25
|
25
|
50
|
- Max. permissible short-circuit current
|
kA
|
30
|
30
|
30
|
30
|
Normal ambient temperature in operation
|
°C
|
See the table on installation altitude and ambient temperature
|
Dimensions
|
|
|
|
|
|
|
mm
|
600
|
600
|
600
|
800
|
|
mm
|
2 326
|
2 326
|
2 326
|
2 200
|
|
mm
|
600
|
600
|
600
|
600
|
Size
|
|
BC
|
BC
|
BC
|
CC
|
Weight, approx.
|
kg
|
240
|
273
|
273
|
340
|
1) With cable lugs according to DIN 46234 or DIN 46235; for units from 2 600 to 3 000 A, motor cables are only directly connected at the DC converter using cable lugs according to DIN 46234.
2) With option L00 (radio interference suppression filter), the maximum permissible short-circuit current is reduced to 43 kA.
3) With option L00 (radio interference suppression filter), the maximum permissible short-circuit current is reduced to 25 kA.
SINAMICS DC MASTER Cabinet for 480 V 3 AC, 600 to 1 200 A, four-quadrant operation
|
|
Type
|
|
|
6RM8085- 6FV62?0AA0
|
6RM8087- 6FV62?0AA0
|
6RM8091- 6FV62?0AA0
|
Rated armature supply voltage
|
V
|
3 AC 480 (+10 %/–20 %)
|
Rated armature input current
|
A
|
498
|
706
|
996
|
Cooling air requirement
|
m?/h
|
600
|
600
|
1 000
|
Sound pressure level
|
dB (A)
|
74
|
74
|
76
|
Rated frequency
|
Hz
|
45 ... 65
|
45 ... 65
|
45 ... 65
|
Rated DC voltage
|
V
|
500
|
500
|
500
|
Rated DC current
|
A
|
600
|
850
|
1 200
|
Overload capability
|
x ? In
|
1.8
|
1.8
|
1.8
|
Rated power
|
kW
|
300
|
425
|
600
|
Power loss at rated DC current
|
W
|
3 197
|
4 303
|
4 857
|
Rated DC field voltage
|
V
|
max. 390
|
max. 390
|
max. 390
|
Rated DC field current
|
A
|
25
|
30
|
30
|
Max. connection cross-sections 1)
|
|
|
|
|
- Line connection (3 phases and PE)
|
Number ? mm2
|
2 ? 150
|
2 ? 240
|
4 ? 150
|
- Armature circuit connection
|
Number ? mm2
|
2 ? 150
|
4 ? 95
|
4 ? 185
|
|
Number ? mm2
|
1 ? 4
|
1 ? 4
|
1 ? 4
|
|
mm2
|
10
|
16
|
16
|
Max. permissible fusing on the customer's side (NH fuse gL/gG)
|
|
|
|
|
|
A
|
500
|
710
|
– 2)
|
- Max. permissible short-circuit current
|
kA
|
50
|
50
|
65
|
|
A
|
50
|
63
|
63
|
- Max. permissible short-circuit current
|
kA
|
30
|
30
|
30
|
Normal ambient temperature in operation
|
°C
|
See the table on installation altitude and ambient temperature
|
Dimensions
|
|
|
|
|
|
mm
|
800
|
1 200
|
1 200
|
|
mm
|
2 200
|
2 200
|
2 200
|
|
mm
|
600
|
600
|
600
|
Size
|
|
CC
|
DC
|
DC
|
Weight, approx.
|
kg
|
355
|
500
|
570
|
1) With cable lugs according to DIN 46234 or DIN 46235; for units from 2 600 to 3 000 A, motor cables are only directly connected at the DC converter using cable lugs according to DIN 46234.
2) It must be ensured that the maximum permissible short-circuit current at the supply switch of the drive cabinet is not exceeded.
SINAMICS DC MASTER Cabinet for 575 V 3 AC, 60 to 400 A, four-quadrant operation
|
|
Type
|
|
|
6RM8025- 6GV62?0AA0
|
6RM8031- 6GV62?0AA0
|
6RM8075- 6GV62?0AA0
|
6RM8081- 6GV62?0AA0
|
Rated armature supply voltage
|
V
|
3 AC 575 (+10 %/–20 %)
|
Rated armature input current
|
A
|
50
|
104
|
174
|
332
|
Cooling air requirement
|
m?/h
|
800
|
800
|
800
|
600
|
Sound pressure level
|
dB (A)
|
72
|
72
|
72
|
74
|
Rated frequency
|
Hz
|
45 ... 65
|
45 ... 65
|
45 ... 65
|
45 ... 65
|
Rated DC voltage
|
V
|
600
|
600
|
600
|
600
|
Rated DC current
|
A
|
60
|
125
|
210
|
400
|
Overload capability
|
x ? In
|
1.8
|
1.8
|
1.8
|
1.8
|
Rated power
|
kW
|
36
|
75
|
126
|
240
|
Power loss at rated DC current
|
W
|
509
|
797
|
1 320
|
2 534
|
Rated DC field voltage
|
V
|
max. 390
|
max. 390
|
max. 390
|
max. 390
|
Rated DC field current
|
A
|
10
|
10
|
15
|
25
|
Max. connection cross-sections 1)
|
|
|
|
|
|
- Line connection (3 phases and PE)
|
Number ? mm2
|
1 ? 16
|
1 ? 50
|
1 ? 95
|
1 ? 185
|
- Armature circuit connection
|
Number ? mm2
|
1 ? 16
|
1 ? 50
|
1 ? 95
|
1 ? 185
|
|
Number ? mm2
|
1 ? 1.5
|
1 ? 2.5
|
1 ? 2.5
|
1 ? 4
|
|
mm2
|
2.5
|
2.5
|
4
|
10
|
Max. permissible fusing on the customer's side (NH fuse gL/gG)
|
|
|
|
|
|
|
A
|
63
|
125
|
200
|
355
|
- Max. permissible short-circuit current
|
kA
|
50 2)
|
50 2)
|
50 3)
|
50
|
|
A
|
16
|
16
|
25
|
50
|
- Max. permissible short-circuit current
|
kA
|
30
|
30
|
30
|
30
|
Normal ambient temperature in operation
|
°C
|
See the table on installation altitude and ambient temperature
|
Dimensions
|
|
|
|
|
|
|
mm
|
600
|
600
|
600
|
800
|
|
mm
|
2 326
|
2 326
|
2 326
|
2 200
|
|
mm
|
600
|
600
|
600
|
600
|
Size
|
|
BC
|
BC
|
BC
|
CC
|
Weight, approx.
|
kg
|
233
|
240
|
273
|
335
|
1) With cable lugs according to DIN 46234 or DIN 46235; for units from 2 600 to 3 000 A, motor cables are only directly connected at the DC converter using cable lugs according to DIN 46234.
2) With option L00 (radio interference suppression filter), the maximum permissible short-circuit current is reduced to 43 kA.
3) With option L00 (radio interference suppression filter), the maximum permissible short-circuit current is reduced to 25 kA.
SINAMICS DC MASTER Cabinet for 575 V 3 AC, 600 to 1 600 A, four-quadrant operation
|
|
Type
|
|
|
6RM8085- 6GV62?0AA0
|
6RM8087- 6GV62?0AA0
|
6RM8090- 6GV62?0AA0
|
6RM8093- 4GV62?0AA0
|
Rated armature supply voltage
|
V
|
3 AC 575 (+10 %/–20 %)
|
Rated armature input current
|
A
|
498
|
706
|
913
|
1 328
|
Cooling air requirement
|
m?/h
|
600
|
600
|
1 000
|
3 000
|
Sound pressure level
|
dB (A)
|
74
|
74
|
76
|
78
|
Rated frequency
|
Hz
|
45 ... 65
|
45 ... 65
|
45 ... 65
|
45 ... 65
|
Rated DC voltage
|
V
|
600
|
600
|
600
|
600
|
Rated DC current
|
A
|
600
|
850
|
1 100
|
1 600
|
Overload capability
|
x ? In
|
1.8
|
1.8
|
1.8
|
1.8
|
Rated power
|
kW
|
360
|
510
|
660
|
960
|
Power loss at rated DC current
|
W
|
3 290
|
4 112
|
4 583
|
6 988
|
Rated DC field voltage
|
V
|
max. 390
|
max. 390
|
max. 390
|
max. 390
|
Rated DC field current
|
A
|
25
|
30
|
30
|
40
|
Max. connection cross-sections 1)
|
|
|
|
|
|
- Line connection (3 phases and PE)
|
Number ? mm2
|
2 ? 150
|
2 ? 240
|
4 ? 150
|
6 ? 150
|
- Armature circuit connection
|
Number ? mm2
|
2 ? 150
|
4 ? 95
|
4 ? 120
|
8 ? 95
|
|
Number ? mm2
|
1 ? 4
|
1 ? 4
|
1 ? 4
|
1 ? 6
|
|
mm2
|
10
|
16
|
16
|
35
|
Max. permissible fusing on the customer's side (NH fuse gL/gG)
|
|
|
|
|
|
|
A
|
500
|
710
|
– 2)
|
– 2)
|
- Max. permissible short-circuit current
|
kA
|
50
|
50
|
65
|
75
|
|
A
|
50
|
63
|
63
|
100
|
- Max. permissible short-circuit current
|
kA
|
30
|
30
|
30
|
50
|
Normal ambient temperature in operation
|
°C
|
See the table on installation altitude and ambient temperature
|
Dimensions
|
|
|
|
|
|
|
mm
|
800
|
1 200
|
1 200
|
1 400
|
|
mm
|
2 200
|
2 200
|
2 200
|
2 200
|
|
mm
|
600
|
600
|
600
|
600
|
Size
|
|
CC
|
DC
|
DC
|
EC
|
Weight, approx.
|
kg
|
355
|
515
|
600
|
795
|
1) With cable lugs according to DIN 46234 or DIN 46235; for units from 2 600 to 3 000 A, motor cables are only directly connected at the DC converter using cable lugs according to DIN 46234.
2) It must be ensured that the maximum permissible short-circuit current at the supply switch of the drive cabinet is not exceeded.
SINAMICS DC MASTER Cabinet for 575 V 3 AC, 2 000 to 2 800 A, four-quadrant operation
|
|
Type
|
|
|
6RM8095- 4GV62?0AA0
|
6RM8096- 4GV62?0AA0
|
6RM8097- 4GV62?0AA0
|
Rated armature supply voltage
|
V
|
3 AC 575 (+10 %/–20 %)
|
Rated armature input current
|
A
|
1 660
|
1 826
|
2 324
|
Cooling air requirement
|
m?/h
|
3 000
|
3 000
|
3 000
|
Sound pressure level
|
dB (A)
|
78
|
78
|
78
|
Rated frequency
|
Hz
|
45 ... 65
|
45 ... 65
|
45 ... 65
|
Rated DC voltage
|
V
|
600
|
600
|
600
|
Rated DC current
|
A
|
2 000
|
2 200
|
2 800
|
Overload capability
|
x ? In
|
1.8
|
1.8
|
1.8
|
Rated power
|
kW
|
1 200
|
1 320
|
1 680
|
Power loss at rated DC current
|
W
|
8 090
|
8 408
|
11 937
|
Rated DC field voltage
|
V
|
max. 390
|
max. 390
|
max. 390
|
Rated DC field current
|
A
|
40
|
40
|
40
|
Max. connection cross-sections 1)
|
|
|
|
|
- Line connection (3 phases and PE)
|
Number ? mm2
|
6 ? 185
|
8 ? 150
|
8 ? 240
|
- Armature circuit connection
|
Number ? mm2
|
8 ? 150
|
8 ? 185
|
8 ? 240
|
|
Number ? mm2
|
1 ? 6
|
1 ? 6
|
1 ? 6
|
|
mm2
|
35
|
35
|
35
|
Max. permissible fusing on the customer's side (NH fuse gL/gG)
|
|
|
|
|
|
A
|
– 2)
|
– 2)
|
– 2)
|
- Max. permissible short-circuit current
|
kA
|
75
|
75
|
75
|
|
A
|
100
|
100
|
100
|
- Max. permissible short-circuit current
|
kA
|
50
|
50
|
50
|
Normal ambient temperature in operation
|
°C
|
See the table on installation altitude and ambient temperature
|
Dimensions
|
|
|
|
|
|
mm
|
1 400
|
1 400
|
1 400
|
|
mm
|
2 200
|
2 200
|
2 200
|
|
mm
|
600
|
600
|
600
|
Size
|
|
EC
|
EC
|
EC
|
Weight, approx.
|
kg
|
850
|
950
|
1 030
|
1) With cable lugs according to DIN 46234 or DIN 46235; for units from 2 600 to 3 000 A, motor cables are only directly connected at the DC converter using cable lugs according to DIN 46234.
2) It must be ensured that the maximum permissible short-circuit current at the supply switch of the drive cabinet is not exceeded.
SINAMICS DC MASTER Cabinet for 690 V 3 AC, 760 to 2 600 A, four-quadrant operation
|
|
Type
|
|
|
6RM8086- 6KV62?0AA0
|
6RM8090- 6KV62?0AA0
|
6RM8093- 4KV62?0AA0
|
6RM8095- 4KV62?0AA0
|
6RM8097- 4KV62?0AA0
|
Rated armature supply voltage
|
V
|
3 AC 690 (+10 %/–20 %)
|
Rated armature input current
|
A
|
631
|
830
|
1 245
|
1 660
|
2 158
|
Cooling air requirement
|
m?/h
|
600
|
1 000
|
3 000
|
3 000
|
3 000
|
Sound pressure level
|
dB (A)
|
74
|
76
|
78
|
78
|
78
|
Rated frequency
|
Hz
|
45 ... 65
|
45 ... 65
|
45 ... 65
|
45 ... 65
|
45 ... 65
|
Rated DC voltage
|
V
|
725
|
725
|
725
|
725
|
725
|
Rated DC current
|
A
|
760
|
1 000
|
1 500
|
2 000
|
2 600
|
Overload capability
|
x ? In
|
1.8
|
1.8
|
1.8
|
1.8
|
1.8
|
Rated power
|
kW
|
551
|
725
|
1 087.5
|
1 450
|
1 885
|
Power loss at rated DC current
|
W
|
4 352
|
4 642
|
7 627
|
9 175
|
12 007
|
Rated DC field voltage
|
V
|
max. 390
|
max. 390
|
max. 390
|
max. 390
|
max. 390
|
Rated DC field current
|
A
|
30
|
30
|
40
|
40
|
40
|
Max. connection cross-sections 1)
|
|
|
|
|
|
|
- Line connection (3 phases and PE)
|
Number ? mm2
|
2 ? 240
|
4 ? 120
|
6 ? 120
|
6 ? 185
|
8 ? 240
|
- Armature circuit connection
|
Number ? mm2
|
4 ? 95
|
4 ? 120
|
8 ? 95
|
8 ? 150
|
8 ? 240
|
|
Number ? mm2
|
1 ? 4
|
1 ? 4
|
1 ? 6
|
1 ? 6
|
1 ? 6
|
|
mm2
|
16
|
16
|
35
|
35
|
35
|
Max. permissible fusing on the customer's side (NH fuse gL/gG)
|
|
|
|
|
|
|
|
A
|
630
|
– 2)
|
– 2)
|
– 2)
|
– 2)
|
- Max. permissible short-circuit current
|
kA
|
50
|
65
|
75
|
75
|
75
|
|
A
|
63
|
63
|
100
|
100
|
100
|
- Max. permissible short-circuit current
|
kA
|
30
|
30
|
50
|
50
|
50
|
Normal ambient temperature in operation
|
°C
|
See the table on installation altitude and ambient temperature
|
Dimensions
|
|
|
|
|
|
|
|
mm
|
1 200
|
1 200
|
1 400
|
1 400
|
1 600
|
|
mm
|
2 200
|
2 200
|
2 200
|
2 200
|
2 200
|
|
mm
|
600
|
600
|
600
|
600
|
600
|
Size
|
|
DC
|
DC
|
EC
|
EC
|
FC
|
Weight, approx.
|
kg
|
515
|
600
|
815
|
850
|
1 070
|
1) With cable lugs according to DIN 46234 or DIN 46235; for units from 2 600 to 3 000 A, motor cables are only directly connected at the DC converter using cable lugs according to DIN 46234.
2) It must be ensured that the maximum permissible short-circuit current at the supply switch of the drive cabinet is not exceeded.
SINAMICS DC MASTER Cabinet for 830 V 3 AC, 950 to 1 900 A and 950 V 3 AC, 2 200 V, four-quadrant operation
|
|
Type
|
|
|
6RM8088- 6LV62?0AA0
|
6RM8093- 4LV62?0AA0
|
6RM8095- 4LV62?0AA0
|
6RM8096- 4MV62?0AA0
|
Rated armature supply voltage
|
V
|
3 AC 830 (+10 %/–20 %)
|
3 AC 950 (+15%/–20%)
|
Rated armature input current
|
A
|
789
|
1 245
|
1 577
|
1 826
|
Cooling air requirement
|
m?/h
|
1 000
|
3 000
|
3 000
|
3 000
|
Sound pressure level
|
dB (A)
|
76
|
78
|
78
|
78
|
Rated frequency
|
Hz
|
45 ... 65
|
45 ... 65
|
45 ... 65
|
45 ... 65
|
Rated DC voltage
|
V
|
875
|
875
|
875
|
1 000
|
Rated DC current
|
A
|
950
|
1 500
|
1 900
|
2 200
|
Overload capability
|
x ? In
|
1.8
|
1.8
|
1.8
|
1.8
|
Rated power
|
kW
|
831.25
|
1 312.5
|
1 662.5
|
2 200
|
Power loss at rated DC current
|
W
|
4 911
|
8 039
|
9 986
|
12 957
|
Rated DC field voltage
|
V
|
max. 390
|
max. 390
|
max. 390
|
max. 390
|
Rated DC field current
|
A
|
30
|
40
|
40
|
40
|
Max. connection cross-sections 1)
|
|
|
|
|
|
- Line connection (3 phases and PE)
|
Number ? mm2
|
4 ? 120
|
6 ? 120
|
6 ? 185
|
8 ? 150
|
- Armature circuit connection
|
Number ? mm2
|
4 ? 150
|
8 ? 95
|
8 ? 150
|
8 ? 185
|
|
Number ? mm2
|
1 ? 4
|
1 ? 6
|
1 ? 6
|
1 ? 6
|
|
mm2
|
16
|
35
|
35
|
35
|
Max. permissible fusing on the customer's side (NH fuse gL/gG)
|
|
|
|
|
|
|
A
|
– 2)
|
– 2)
|
– 2)
|
– 2)
|
- Max. permissible short-circuit current
|
kA
|
50
|
50
|
50
|
50
|
|
A
|
63
|
100
|
100
|
100
|
- Max. permissible short-circuit current
|
kA
|
30
|
50
|
50
|
50
|
Normal ambient temperature in operation
|
°C
|
See the table on installation altitude and ambient temperature
|
Dimensions
|
|
|
|
|
|
|
mm
|
1 200
|
1 400
|
1 400
|
1 600
|
|
mm
|
2 200
|
2 200
|
2 200
|
2 200
|
|
mm
|
600
|
600
|
600
|
600
|
Size
|
|
DC
|
EC
|
EC
|
FC
|
Weight, approx.
|
kg
|
600
|
845
|
925
|
1 070
|
1) With cable lugs according to DIN 46234 or DIN 46235; for units from 2 600 to 3 000 A, motor cables are only directly connected at the DC converter using cable lugs according to DIN 46234.
2) It must be ensured that the maximum permissible short-circuit current at the supply switch of the drive cabinet is not exceeded.
|
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Àðìàòóðà DENDOR
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Äàò÷èêè è èçìåðèòåëè
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ðåãóëÿòîðû è ðåãèñòðàòîðû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ïíåâìàòè÷åñêîå îáîðóäîâàíèå
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Êðàíû è Êëàïàíû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Èçìåðèòåëüíûå ïðèáîðû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ñèñòåìû áåñïðîâîäíîãî óïðàâëåíèÿ «óìíûé äîì»
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Áåñêîíòàêòíûå âûêëþ÷àòåëè Êîíå÷íûå âûêëþ÷àòåëè Îïòè÷åñêèå äàò÷èêè Ýíêîäåðû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FS - Óñòàíîâêà óìÿã÷åíèÿ
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FK - Óñòàíîâêà îáåçæåëåçèâàíèÿ
|