General technical specifications |
|---|
Relevant standards | EN 50178 | Electronic equipment for use in power installations | EN 50274 | Low-voltage switchgear and controlgear assemblies: Protection against electric shock – Protection against unintentional direct contact with hazardous live parts | EN 60146-1-1 | Semiconductor converters: General requirements and line-commutated converters; specification of basic requirements | EN 61800-1 | Adjustable speed electrical power drive systems, Part 1 – (DC drives) General requirements – Rating specifications for low voltage adjustable speed DC power drive systems | EN 61800-3 | Adjustable speed electrical power drive systems, Part 3 – EMC product standard including specific test methods | EN 61800-5-1 | Adjustable speed electrical power drive systems – Part 5-1: Requirements regarding safety – electrical, thermal, and energy requirements | IEC 62103 (identical to EN 50178) | Electronic equipment for use in power installations | UBC 97 | Uniform Building Code | Electrical specifications | Overvoltage category | Category II acc. to EN 61800-5-1 within the line supply circuits Category III acc. to EN 61800-5-1 for line supply circuits with respect to the environment (other line supply circuits, housing, electronics) | Overvoltage strength | Class 1 acc. to EN 50178 | Short-circuit current | Rated supply voltage | Rated DC current | Short-circuit current, max. | V | A | kA | 400, 480 3 AC | 15 ... 1200 | 65 | 1600, 2000 | 85 | 3000 | 100 | 575, 690, 830, 950 3 AC | 60 ... 850 | 65 | 950 ... 1600 | 85 | 1900 ... 2800 | 100 | Radio interference suppression | No radio interference suppression according to EN 61800-3 | Mechanical data | Degree of protection | IP00 acc. to EN 60529; IP20 with accessories "Mounting kit to upgrade to IP20" for units up to 850 A | Protection class | Class 1 acc. to EN 61140 | Cooling method | | - Units ≤ 125 A rated DC current: Permissible ambient temperature in operation
| Self-ventilated 0 ... 45 °C - for higher ambient temperature, refer to current derating | - Units ≥ 210 A rated DC current: Permissible ambient temperature in operation
| Forced-air cooling with integrated fan 0 ... 40 °C - for higher ambient temperature, refer to current derating | Closed-loop control stability | | - for pulse encoder operation and digital setpoint
| Δn = 0.006 % of the rated motor speed | - for analog tachometer and analog setpoint 1)
| Δn = 0.1 % of the rated motor speed | MTBF | > 170000 h | Environmental conditions | Permissible ambient temperature during storage and transport | -40 ... +70 °C | Permissible humidity | Relative air humidity ≤ 95 % (75 % at 17 °C as average annual value, 95 % at 24 °C max., condensation not permissible) | Climate class | 3K3 acc. to EN 60721-3-3 | Insulation | Pollution degree 2 according to EN 61800-5-1 Condensation not permissible | Installation altitude | ≤ 1000 m above sea level (100 % load capability) > 1000 ... 5000 m above sea level (see under "Coolant temperature and installation altitude") | Mechanical strength | Storage | Transport | Operation | Vibratory load | 1M2 acc. to EN 60721-3-1 (dropping not permissible) | 2M2 acc. to EN 60721-3-2 (dropping not permissible) | Constant deflection: 0.075 mm at 10 to 58 Hz Constant acceleration: 10 m/s2 at > 58 to 200 Hz (testing and measuring techniques acc. to EN 60068-2-6, Fc) | Shock load | 100 m/s2 at 11 ms (testing and measuring techniques acc. to EN 60068-2-27, Ea) | Approvals | UL/cUL | UL file No.: E203250 | UL 508 C (UL Standard for Power Conversion Equipment) | Certification of the units up to and including 575 V | GOST | Lloyd´s Register | In order to maintain the important limit values for marine certification, radio interference suppression filters should be used (see "Accessories and supplementary components") and option M08 (coated PCBs) should be selected. | Det Norske Veritas | American Bureau of Shipping | Germanischer Lloyd |
1) Conditions: The closed-loop control (PI control) stability is referred to the rated motor speed and applies when the SINAMICS DC MASTER is in the warm operating condition. This is based on the following preconditions: - Temperature changes of ±10 °C - Line supply voltage changes of +10 % / -5 % of the rated input voltage - Temperature coefficient of the tachometer generator with temperature compensation 0.15 ‰ every 10 °C (for analog tachometer generators only) - Constant setpoint SINAMICS DC MASTER converters for 400 V 3 AC, 60 to 280 A, two-quadrant operation | | Type |
|---|
| | | 6RA8025- 6DS22-0AA0 | 6RA8028- 6DS22-0AA0 | 6RA8031- 6DS22-0AA0 | 6RA8075- 6DS22-0AA0 | 6RA8078- 6DS22-0AA0 |
|---|
Rated armature supply voltage 1) | V | 400 3 AC (+15/-20 %) | Rated armature input current | A | 50 | 75 | 104 | 174 | 232 | Rated supply voltage, electronics power supply | V | 380 (-25 %) … 480 (+10 %) 2 AC; In = 1 A or 190 (-25 %) … 240 (+10 %) 2 AC; In = 2 A | Rated fan supply voltage | V | Self-ventilated | 24 V DC internal | Rated fan current | A | Internal supply | Cooling air requirement | m3/h | 300 | Sound pressure level 2) | dB (A) | 52.4 | Rated field supply voltage 1) | V | 400 V 2 AC (+15/-20 %) | Rated frequency | Hz | 45 … 65 | Rated DC voltage 1) | V | 485 | Rated DC current | A | 60 | 90 | 125 | 210 | 280 | Overload capability | x × In | 1.8 | Rated power | kW | 29 | 44 | 61 | 102 | 136 | Power loss at rated DC current | kW | 0.25 | 0.36 | 0.41 | 0.69 | 0.81 | Rated DC field voltage 1) | V | Max. 325 | Rated DC field current | A | 10 | 15 | Normal ambient temperature in operation 3) | °C | 0 … +45 | 0 … +40 | Storage and transport temperature | °C | -40 … +70 | Installation altitude above sea level 3) | | ≤ 1000 m for rated DC current | Dimensions | | mm | 268 | | mm | 385 | | mm | 252 | Weight, approx. | kg | 10 | 14 | 15 |
Note: Detailed dimensional drawings in PDF and DXF format are available on the Internet at http://support.automation.siemens.com/WW/view/en/81717045. Data for single-phase connection | | Type |
|---|
| | | 6RA8025- 6DS22-0AA0 | 6RA8028- 6DS22-0AA0 | 6RA8031- 6DS22-0AA0 | | |
|---|
Rated DC voltage | V | 320 | | | Rated DC current | A | 42.0 | 63.0 | 87.5 | | |
1) The armature/field supply voltage may be lower than the rated armature/field voltage (set by parameter). A minimum input voltage of 50 V is permissible for units with a rated voltage of 400 V, 480 V and 575 V, or 85 V for higher rated voltages. The output voltage is reduced accordingly. The specified DC output voltage can be maintained up to an undervoltage of 5 % of the line supply voltage (rated armature/field supply voltage). 2) Fan noise for a unit installed in an IP20 electrical cabinet (door closed, 50 Hz operation or operation at 24 V DC for units with an internal supply). 3) For derating factors at higher temperatures and installation altitudes, see „Current derating“. SINAMICS DC MASTER converters for 400 V 3 AC, 400 to 1200 A, two-quadrant operation | | Type |
|---|
| | | 6RA8081- 6DS22-0AA0 | 6RA8085- 6DS22-0AA0 | 6RA8087- 6DS22-0AA0 | 6RA8091- 6DS22-0AA0 |
|---|
Rated armature supply voltage 1) | V | 400 3 AC (+15/-20 %) | Rated armature input current | A | 332 | 498 | 706 | 996 | Rated supply voltage, electronics power supply | V | 380 (-25 %) … 480 (+10 %) 2 AC; In = 1 A or 190 (-25 %) … 240 (+10 %) 2 AC; In = 2 A | Rated fan supply voltage | V | 400 V 3 AC ± 10 % (50 Hz) 460 V 3 AC ± 10 % (60 Hz) | Rated fan current | A | 0.23 3) | 0.3 3) | Cooling air requirement | m3/h | 600 | 1000 | Sound pressure level 2) | dB (A) | 64.5 | Rated field supply voltage 1) | V | 400 2 AC (+15/-20 %) | 480 2 AC (+10/-20 %) | Rated frequency | Hz | 45 … 65 | Rated DC voltage 1) | V | 485 | Rated DC current | A | 400 | 600 | 850 | 1200 | Overload capability | x × In | 1.8 | Rated power | kW | 194 | 291 | 412 | 582 | Power loss at rated DC current | kW | 1.37 | 1.84 | 2.47 | 4.11 | Rated DC field voltage 1) | V | Max. 325 | Max. 390 | Rated DC field current | A | 25 | 30 | 40 | Normal ambient temperature in operation 4) | °C | 0 … +40 | Storage and transport temperature | °C | -40 … +70 | Installation altitude above sea level 4) | | ≤ 1000 m for rated DC current | Dimensions | | mm | 268 | | mm | 625 | 700 | 785 | | mm | 275 | 311 | 435 | Weight, approx. | kg | 26 | 28 | 38 | 78 |
Note: Detailed dimensional drawings in PDF and DXF format are available on the Internet at http://support.automation.siemens.com/WW/view/en/81717045. 1) The armature/field supply voltage may be lower than the rated armature/field voltage (set by parameter). A minimum input voltage of 50 V is permissible for units with a rated voltage of 400 V, 480 V and 575 V, or 85 V for higher rated voltages. The output voltage is reduced accordingly. The specified DC output voltage can be maintained up to an undervoltage of 5 % of the line supply voltage (rated armature/field supply voltage). 2) Fan noise for a unit installed in an IP20 electrical cabinet (door closed, 50 Hz operation or operation at 24 V DC for units with an internal supply). 3) For fan motor type R2D220-AB02-19 in units 6RA8081, 6RA8085, and 6RA8087 with a rated voltage of 400 V or 575 V, UL systems require a Siemens motor circuit breaker of type 3RV1011-0DA1 or 3RV1011-0EA1, set to 0.3 A. 4) For derating factors at higher temperatures and installation altitudes, see „Current derating“. SINAMICS DC MASTER converters for 400 V 3 AC, 1600 to 3000 A, two-quadrant operation | | Type |
|---|
| | | 6RA8093- 4DS22-0AA0 | 6RA8095- 4DS22-0AA0 | 6RA8098- 4DS22-0AA0 |
|---|
Rated armature supply voltage 1) | V | 400 3 AC (+15/-20 %) | 400 3 AC (+10/-20 %) | Rated armature input current | A | 1328 | 1660 | 2490 | Rated supply voltage, electronics power supply | V | 380 (-25 %) … 480 (+10 %) 2 AC; In = 1 A or 190 (-25 %) … 240 (+10 %) 2 AC; In = 2 A | Rated fan supply voltage | V | 400 V 3 AC ± 10 % (50 Hz) 460 V 3 AC ± 10 % (60 Hz) | Rated fan current | A | 1 3) | Cooling air requirement | m3/h | 2400 | Sound pressure level 2) | dB (A) | 75.6 | Rated field supply voltage 1) | V | 480 2 AC (+10/-20 %) | Rated frequency | Hz | 45 … 65 | Rated DC voltage 1) | V | 485 | Rated DC current | A | 1600 | 2000 | 3000 | Overload capability | x × In | 1.8 | Rated power | kW | 776 | 970 | 1455 | Power loss at rated DC current | kW | 5.68 | 6.78 | 10.64 | Rated DC field voltage 1) | V | Max. 390 | Rated DC field current | A | 40 | Normal ambient temperature in operation 4) | °C | 0 … +40 | Storage and transport temperature | °C | -40 … +70 | Installation altitude above sea level 4) | | ≤ 1000 m for rated DC current | Dimensions | | mm | 453 | | mm | 883 | | mm | 505 | Weight, approx. | kg | 135 | 165 |
Note: Detailed dimensional drawings in PDF and DXF format are available on the Internet at http://support.automation.siemens.com/WW/view/en/81717045. 1) The armature/field supply voltage may be lower than the rated armature/field voltage (set by parameter). A minimum input voltage of 50 V is permissible for units with a rated voltage of 400 V, 480 V and 575 V, or 85 V for higher rated voltages. The output voltage is reduced accordingly. The specified DC output voltage can be maintained up to an undervoltage of 5 % of the line supply voltage (rated armature/field supply voltage). 2) Fan noise for a unit installed in an IP20 electrical cabinet (door closed, 50 Hz operation or operation at 24 V DC for units with an internal supply). 3) For fan motor type RH28M-2DK.3F.1R in units 6RA8090, 6RA8091, 6RA8093, and 6RA8095 with a rated voltage of 400 V or 575 V, UL systems require a Siemens motor circuit breaker of type 3RV1011-0KA1 or 3RV1011-1AA1, set to 1.25 A. 4) For derating factors at higher temperatures and installation altitudes, see „Current derating“. SINAMICS DC MASTER converters for 480 V 3 AC, 60 to 280 A, two-quadrant operation | | Type |
|---|
| | | 6RA8025- 6FS22-0AA0 | 6RA8028- 6FS22-0AA0 | 6RA8031- 6FS22-0AA0 | 6RA8075- 6FS22-0AA0 | 6RA8078- 6FS22-0AA0 |
|---|
Rated armature supply voltage 1) | V | 480 3 AC (+10/-20 %) | Rated armature input current | A | 50 | 75 | 104 | 174 | 232 | Rated supply voltage, electronics power supply | V | 380 (-25 %) … 480 (+10 %) 2 AC; In = 1 A or 190 (-25 %) … 240 (+10 %) 2 AC; In = 2 A | Rated fan supply voltage | V | Self-ventilated | 24 V DC internal | Rated fan current | A | Internal supply | Cooling air requirement | m3/h | 300 | Sound pressure level 2) | dB (A) | 52.4 | Rated field supply voltage 1) | V | 480 2 AC (+10/-20 %) | Rated frequency | Hz | 45 … 65 | Rated DC voltage 1) | V | 575 | Rated DC current | A | 60 | 90 | 125 | 210 | 280 | Overload capability | x × In | 1.8 | Rated power | kW | 35 | 52 | 72 | 121 | 161 | Power loss at rated DC current | kW | 0.30 | 0.38 | 0.43 | 0.72 | 0.81 | Rated DC field voltage 1) | V | Max. 390 | Rated DC field current | A | 10 | 15 | Normal ambient temperature in operation 3) | °C | 0 … +45 | 0 … +40 | Storage and transport temperature | °C | -40 … +70 | Installation altitude above sea level 3) | | ≤ 1000 m for rated DC current | Dimensions | | mm | 268 | | mm | 385 | | mm | 252 | Weight, approx. | kg | 11 | 14 | 15 |
Note: Detailed dimensional drawings in PDF and DXF format are available on the Internet at http://support.automation.siemens.com/WW/view/en/81717045. Data for single-phase connection | | Type |
|---|
| | | 6RA8025- 6FS22-0AA0 | 6RA8028- 6FS22-0AA0 | 6RA8031- 6FS22-0AA0 | | |
|---|
Rated DC voltage | V | 385 | | | Rated DC current | A | 42.0 | 63.0 | 87.5 | | |
1) The armature/field supply voltage may be lower than the rated armature/field voltage (set by parameter). A minimum input voltage of 50 V is permissible for units with a rated voltage of 400 V, 480 V and 575 V, or 85 V for higher rated voltages. The output voltage is reduced accordingly. The specified DC output voltage can be maintained up to an undervoltage of 5 % of the line supply voltage (rated armature/field supply voltage). 2) Fan noise for a unit installed in an IP20 electrical cabinet (door closed, 50 Hz operation or operation at 24 V DC for units with an internal supply). 3) For derating factors at higher temperatures and installation altitudes, see „Current derating“. SINAMICS DC MASTER converters for 480 V 3 AC, 450 to 1200 A, two-quadrant operation | | Type |
|---|
| | | 6RA8082- 6FS22-0AA0 | 6RA8085- 6FS22-0AA0 | 6RA8087- 6FS22-0AA0 | 6RA8091- 6FS22-0AA0 |
|---|
Rated armature supply voltage 1) | V | 480 3 AC (+10/-20 %) | Rated armature input current | A | 374 | 498 | 706 | 996 | Rated supply voltage, electronics power supply | V | 380 (-25 %) … 480 (+10 %) 2 AC; In = 1 A or 190 (-25 %) … 240 (+10 %) 2 AC; In = 2 A | Rated fan supply voltage | V | 400 V 3 AC ± 10 % (50 Hz) 460 V 3 AC ± 10 % (60 Hz) | Rated fan current | A | 0.23 3) | 0.3 3) | Cooling air requirement | m3/h | 600 | 1000 | Sound pressure level 2) | dB (A) | 64.5 | Rated field supply voltage 1) | V | 480 2 AC (+10/-20 %) | Rated frequency | Hz | 45 … 65 | Rated DC voltage 1) | V | 575 | Rated DC current | A | 450 | 600 | 850 | 1200 | Overload capability | x × In | 1.8 | Rated power | kW | 259 | 345 | 489 | 690 | Power loss at rated DC current | kW | 1.58 | 1.91 | 2.60 | 4.24 | Rated DC field voltage 1) | V | Max. 390 | Rated DC field current | A | 25 | 30 | 40 | Normal ambient temperature in operation 4) | °C | 0 … +40 | Storage and transport temperature | °C | -40 … +70 | Installation altitude above sea level 4) | | ≤ 1000 m for rated DC current | Dimensions | | mm | 268 | | mm | 625 | 700 | 785 | | mm | 275 | 311 | 435 | Weight, approx. | kg | 28 | 38 | 78 |
Note: Detailed dimensional drawings in PDF and DXF format are available on the Internet at http://support.automation.siemens.com/WW/view/en/81717045. 1) The armature/field supply voltage may be lower than the rated armature/field voltage (set by parameter). A minimum input voltage of 50 V is permissible for units with a rated voltage of 400 V, 480 V and 575 V, or 85 V for higher rated voltages. The output voltage is reduced accordingly. The specified DC output voltage can be maintained up to an undervoltage of 5 % of the line supply voltage (rated armature/field supply voltage). 2) Fan noise for a unit installed in an IP20 electrical cabinet (door closed, 50 Hz operation or operation at 24 V DC for units with an internal supply). 3) For fan motor type R2D220-AB02-19 in units 6RA8081, 6RA8085, and 6RA8087 with a rated voltage of 400 V or 575 V, UL systems require a Siemens motor circuit breaker of type 3RV1011-0DA1 or 3RV1011-0EA1, set to 0.3 A. 4) For derating factors at higher temperatures and installation altitudes, see „Current derating“. SINAMICS DC MASTER converters for 575 V 3 AC, 60 to 800 A, two-quadrant operation | | Type |
|---|
| | | 6RA8025- 6GS22-0AA0 | 6RA8031- 6GS22-0AA0 | 6RA8075- 6GS22-0AA0 | 6RA8081- 6GS22-0AA0 | 6RA8085- 6GS22-0AA0 | 6RA8087- 6GS22-0AA0 |
|---|
Rated armature supply voltage 1) | V | 575 3 AC (+10/-20 %) | Rated armature input current | A | 50 | 104 | 174 | 332 | 498 | 664 | Rated supply voltage, electronics power supply | V | 380 (-25 %) … 480 (+10 %) 2 AC; In = 1 A or 190 (-25 %) … 240 (+10 %) 2 AC; In = 2 A | Rated fan supply voltage | V | Self-ventilated | 24 V DC internal | 400 V 3 AC ± 10 % (50 Hz) 460 V 3 AC ± 10 % (60 Hz) | Rated fan current | A | Internal supply | 0.23 3) | Cooling air requirement | m3/h | 300 | 600 | Sound pressure level 2) | dB (A) | 52.4 | 64.5 | Rated field supply voltage 1) | V | 480 2 AC (+10/-20 %) | Rated frequency | Hz | 45 … 65 | Rated DC voltage 1) | V | 690 | Rated DC current | A | 60 | 125 | 210 | 400 | 600 | 800 | Overload capability | x × In | 1.8 | Rated power | kW | 41 | 86 | 145 | 276 | 414 | 552 | Power loss at rated DC current | kW | 0.27 | 0.46 | 0.74 | 1.60 | 2.00 | 2.69 | Rated DC field voltage 1) | V | Max. 390 | Rated DC field current | A | 10 | 15 | 25 | 30 | Normal ambient temperature in operation 4) | °C | 0 … +45 | 0 … +40 | Storage and transport temperature | °C | -40 … +70 | Installation altitude above sea level 4) | | ≤ 1000 m for rated DC current | Dimensions | | mm | 268 | | mm | 385 | 625 | 700 | | mm | 252 | 275 | 311 | Weight, approx. | kg | 11 | 14 | 26 | 28 | 38 |
Note: Detailed dimensional drawings in PDF and DXF format are available on the Internet at http://support.automation.siemens.com/WW/view/en/81717045. Data for single-phase connection | | Type |
|---|
| | | 6RA8025- 6GS22-0AA0 | 6RA8031- 6GS22-0AA0 | | | | |
|---|
Rated DC voltage | V | 460 | | | | | Rated DC current | A | 42.0 | 87.5 | | | | |
1) The armature/field supply voltage may be lower than the rated armature/field voltage (set by parameter). A minimum input voltage of 50 V is permissible for units with a rated voltage of 400 V, 480 V and 575 V, or 85 V for higher rated voltages. The output voltage is reduced accordingly. The specified DC output voltage can be maintained up to an undervoltage of 5 % of the line supply voltage (rated armature/field supply voltage). 2) Fan noise for a unit installed in an IP20 electrical cabinet (door closed, 50 Hz operation or operation at 24 V DC for units with an internal supply). 3) For fan motor type R2D220-AB02-19 in units 6RA8081, 6RA8085, and 6RA8087 with a rated voltage of 400 V or 575 V, UL systems require a Siemens motor circuit breaker of type 3RV1011-0DA1 or 3RV1011-0EA1, set to 0.3 A. 4) For derating factors at higher temperatures and installation altitudes, see „Current derating“. SINAMICS DC MASTER converters for 575 V 3 AC, 1100 to 2800 A, two-quadrant operation | | Type |
|---|
| | | 6RA8090- 6GS22-0AA0 | 6RA8093- 4GS22-0AA0 | 6RA8095- 4GS22-0AA0 | 6RA8096- 4GS22-0AA0 | 6RA8097- 4GS22-0AA0 |
|---|
Rated armature supply voltage 1) | V | 575 3 AC (+10/-20 %) | Rated armature input current | A | 913 | 1328 | 1660 | 1826 | 2324 | Rated supply voltage, electronics power supply | V | 380 (-25 %) … 480 (+10 %) 2 AC; In = 1 A or 190 (-25 %) … 240 (+10 %) 2 AC; In = 2 A | Rated fan supply voltage | V | 400 V 3 AC ± 10 % (50 Hz) 460 V 3 AC ± 10 % (60 Hz) | Rated fan current | A | 0.3 3) | 1 4) | Cooling air requirement | m3/h | 1000 | 2400 | Sound pressure level 2) | dB (A) | 64.5 | 75.6 | Rated field supply voltage 1) | V | 480 2 AC (+10/-20 %) | Rated frequency | Hz | 45 … 65 | Rated DC voltage 1) | V | 690 | Rated DC current | A | 1100 | 1600 | 2000 | 2200 | 2800 | Overload capability | x × In | 1.8 | Rated power | kW | 759 | 1104 | 1380 | 1518 | 1932 | Power loss at rated DC current | kW | 4.02 | 6.04 | 7.07 | 7.39 | 10.53 | Rated DC field voltage 1) | V | Max. 390 | Rated DC field current | A | 40 | Normal ambient temperature in operation 5) | °C | 0 … +40 | Storage and transport temperature | °C | -40 … +70 | Installation altitude above sea level 5) | | ≤ 1000 m for rated DC current | Dimensions | | mm | 268 | 453 | | mm | 785 | 883 | | mm | 435 | 505 | Weight, approx. | kg | 78 | 135 | 165 |
Note: Detailed dimensional drawings in PDF and DXF format are available on the Internet at http://support.automation.siemens.com/WW/view/en/81717045. 1) The armature/field supply voltage may be lower than the rated armature/field voltage (set by parameter). A minimum input voltage of 50 V is permissible for units with a rated voltage of 400 V, 480 V and 575 V, or 85 V for higher rated voltages. The output voltage is reduced accordingly. The specified DC output voltage can be maintained up to an undervoltage of 5 % of the line supply voltage (rated armature/field supply voltage). 2) Fan noise for a unit installed in an IP20 electrical cabinet (door closed, 50 Hz operation or operation at 24 V DC for units with an internal supply). 3) For fan motor type R2D220-AB02-19 in units 6RA8081, 6RA8085, and 6RA8087 with a rated voltage of 400 V or 575 V, UL systems require a Siemens motor circuit breaker of type 3RV1011-0DA1 or 3RV1011-0EA1, set to 0.3 A. 4) For fan motor type RH28M-2DK.3F.1R in units 6RA8090, 6RA8091, 6RA8093, and 6RA8095 with a rated voltage of 400 V or 575 V, UL systems require a Siemens motor circuit breaker of type 3RV1011-0KA1 or 3RV1011-1AA1, set to 1.25 A. 5) For derating factors at higher temperatures and installation altitudes, see „Current derating“. SINAMICS DC MASTER converters for 690 V 3 AC, 720 to 2600 A, two-quadrant operation | | Type |
|---|
| | | 6RA8086- 6KS22-0AA0 | 6RA8090- 6KS22-0AA0 | 6RA8093- 4KS22-0AA0 | 6RA8095- 4KS22-0AA0 | 6RA8097- 4KS22-0AA0 |
|---|
Rated armature supply voltage 1) | V | 690 3 AC (+10/-20 %) | Rated armature input current | A | 598 | 830 | 1245 | 1660 | 2158 | Rated supply voltage, electronics power supply | V | 380 (-25 %) … 480 (+10 %) 2 AC; In = 1 A or 190 (-25 %) … 240 (+10 %) 2 AC; In = 2 A | Rated fan supply voltage | V | 400 V 3 AC ± 10 % (50 Hz) 460 V 3 AC ± 10 % (60 Hz) | Rated fan current | A | 0.23 3) | 0.3 3) | 1 4) | Cooling air requirement | m3/h | 600 | 1000 | 2400 | Sound pressure level 2) | dB (A) | 64.5 | 75.6 | Rated field supply voltage 1) | V | 480 2 AC (+10/-20 %) | Rated frequency | Hz | 45 … 65 | Rated DC voltage 1) | V | 830 | Rated DC current | A | 720 | 1000 | 1500 | 2000 | 2600 | Overload capability | x × In | 1.8 | Rated power | kW | 598 | 830 | 1245 | 1660 | 2158 | Power loss at rated DC current | kW | 2.77 | 3.96 | 6.67 | 8.16 | 10.30 | Rated DC field voltage 1) | V | Max. 390 | Rated DC field current | A | 30 | 40 | Normal ambient temperature in operation 5) | °C | 0 … +40 | Storage and transport temperature | °C | -40 … +70 | Installation altitude above sea level 5) | | ≤ 1000 m for rated DC current | Dimensions | | mm | 268 | 453 | | mm | 700 | 785 | 883 | | mm | 311 | 435 | 505 | Weight, approx. | kg | 38 | 78 | 135 | 165 |
Note: Detailed dimensional drawings in PDF and DXF format are available on the Internet at http://support.automation.siemens.com/WW/view/en/81717045. 1) The armature/field supply voltage may be lower than the rated armature/field voltage (set by parameter). A minimum input voltage of 50 V is permissible for units with a rated voltage of 400 V, 480 V and 575 V, or 85 V for higher rated voltages. The output voltage is reduced accordingly. The specified DC output voltage can be maintained up to an undervoltage of 5 % of the line supply voltage (rated armature/field supply voltage). 2) Fan noise for a unit installed in an IP20 electrical cabinet (door closed, 50 Hz operation or operation at 24 V DC for units with an internal supply). 3) For fan motor type R2D220-AB02-19 in units 6RA8081, 6RA8085, and 6RA8087 with a rated voltage of 400 V or 575 V, UL systems require a Siemens motor circuit breaker of type 3RV1011-0DA1 or 3RV1011-0EA1, set to 0.3 A. 4) For fan motor type RH28M-2DK.3F.1R in units 6RA8090, 6RA8091, 6RA8093, and 6RA8095 with a rated voltage of 400 V or 575 V, UL systems require a Siemens motor circuit breaker of type 3RV1011-0KA1 or 3RV1011-1AA1, set to 1.25 A. 5) For derating factors at higher temperatures and installation altitudes, see „Current derating“. SINAMICS DC MASTER converters for 830 V 3 AC, 950 to 1900 A and 950 V 3 AC, 2200 A, two-quadrant operation | | Type |
|---|
| | | 6RA8088- 6LS22-0AA0 | 6RA8093- 4LS22-0AA0 | 6RA8095- 4LS22-0AA0 | 6RA8096- 4MS22-0AA0 |
|---|
Rated armature supply voltage 1) | V | 830 3 AC (+10/-20 %) | 950 3 AC (+15/-20 %) | Rated armature input current | A | 789 | 1245 | 1577 | 1826 | Rated supply voltage, electronics power supply | V | 380 (-25 %) … 480 (+10 %) 2 AC; In = 1 A or 190 (-25 %) … 240 (+10 %) 2 AC; In = 2 A | Rated fan supply voltage | V | 400 V 3 AC ± 10 % (50 Hz) 460 V 3 AC ± 10 % (60 Hz) | Rated fan current | A | 0.3 3) | 1 4) | Cooling air requirement | m3/h | 1000 | 2400 | Sound pressure level 2) | dB (A) | 64.5 | 75.6 | Rated field supply voltage 1) | V | 480 2 AC (+10/-20 %) | Rated frequency | Hz | 45 … 65 | Rated DC voltage 1) | V | 1000 | 1140 | Rated DC current | A | 950 | 1500 | 1900 | 2200 | Overload capability | x × In | 1.8 | Rated power | kW | 950 | 1500 | 1900 | 2508 | Power loss at rated DC current | kW | 4.22 | 7.12 | 8.67 | 11.34 | Rated DC field voltage 1) | V | Max. 390 | Rated DC field current | A | 40 | Normal ambient temperature in operation 5) | °C | 0 … +40 | Storage and transport temperature | °C | -40 … +70 | Installation altitude above sea level 5) | | ≤ 1000 m for rated DC current | Dimensions | | mm | 268 | 453 | | mm | 785 | 883 | | mm | 435 | 505 | Weight, approx. | kg | 78 | 135 | 165 |
Note: Detailed dimensional drawings in PDF and DXF format are available on the Internet at http://support.automation.siemens.com/WW/view/en/81717045. 1) The armature/field supply voltage may be lower than the rated armature/field voltage (set by parameter). A minimum input voltage of 50 V is permissible for units with a rated voltage of 400 V, 480 V and 575 V, or 85 V for higher rated voltages. The output voltage is reduced accordingly. The specified DC output voltage can be maintained up to an undervoltage of 5 % of the line supply voltage (rated armature/field supply voltage). 2) Fan noise for a unit installed in an IP20 electrical cabinet (door closed, 50 Hz operation or operation at 24 V DC for units with an internal supply). 3) For fan motor type R2D220-AB02-19 in units 6RA8081, 6RA8085, and 6RA8087 with a rated voltage of 400 V or 575 V, UL systems require a Siemens motor circuit breaker of type 3RV1011-0DA1 or 3RV1011-0EA1, set to 0.3 A. 4) For fan motor type RH28M-2DK.3F.1R in units 6RA8090, 6RA8091, 6RA8093, and 6RA8095 with a rated voltage of 400 V or 575 V, UL systems require a Siemens motor circuit breaker of type 3RV1011-0KA1 or 3RV1011-1AA1, set to 1.25 A. 5) For derating factors at higher temperatures and installation altitudes, see „Current derating“. SINAMICS DC MASTER converters for 400 V 3 AC, 15 to 125 A, four-quadrant operation | | Type |
|---|
| | | 6RA8013- 6DV62-0AA0 | 6RA8018- 6DV62-0AA0 | 6RA8025- 6DV62-0AA0 | 6RA8028- 6DV62-0AA0 | 6RA8031- 6DV62-0AA0 |
|---|
Rated armature supply voltage 1) | V | 400 3 AC (+15/-20 %) | Rated armature input current | A | 12 | 25 | 50 | 75 | 104 | Rated supply voltage, electronics power supply | V | 380 (-25 %) … 480 (+10 %) 2 AC; In = 1 A or 190 (-25 %) … 240 (+10 %) 2 AC; In = 2 A | Rated fan supply voltage | V | Self-ventilated | Rated fan current | A | Cooling air requirement | m3/h | Sound pressure level 2) | dB (A) | Rated field supply voltage 1) | V | 400 2 AC (+15/-20 %) | Rated frequency | Hz | 45 … 65 | Rated DC voltage 1) | V | 420 | Rated DC current | A | 15 | 30 | 60 | 90 | 125 | Overload capability | x × In | 1.8 | Rated power | kW | 6.3 | 12.6 | 25 | 38 | 53 | Power loss at rated DC current | kW | 0.13 | 0.18 | 0.25 | 0.32 | 0.41 | Rated DC field voltage 1) | V | Max. 325 | Rated DC field current | A | 3 | 5 | 10 | Normal ambient temperature in operation 3) | °C | 0 … +45 | Storage and transport temperature | °C | -40 … +70 | Installation altitude above sea level 3) | | ≤ 1000 m for rated DC current | Dimensions | | mm | 268 | | mm | 385 | | mm | 221 | 252 | Weight, approx. | kg | 11 | 14 |
Note: Detailed dimensional drawings in PDF and DXF format are available on the Internet at http://support.automation.siemens.com/WW/view/en/81717045. Data for single-phase connection | | Type |
|---|
| | | 6RA8013- 6DV62-0AA0 | 6RA8018- 6DV62-0AA0 | 6RA8025- 6DV62-0AA0 | 6RA8028- 6DV62-0AA0 | 6RA8031- 6DV62-0AA0 |
|---|
Rated DC voltage | V | 280 | Rated DC current | A | 10.5 | 21.0 | 42.0 | 63.0 | 87.5 |
1) The armature/field supply voltage may be lower than the rated armature/field voltage (set by parameter). A minimum input voltage of 50 V is permissible for units with a rated voltage of 400 V, 480 V and 575 V, or 85 V for higher rated voltages. The output voltage is reduced accordingly. The specified DC output voltage can be maintained up to an undervoltage of 5 % of the line supply voltage (rated armature/field supply voltage). 2) Fan noise for a unit installed in an IP20 electrical cabinet (door closed, 50 Hz operation or operation at 24 V DC for units with an internal supply). 3) For derating factors at higher temperatures and installation altitudes, see „Current derating“. SINAMICS DC MASTER converters for 400 V 3 AC, 210 to 850 A, four-quadrant operation | | Type |
|---|
| | | 6RA8075- 6DV62-0AA0 | 6RA8078- 6DV62-0AA0 | 6RA8081- 6DV62-0AA0 | 6RA8085- 6DV62-0AA0 | 6RA8087- 6DV62-0AA0 |
|---|
Rated armature supply voltage 1) | V | 400 3 AC (+15/-20 %) | Rated armature input current | A | 174 | 232 | 332 | 498 | 706 | Rated supply voltage, electronics power supply | V | 380 (-25 %) … 480 (+10 %) 2 AC; In = 1 A or 190 (-25 %) … 240 (+10 %) 2 AC; In = 2 A | Rated fan supply voltage | V | 24 V DC internal | 400 V 3 AC ± 10 % (50 Hz) 460 V 3 AC ± 10 % (60 Hz) | Rated fan current | A | Internal supply | 0.23 3) | Cooling air requirement | m3/h | 300 | 600 | Sound pressure level 2) | dB (A) | 52.4 | 64.5 | Rated field supply voltage 1) | V | 400 2 AC (+15/-20 %) | Rated frequency | Hz | 45 … 65 | Rated DC voltage 1) | V | 420 | Rated DC current | A | 210 | 280 | 400 | 600 | 850 | Overload capability | x × In | 1.8 | Rated power | kW | 88 | 118 | 168 | 252 | 357 | Power loss at rated DC current | kW | 0.69 | 0.81 | 1.37 | 1.84 | 2.47 | Rated DC field voltage 1) | V | Max. 325 | Rated DC field current | A | 15 | 25 | 30 | Normal ambient temperature in operation 4) | °C | 0 … +40 | Storage and transport temperature | °C | -40 … +70 | Installation altitude above sea level 4) | | ≤ 1000 m for rated DC current | Dimensions | | mm | 268 | | mm | 385 | 625 | 700 | | mm | 252 | 275 | 311 | Weight, approx. | kg | 15 | 26 | 31 | 42 |
Note: Detailed dimensional drawings in PDF and DXF format are available on the Internet at http://support.automation.siemens.com/WW/view/en/81717045. 1) The armature/field supply voltage may be lower than the rated armature/field voltage (set by parameter). A minimum input voltage of 50 V is permissible for units with a rated voltage of 400 V, 480 V and 575 V, or 85 V for higher rated voltages. The output voltage is reduced accordingly. The specified DC output voltage can be maintained up to an undervoltage of 5 % of the line supply voltage (rated armature/field supply voltage). 2) Fan noise for a unit installed in an IP20 electrical cabinet (door closed, 50 Hz operation or operation at 24 V DC for units with an internal supply). 3) For fan motor type R2D220-AB02-19 in units 6RA8081, 6RA8085, and 6RA8087 with a rated voltage of 400 V or 575 V, UL systems require a Siemens motor circuit breaker of type 3RV1011-0DA1 or 3RV1011-0EA1, set to 0.3 A. 4) For derating factors at higher temperatures and installation altitudes, see „Current derating“. SINAMICS DC MASTER converters for 400 V 3 AC, 1200 to 3000 A, four-quadrant operation | | Type |
|---|
| | | 6RA8091- 6DV62-0AA0 | 6RA8093- 4DV62-0AA0 | 6RA8095- 4DV62-0AA0 | 6RA8098- 4DV62-0AA0 |
|---|
Rated armature supply voltage 1) | V | 400 3 AC (+15/-20 %) | 400 3 AC (+10/-20 %) | Rated armature input current | A | 996 | 1328 | 1660 | 2490 | Rated supply voltage, electronics power supply | V | 380 (-25 %) … 480 (+10 %) 2 AC; In = 1 A or 190 (-25 %) … 240 (+10 %) 2 AC; In = 2 A | Rated fan supply voltage | V | 400 V 3 AC ± 10 % (50 Hz) 460 V 3 AC ± 10 % (60 Hz) | Rated fan current | A | 0.3 3) | 1 4) | Cooling air requirement | m3/h | 1000 | 2400 | Sound pressure level 2) | dB (A) | 64.5 | 75.6 | Rated field supply voltage 1) | V | 480 2 AC (+10/-20 %) | Rated frequency | Hz | 45 … 65 | Rated DC voltage 1) | V | 420 | Rated DC current | A | 1200 | 1600 | 2000 | 3000 | Overload capability | x × In | 1.8 | Rated power | kW | 504 | 672 | 840 | 1260 | Power loss at rated DC current | kW | 4.11 | 5.68 | 6.78 | 10.64 | Rated DC field voltage 1) | V | Max. 390 | Rated DC field current | A | 40 | Normal ambient temperature in operation 4) | °C | 0 … +40 | Storage and transport temperature | °C | -40 … +70 | Installation altitude above sea level 4) | | ≤ 1000 m for rated DC current | Dimensions | | mm | 268 | 453 | | mm | 785 | 883 | | mm | 435 | 505 | Weight, approx. | kg | 78 | 155 | 185 |
Note: Detailed dimensional drawings in PDF and DXF format are available on the Internet at http://support.automation.siemens.com/WW/view/en/81717045. 1) The armature/field supply voltage may be lower than the rated armature/field voltage (set by parameter). A minimum input voltage of 50 V is permissible for units with a rated voltage of 400 V, 480 V and 575 V, or 85 V for higher rated voltages. The output voltage is reduced accordingly. The specified DC output voltage can be maintained up to an undervoltage of 5 % of the line supply voltage (rated armature/field supply voltage). 2) Fan noise for a unit installed in an IP20 electrical cabinet (door closed, 50 Hz operation or operation at 24 V DC for units with an internal supply). 3) For fan motor type R2D220-AB02-19 in units 6RA8081, 6RA8085, and 6RA8087 with a rated voltage of 400 V or 575 V, UL systems require a Siemens motor circuit breaker of type 3RV1011-0DA1 or 3RV1011-0EA1, set to 0.3 A. 4) For derating factors at higher temperatures and installation altitudes, see „Current derating“. SINAMICS DC MASTER converters for 480 V 3 AC, 15 to 210 A, four-quadrant operation | | Type |
|---|
| | | 6RA8013- 6FV62-0AA0 | 6RA8018- 6FV62-0AA0 | 6RA8025- 6FV62-0AA0 | 6RA8028- 6FV62-0AA0 | 6RA8031- 6FV62-0AA0 | 6RA8075- 6FV62-0AA0 |
|---|
Rated armature supply voltage 1) | V | 480 3 AC (+15/-20 %) | 480 3 AC (+10/-20 %) | Rated armature input current | A | 12 | 25 | 50 | 75 | 104 | 174 | Rated supply voltage, electronics power supply | V | 380 (-25 %) … 480 (+10 %) 2 AC; In = 1 A or 190 (-25 %) … 240 (+10 %) 2 AC; In = 2 A | Rated fan supply voltage | V | Self-ventilated | 24 V DC internal | Rated fan current | A | Internal supply | Cooling air requirement | m3/h | 300 | Sound pressure level 2) | dB (A) | 52.4 | Rated field supply voltage 1) | V | 480 2 AC (+10/-20 %) | Rated frequency | Hz | 45 … 65 | Rated DC voltage 1) | V | 500 | Rated DC current | A | 15 | 30 | 60 | 90 | 125 | 210 | Overload capability | x × In | 1.8 | Rated power | kW | 6 | 15 | 30 | 45 | 63 | 105 | Power loss at rated DC current | kW | 0.13 | 0.19 | 0.30 | 0.34 | 0.43 | 0.72 | Rated DC field voltage 1) | V | Max. 390 | Rated DC field current | A | 3 | 5 | 10 | 10 | 10 | 15 | Normal ambient temperature in operation 3) | °C | 0 … +45 | 0 … +40 | Storage and transport temperature | °C | -40 … +70 | Installation altitude above sea level 3) | | ≤ 1000 m for rated DC current | Dimensions | | mm | 268 | | mm | 385 | | mm | 221 | 252 | Weight, approx. | kg | 11 | 14 | 15 |
Note: Detailed dimensional drawings in PDF and DXF format are available on the Internet at http://support.automation.siemens.com/WW/view/en/81717045. Data for single-phase connection | | Type |
|---|
| | | 6RA8013- 6FV62-0AA0 | 6RA8018- 6FV62-0AA0 | 6RA8025- 6FV62-0AA0 | 6RA8028- 6FV62-0AA0 | 6RA8031- 6FV62-0AA0 | |
|---|
Rated DC voltage | V | 335 | | Rated DC current | A | 10.5 | 21.0 | 42.0 | 63.0 | 87.5 | |
1) The armature/field supply voltage may be lower than the rated armature/field voltage (set by parameter). A minimum input voltage of 50 V is permissible for units with a rated voltage of 400 V, 480 V and 575 V, or 85 V for higher rated voltages. The output voltage is reduced accordingly. The specified DC output voltage can be maintained up to an undervoltage of 5 % of the line supply voltage (rated armature/field supply voltage). 2) Fan noise for a unit installed in an IP20 electrical cabinet (door closed, 50 Hz operation or operation at 24 V DC for units with an internal supply). 3) For derating factors at higher temperatures and installation altitudes, see „Current derating“. SINAMICS DC MASTER converters for 480 V 3 AC, 280 to 1200 A, four-quadrant operation | | Type |
|---|
| | | 6RA8078- 6FV62-0AA0 | 6RA8082- 6FV62-0AA0 | 6RA8085- 6FV62-0AA0 | 6RA8087- 6FV62-0AA0 | 6RA8091- 6FV62-0AA0 |
|---|
Rated armature supply voltage 1) | V | 480 3 AC (+10/-20 %) | Rated armature input current | A | 232 | 374 | 498 | 706 | 996 | Rated supply voltage, electronics power supply | V | 380 (-25 %) … 480 (+10 %) 2 AC; In = 1 A or 190 (-25 %) … 240 (+10 %) 2 AC; In = 2 A | Rated fan supply voltage | V | 24 V DC internal | 400 V 3 AC ± 10 % (50 Hz) 460 V 3 AC ± 10 % (60 Hz) | Rated fan current | A | Internal supply | 0.23 3) | 0.3 3) | Cooling air requirement | m3/h | 300 | 600 | 1000 | Sound pressure level 2) | dB (A) | 52.4 | 64.5 | Rated field supply voltage 1) | V | 480 2 AC (+10/-20 %) | Rated frequency | Hz | 45 … 65 | Rated DC voltage 1) | V | 500 | Rated DC current | A | 280 | 450 | 600 | 850 | 1200 | Overload capability | x × In | 1.8 | Rated power | kW | 140 | 225 | 300 | 425 | 600 | Power loss at rated DC current | kW | 0.81 | 1.58 | 1.91 | 2.60 | 4.24 | Rated DC field voltage 1) | V | Max. 390 | Rated DC field current | A | 15 | 25 | 25 | 30 | 40 | Normal ambient temperature in operation 4) | °C | 0 … +40 | Storage and transport temperature | °C | -40 … +70 | Installation altitude above sea level 4) | | ≤ 1000 m for rated DC current | Dimensions | | mm | 268 | | mm | 385 | 625 | 700 | 785 | | mm | 252 | 275 | 311 | 435 | Weight, approx. | kg | 15 | 31 | 42 | 78 |
Note: Detailed dimensional drawings in PDF and DXF format are available on the Internet at http://support.automation.siemens.com/WW/view/en/81717045. 1) The armature/field supply voltage may be lower than the rated armature/field voltage (set by parameter). A minimum input voltage of 50 V is permissible for units with a rated voltage of 400 V, 480 V and 575 V, or 85 V for higher rated voltages. The output voltage is reduced accordingly. The specified DC output voltage can be maintained up to an undervoltage of 5 % of the line supply voltage (rated armature/field supply voltage). 2) Fan noise for a unit installed in an IP20 electrical cabinet (door closed, 50 Hz operation or operation at 24 V DC for units with an internal supply). 3) For fan motor type R2D220-AB02-19 in units 6RA8081, 6RA8085, and 6RA8087 with a rated voltage of 400 V or 575 V, UL systems require a Siemens motor circuit breaker of type 3RV1011-0DA1 or 3RV1011-0EA1, set to 0.3 A. 4) For derating factors at higher temperatures and installation altitudes, see „Current derating“. SINAMICS DC MASTER converters for 575 V 3 AC, 60 to 850 A, four-quadrant operation | | Type |
|---|
| | | 6RA8025- 6GV62-0AA0 | 6RA8031- 6GV62-0AA0 | 6RA8075- 6GV62-0AA0 | 6RA8081- 6GV62-0AA0 | 6RA8085- 6GV62-0AA0 | 6RA8087- 6GV62-0AA0 |
|---|
Rated armature supply voltage 1) | V | 575 3 AC (+10/-20 %) | Rated armature input current | A | 50 | 104 | 174 | 332 | 498 | 706 | Rated supply voltage, electronics power supply | V | 380 (-25 %) … 480 (+10 %) 2 AC; In = 1 A or 190 (-25 %) … 240 (+10 %) 2 AC; In = 2 A | Rated fan supply voltage | V | Self-ventilated | 24 V DC internal | 400 V 3 AC ± 10 % (50 Hz) 460 V 3 AC ± 10 % (60 Hz) | Rated fan current | A | Internal supply | 0.23 3) | Cooling air requirement | m3/h | 300 | 600 | Sound pressure level 2) | dB (A) | 52.4 | 64.5 | Rated field supply voltage 1) | V | 480 2 AC (+10/-20 %) | Rated frequency | Hz | 45 … 65 | Rated DC voltage 1) | V | 600 | Rated DC current | A | 60 | 125 | 210 | 400 | 600 | 850 | Overload capability | x × In | 1.8 | Rated power | kW | 36 | 75 | 126 | 240 | 360 | 510 | Power loss at rated DC current | kW | 0.27 | 0.46 | 0.74 | 1.60 | 2.00 | 2.83 | Rated DC field voltage 1) | V | Max. 390 | Rated DC field current | A | 10 | 10 | 15 | 25 | 25 | 30 | Normal ambient temperature in operation 4) | °C | 0 … +45 | 0 … +40 | Storage and transport temperature | °C | -40 … +70 | Installation altitude above sea level 4) | | ≤ 1000 m for rated DC current | Dimensions | | mm | 268 | | mm | 385 | 65 | 700 | | mm | 252 | 275 | 311 | Weight, approx. | kg | 11 | 14 | 15 | 26 | 31 | 42 |
Note: Detailed dimensional drawings in PDF and DXF format are available on the Internet at http://support.automation.siemens.com/WW/view/en/81717045. Data for single-phase connection | | Type |
|---|
| | | 6RA8025- 6GV62-0AA0 | 6RA8031- 6GV62-0AA0 | | | | |
|---|
Rated DC voltage | V | 400 | | | | | Rated DC current | A | 42.0 | 87.5 | | | | |
1) The armature/field supply voltage may be lower than the rated armature/field voltage (set by parameter). A minimum input voltage of 50 V is permissible for units with a rated voltage of 400 V, 480 V and 575 V, or 85 V for higher rated voltages. The output voltage is reduced accordingly. The specified DC output voltage can be maintained up to an undervoltage of 5 % of the line supply voltage (rated armature/field supply voltage). 2) Fan noise for a unit installed in an IP20 electrical cabinet (door closed, 50 Hz operation or operation at 24 V DC for units with an internal supply). 3) For fan motor type R2D220-AB02-19 in units 6RA8081, 6RA8085, and 6RA8087 with a rated voltage of 400 V or 575 V, UL systems require a Siemens motor circuit breaker of type 3RV1011-0DA1 or 3RV1011-0EA1, set to 0.3 A. 4) For derating factors at higher temperatures and installation altitudes, see „Current derating“. SINAMICS DC MASTER converters for 575 V 3 AC, 1100 to 2800 A, four-quadrant operation | | Type |
|---|
| | | 6RA8090- 6GV62-0AA0 | 6RA8093- 4GV62-0AA0 | 6RA8095- 4GV62-0AA0 | 6RA8096- 4GV62-0AA0 | 6RA8097- 4GV62-0AA0 |
|---|
Rated armature supply voltage 1) | V | 575 3 AC (+10/-20 %) | Rated armature input current | A | 913 | 1328 | 1660 | 1826 | 2324 | Rated supply voltage, electronics power supply | V | 380 (-25 %) … 480 (+10 %) 2 AC; In = 1 A or 190 (-25 %) … 240 (+10 %) 2 AC; In = 2 A | Rated fan supply voltage | V | 400 V 3 AC ± 10 % (50 Hz) 460 V 3 AC ± 10 % (60 Hz) | Rated fan current | A | 0.3 3) | 1 4) | Cooling air requirement | m3/h | 1000 | 2400 | Sound pressure level 2) | dB (A) | 64.5 | 75.6 | Rated field supply voltage 1) | V | 480 2 AC (+10/-20 %) | Rated frequency | Hz | 45 … 65 | Rated DC voltage 1) | V | 600 | Rated DC current | A | 1100 | 1600 | 2000 | 2200 | 2800 | Overload capability | x × In | 1.8 | Rated power | kW | 660 | 960 | 1200 | 1320 | 1680 | Power loss at rated DC current | kW | 4.02 | 6.04 | 7.07 | 7.39 | 10.53 | Rated DC field voltage 1) | V | Max. 390 | Rated DC field current | A | 40 | Normal ambient temperature in operation 5) | °C | 0 … +40 | Storage and transport temperature | °C | -40 … +70 | Installation altitude above sea level 5) | | ≤ 1000 m for rated DC current | Dimensions | | mm | 268 | 453 | | mm | 785 | 883 | | mm | 435 | 505 | Weight, approx. | kg | 78 | 155 | 185 |
Note: Detailed dimensional drawings in PDF and DXF format are available on the Internet at http://support.automation.siemens.com/WW/view/en/81717045. 1) The armature/field supply voltage may be lower than the rated armature/field voltage (set by parameter). A minimum input voltage of 50 V is permissible for units with a rated voltage of 400 V, 480 V and 575 V, or 85 V for higher rated voltages. The output voltage is reduced accordingly. The specified DC output voltage can be maintained up to an undervoltage of 5 % of the line supply voltage (rated armature/field supply voltage). 2) Fan noise for a unit installed in an IP20 electrical cabinet (door closed, 50 Hz operation or operation at 24 V DC for units with an internal supply). 3) For fan motor type R2D220-AB02-19 in units 6RA8081, 6RA8085, and 6RA8087 with a rated voltage of 400 V or 575 V, UL systems require a Siemens motor circuit breaker of type 3RV1011-0DA1 or 3RV1011-0EA1, set to 0.3 A. 4) For fan motor type RH28M-2DK.3F.1R in units 6RA8090, 6RA8091, 6RA8093, and 6RA8095 with a rated voltage of 400 V or 575 V, UL systems require a Siemens motor circuit breaker of type 3RV1011-0KA1 or 3RV1011-1AA1, set to 1.25 A. 5) For derating factors at higher temperatures and installation altitudes, see „Current derating“. SINAMICS DC MASTER converters for 690 V 3 AC, 760 to 2600 A, four-quadrant operation | | Type |
|---|
| | 6RA8086- 6KV62-0AA0 | 6RA8090- 6KV62-0AA0 | 6RA8093- 4KV62-0AA0 | 6RA8095- 4KV62-0AA0 | 6RA8097- 4KV62-0AA0 |
|---|
Rated armature supply voltage 1) | V | 690 3 AC (+10/-20 %) | Rated armature input current | A | 631 | 830 | 1245 | 1660 | 2158 | Rated supply voltage, electronics power supply | V | 380 (-25 %) … 480 (+10 %) 2 AC; In = 1 A or 190 (-25 %) … 240 (+10 %) 2 AC; In = 2 A | Rated fan supply voltage | V | 400 V 3 AC ± 10 % (50 Hz) 460 V 3 AC ± 10 % (60 Hz) | Rated fan current | A | 0.23 3) | 0.3 3) | 1 4) | Cooling air requirement | m3/h | 600 | 1000 | 2400 | Sound pressure level 2) | dB (A) | 64.5 | 75.6 | Rated field supply voltage 1) | V | 480 2 AC (+10/-20 %) | Rated frequency | Hz | 45 … 65 | Rated DC voltage 1) | V | 725 | Rated DC current | A | 760 | 1000 | 1500 | 2000 | 2600 | Overload capability | x × In | 1.8 | Rated power | kW | 551 | 725 | 1088 | 1450 | 1885 | Power loss at rated DC current | kW | 2.90 | 3.96 | 6.67 | 8.16 | 10.30 | Rated DC field voltage 1) | V | Max. 390 | Rated DC field current | A | 30 | 40 | Normal ambient temperature in operation 5) | °C | 0 … +40 | Storage and transport temperature | °C | -40 … +70 | Installation altitude above sea level 5) | | ≤ 1000 m for rated DC current | Dimensions | | mm | 268 | 453 | | mm | 700 | 785 | 883 | | mm | 311 | 435 | 505 | Weight, approx. | kg | 42 | 78 | 155 | 185 |
Note: Detailed dimensional drawings in PDF and DXF format are available on the Internet at http://support.automation.siemens.com/WW/view/en/81717045. 1) The armature/field supply voltage may be lower than the rated armature/field voltage (set by parameter). A minimum input voltage of 50 V is permissible for units with a rated voltage of 400 V, 480 V and 575 V, or 85 V for higher rated voltages. The output voltage is reduced accordingly. The specified DC output voltage can be maintained up to an undervoltage of 5 % of the line supply voltage (rated armature/field supply voltage). 2) Fan noise for a unit installed in an IP20 electrical cabinet (door closed, 50 Hz operation or operation at 24 V DC for units with an internal supply). 3) For fan motor type R2D220-AB02-19 in units 6RA8081, 6RA8085, and 6RA8087 with a rated voltage of 400 V or 575 V, UL systems require a Siemens motor circuit breaker of type 3RV1011-0DA1 or 3RV1011-0EA1, set to 0.3 A. 4) For fan motor type RH28M-2DK.3F.1R in units 6RA8090, 6RA8091, 6RA8093, and 6RA8095 with a rated voltage of 400 V or 575 V, UL systems require a Siemens motor circuit breaker of type 3RV1011-0KA1 or 3RV1011-1AA1, set to 1.25 A. 5) For derating factors at higher temperatures and installation altitudes, see „Current derating“. SINAMICS DC MASTER converters for 830 V 3 AC, 950 to 1900 A and 950 V 3 AC, 2200 A, four-quadrant operation | | Type |
|---|
| | 6RA8088- 6LV62-0AA0 | 6RA8093- 4LV62-0AA0 | 6RA8095- 4LV62-0AA0 | 6RA8096- 4MV62-0AA0 |
|---|
Rated armature supply voltage 1) | V | 830 3 AC (+10/-20 %) | 950 3 AC (+15/-20 %) | Rated armature input current | A | 789 | 1245 | 1577 | 1826 | Rated supply voltage, electronics power supply | V | 380 (-25 %) … 480 (+10 %) 2 AC; In = 1 A or 190 (-25 %) … 240 (+10 %) 2 AC; In = 2 A | Rated fan supply voltage | V | 400 V 3 AC ± 10 % (50 Hz) 460 V 3 AC ± 10 % (60 Hz) | Rated fan current | A | 0.3 3) | 1 4) | Cooling air requirement | m3/h | 1000 | 2400 | Sound pressure level 2) | dB (A) | 64.5 | 75.6 | Rated field supply voltage 1) | V | 480 2 AC (+10/-20 %) | Rated frequency | Hz | 45 … 65 | Rated DC voltage 1) | V | 875 | 1000 | Rated DC current | A | 950 | 1500 | 1900 | 2200 | Overload capability | x × In | 1.8 | Rated power | kW | 831 | 1313 | 1663 | 2200 | Power loss at rated DC current | kW | 4.22 | 7.12 | 8.67 | 11.34 | Rated DC field voltage 1) | V | Max. 390 | Rated DC field current | A | 40 | Normal ambient temperature in operation 5) | °C | 0 … +40 | Storage and transport temperature | °C | -40 … +70 | Installation altitude above sea level 5) | | ≤ 1000 m for rated DC current | Dimensions | | mm | 268 | 453 | | mm | 785 | 883 | | mm | 435 | 505 | Weight, approx. | kg | 78 | 155 | 185 |
Note: Detailed dimensional drawings in PDF and DXF format are available on the Internet at http://support.automation.siemens.com/WW/view/en/81717045. 1) The armature/field supply voltage may be lower than the rated armature/field voltage (set by parameter). A minimum input voltage of 50 V is permissible for units with a rated voltage of 400 V, 480 V and 575 V, or 85 V for higher rated voltages. The output voltage is reduced accordingly. The specified DC output voltage can be maintained up to an undervoltage of 5 % of the line supply voltage (rated armature/field supply voltage). 2) Fan noise for a unit installed in an IP20 electrical cabinet (door closed, 50 Hz operation or operation at 24 V DC for units with an internal supply). 3) For fan motor type R2D220-AB02-19 in units 6RA8081, 6RA8085, and 6RA8087 with a rated voltage of 400 V or 575 V, UL systems require a Siemens motor circuit breaker of type 3RV1011-0DA1 or 3RV1011-0EA1, set to 0.3 A. 4) For fan motor type RH28M-2DK.3F.1R in units 6RA8090, 6RA8091, 6RA8093, and 6RA8095 with a rated voltage of 400 V or 575 V, UL systems require a Siemens motor circuit breaker of type 3RV1011-0KA1 or 3RV1011-1AA1, set to 1.25 A. 5) For derating factors at higher temperatures and installation altitudes, see „Current derating“.
|