Electronic equipment for use in power installations
EN 50274
Low-voltage switchgear and controlgear assemblies: Protection against electric shock – Protection against unintentional direct contact with hazardous live parts
EN 60146-1-1
Semiconductor converters: General requirements and line-commutated converters; specification of basic requirements
EN 61800-1
Adjustable speed electrical power drive systems, Part 1 – (DC drives) General requirements – Rating specifications for low voltage adjustable speed DC power drive systems
EN 61800-3
Adjustable speed electrical power drive systems, Part 3 – EMC product standard including specific test methods
EN 61800-5-1
Adjustable speed electrical power drive systems – Part 5-1: Requirements regarding safety – electrical, thermal, and energy requirements
IEC 62103 (identical to EN 50178)
Electronic equipment for use in power installations
UBC 97
Uniform Building Code
Electrical specifications
Overvoltage category
Category II acc. to EN 61800-5-1 within the line supply circuits Category III acc. to EN 61800-5-1 for line supply circuits with respect to the environment (other line supply circuits, housing, electronics)
Overvoltage strength
Class 1 acc. to EN 50178
Short-circuit current
Rated supply voltage
Rated DC current
Short-circuit current, max.
V
A
kA
400, 480 3 AC
15 ... 1200
65
1600, 2000
85
3000
100
575, 690, 830, 950 3 AC
60 ... 850
65
950 ... 1600
85
1900 ... 2800
100
Radio interference suppression
No radio interference suppression according to EN 61800-3
Mechanical data
Degree of protection
IP00 acc. to EN 60529; IP20 with accessories "Mounting kit to upgrade to IP20" for units up to 850 A
Protection class
Class 1 acc. to EN 61140
Cooling method
Units ? 125 A rated DC current: Permissible ambient temperature in operation
Self-ventilated 0 ... 45 °C - for higher ambient temperature, refer to current derating
Units ? 210 A rated DC current: Permissible ambient temperature in operation
Forced-air cooling with integrated fan 0 ... 40 °C - for higher ambient temperature, refer to current derating
Closed-loop control stability
for pulse encoder operation and digital setpoint
?n = 0.006 % of the rated motor speed
for analog tachometer and analog setpoint 1)
?n = 0.1 % of the rated motor speed
MTBF
> 170000 h
Environmental conditions
Permissible ambient temperature during storage and transport
-40 ... +70 °C
Permissible humidity
Relative air humidity ? 95 % (75 % at 17 °C as average annual value, 95 % at 24 °C max., condensation not permissible)
Climate class
3K3 acc. to EN 60721-3-3
Insulation
Pollution degree 2 according to EN 61800-5-1 Condensation not permissible
Installation altitude
? 1000 m above sea level (100 % load capability) > 1000 ... 5000 m above sea level (see under "Coolant temperature and installation altitude")
Mechanical strength
Storage
Transport
Operation
Vibratory load
1M2 acc. to EN 60721-3-1 (dropping not permissible)
2M2 acc. to EN 60721-3-2 (dropping not permissible)
Constant deflection: 0.075 mm at 10 to 58 Hz Constant acceleration: 10 m/s2 at > 58 to 200 Hz (testing and measuring techniques acc. to EN 60068-2-6, Fc)
Shock load
100 m/s2 at 11 ms (testing and measuring techniques acc. to EN 60068-2-27, Ea)
Approvals
UL/cUL
UL file No.: E203250
UL 508 C (UL Standard for Power Conversion Equipment)
Certification of the units up to and including 575 V
GOST
Lloyd?s Register
In order to maintain the important limit values for marine certification, radio interference suppression filters should be used (see "Accessories and supplementary components") and option M08 (coated PCBs) should be selected.
Det Norske Veritas
American Bureau of Shipping
Germanischer Lloyd
1)Conditions: The closed-loop control (PI control) stability is referred to the rated motor speed and applies when the SINAMICS DC MASTER is in the warm operating condition. This is based on the following preconditions: - Temperature changes of ±10 °C - Line supply voltage changes of +10 % / -5 % of the rated input voltage - Temperature coefficient of the tachometer generator with temperature compensation 0.15 ‰ every 10 °C (for analog tachometer generators only) - Constant setpoint
SINAMICS DC MASTER converters for 400 V 3 AC, 60 to 280 A, two-quadrant operation
Type
6RA8025- 6DS22-0AA0
6RA8028- 6DS22-0AA0
6RA8031- 6DS22-0AA0
6RA8075- 6DS22-0AA0
6RA8078- 6DS22-0AA0
Rated armature supply voltage 1)
V
400 3 AC (+15/-20 %)
Rated armature input current
A
50
75
104
174
232
Rated supply voltage, electronics power supply
V
380 (-25 %) … 480 (+10 %) 2 AC; In = 1 A or 190 (-25 %) … 240 (+10 %) 2 AC; In = 2 A
1) The armature/field supply voltage may be lower than the rated armature/field voltage (set by parameter). A minimum input voltage of 50 V is permissible for units with a rated voltage of 400 V, 480 V and 575 V, or 85 V for higher rated voltages. The output voltage is reduced accordingly. The specified DC output voltage can be maintained up to an undervoltage of 5 % of the line supply voltage (rated armature/field supply voltage).
2) Fan noise for a unit installed in an IP20 electrical cabinet (door closed, 50 Hz operation or operation at 24 V DC for units with an internal supply).
3) For derating factors at higher temperatures and installation altitudes, see „Current derating“.
SINAMICS DC MASTER converters for 400 V 3 AC, 400 to 1200 A, two-quadrant operation
Type
6RA8081- 6DS22-0AA0
6RA8085- 6DS22-0AA0
6RA8087- 6DS22-0AA0
6RA8091- 6DS22-0AA0
Rated armature supply voltage 1)
V
400 3 AC (+15/-20 %)
Rated armature input current
A
332
498
706
996
Rated supply voltage, electronics power supply
V
380 (-25 %) … 480 (+10 %) 2 AC; In = 1 A or 190 (-25 %) … 240 (+10 %) 2 AC; In = 2 A
Rated fan supply voltage
V
400 V 3 AC ± 10 % (50 Hz) 460 V 3 AC ± 10 % (60 Hz)
1) The armature/field supply voltage may be lower than the rated armature/field voltage (set by parameter). A minimum input voltage of 50 V is permissible for units with a rated voltage of 400 V, 480 V and 575 V, or 85 V for higher rated voltages. The output voltage is reduced accordingly. The specified DC output voltage can be maintained up to an undervoltage of 5 % of the line supply voltage (rated armature/field supply voltage).
2) Fan noise for a unit installed in an IP20 electrical cabinet (door closed, 50 Hz operation or operation at 24 V DC for units with an internal supply).
3) For fan motor type R2D220-AB02-19 in units 6RA8081, 6RA8085, and 6RA8087 with a rated voltage of 400 V or 575 V, UL systems require a Siemens motor circuit breaker of type 3RV1011-0DA1 or 3RV1011-0EA1, set to 0.3 A.
4) For derating factors at higher temperatures and installation altitudes, see „Current derating“.
SINAMICS DC MASTER converters for 400 V 3 AC, 1600 to 3000 A, two-quadrant operation
Type
6RA8093- 4DS22-0AA0
6RA8095- 4DS22-0AA0
6RA8098- 4DS22-0AA0
Rated armature supply voltage 1)
V
400 3 AC (+15/-20 %)
400 3 AC (+10/-20 %)
Rated armature input current
A
1328
1660
2490
Rated supply voltage, electronics power supply
V
380 (-25 %) … 480 (+10 %) 2 AC; In = 1 A or 190 (-25 %) … 240 (+10 %) 2 AC; In = 2 A
Rated fan supply voltage
V
400 V 3 AC ± 10 % (50 Hz) 460 V 3 AC ± 10 % (60 Hz)
1) The armature/field supply voltage may be lower than the rated armature/field voltage (set by parameter). A minimum input voltage of 50 V is permissible for units with a rated voltage of 400 V, 480 V and 575 V, or 85 V for higher rated voltages. The output voltage is reduced accordingly. The specified DC output voltage can be maintained up to an undervoltage of 5 % of the line supply voltage (rated armature/field supply voltage).
2) Fan noise for a unit installed in an IP20 electrical cabinet (door closed, 50 Hz operation or operation at 24 V DC for units with an internal supply).
3) For fan motor type RH28M-2DK.3F.1R in units 6RA8090, 6RA8091, 6RA8093, and 6RA8095 with a rated voltage of 400 V or 575 V, UL systems require a Siemens motor circuit breaker of type 3RV1011-0KA1 or 3RV1011-1AA1, set to 1.25 A.
4) For derating factors at higher temperatures and installation altitudes, see „Current derating“.
SINAMICS DC MASTER converters for 480 V 3 AC, 60 to 280 A, two-quadrant operation
Type
6RA8025- 6FS22-0AA0
6RA8028- 6FS22-0AA0
6RA8031- 6FS22-0AA0
6RA8075- 6FS22-0AA0
6RA8078- 6FS22-0AA0
Rated armature supply voltage 1)
V
480 3 AC (+10/-20 %)
Rated armature input current
A
50
75
104
174
232
Rated supply voltage, electronics power supply
V
380 (-25 %) … 480 (+10 %) 2 AC; In = 1 A or 190 (-25 %) … 240 (+10 %) 2 AC; In = 2 A
1) The armature/field supply voltage may be lower than the rated armature/field voltage (set by parameter). A minimum input voltage of 50 V is permissible for units with a rated voltage of 400 V, 480 V and 575 V, or 85 V for higher rated voltages. The output voltage is reduced accordingly. The specified DC output voltage can be maintained up to an undervoltage of 5 % of the line supply voltage (rated armature/field supply voltage).
2) Fan noise for a unit installed in an IP20 electrical cabinet (door closed, 50 Hz operation or operation at 24 V DC for units with an internal supply).
3) For derating factors at higher temperatures and installation altitudes, see „Current derating“.
SINAMICS DC MASTER converters for 480 V 3 AC, 450 to 1200 A, two-quadrant operation
Type
6RA8082- 6FS22-0AA0
6RA8085- 6FS22-0AA0
6RA8087- 6FS22-0AA0
6RA8091- 6FS22-0AA0
Rated armature supply voltage 1)
V
480 3 AC (+10/-20 %)
Rated armature input current
A
374
498
706
996
Rated supply voltage, electronics power supply
V
380 (-25 %) … 480 (+10 %) 2 AC; In = 1 A or 190 (-25 %) … 240 (+10 %) 2 AC; In = 2 A
Rated fan supply voltage
V
400 V 3 AC ± 10 % (50 Hz) 460 V 3 AC ± 10 % (60 Hz)
1) The armature/field supply voltage may be lower than the rated armature/field voltage (set by parameter). A minimum input voltage of 50 V is permissible for units with a rated voltage of 400 V, 480 V and 575 V, or 85 V for higher rated voltages. The output voltage is reduced accordingly. The specified DC output voltage can be maintained up to an undervoltage of 5 % of the line supply voltage (rated armature/field supply voltage).
2) Fan noise for a unit installed in an IP20 electrical cabinet (door closed, 50 Hz operation or operation at 24 V DC for units with an internal supply).
3) For fan motor type R2D220-AB02-19 in units 6RA8081, 6RA8085, and 6RA8087 with a rated voltage of 400 V or 575 V, UL systems require a Siemens motor circuit breaker of type 3RV1011-0DA1 or 3RV1011-0EA1, set to 0.3 A.
4) For derating factors at higher temperatures and installation altitudes, see „Current derating“.
SINAMICS DC MASTER converters for 575 V 3 AC, 60 to 800 A, two-quadrant operation
Type
6RA8025- 6GS22-0AA0
6RA8031- 6GS22-0AA0
6RA8075- 6GS22-0AA0
6RA8081- 6GS22-0AA0
6RA8085- 6GS22-0AA0
6RA8087- 6GS22-0AA0
Rated armature supply voltage 1)
V
575 3 AC (+10/-20 %)
Rated armature input current
A
50
104
174
332
498
664
Rated supply voltage, electronics power supply
V
380 (-25 %) … 480 (+10 %) 2 AC; In = 1 A or 190 (-25 %) … 240 (+10 %) 2 AC; In = 2 A
Rated fan supply voltage
V
Self-ventilated
24 V DC internal
400 V 3 AC ± 10 % (50 Hz) 460 V 3 AC ± 10 % (60 Hz)
1) The armature/field supply voltage may be lower than the rated armature/field voltage (set by parameter). A minimum input voltage of 50 V is permissible for units with a rated voltage of 400 V, 480 V and 575 V, or 85 V for higher rated voltages. The output voltage is reduced accordingly. The specified DC output voltage can be maintained up to an undervoltage of 5 % of the line supply voltage (rated armature/field supply voltage).
2) Fan noise for a unit installed in an IP20 electrical cabinet (door closed, 50 Hz operation or operation at 24 V DC for units with an internal supply).
3) For fan motor type R2D220-AB02-19 in units 6RA8081, 6RA8085, and 6RA8087 with a rated voltage of 400 V or 575 V, UL systems require a Siemens motor circuit breaker of type 3RV1011-0DA1 or 3RV1011-0EA1, set to 0.3 A.
4) For derating factors at higher temperatures and installation altitudes, see „Current derating“.
SINAMICS DC MASTER converters for 575 V 3 AC, 1100 to 2800 A, two-quadrant operation
Type
6RA8090- 6GS22-0AA0
6RA8093- 4GS22-0AA0
6RA8095- 4GS22-0AA0
6RA8096- 4GS22-0AA0
6RA8097- 4GS22-0AA0
Rated armature supply voltage 1)
V
575 3 AC (+10/-20 %)
Rated armature input current
A
913
1328
1660
1826
2324
Rated supply voltage, electronics power supply
V
380 (-25 %) … 480 (+10 %) 2 AC; In = 1 A or 190 (-25 %) … 240 (+10 %) 2 AC; In = 2 A
Rated fan supply voltage
V
400 V 3 AC ± 10 % (50 Hz) 460 V 3 AC ± 10 % (60 Hz)
1) The armature/field supply voltage may be lower than the rated armature/field voltage (set by parameter). A minimum input voltage of 50 V is permissible for units with a rated voltage of 400 V, 480 V and 575 V, or 85 V for higher rated voltages. The output voltage is reduced accordingly. The specified DC output voltage can be maintained up to an undervoltage of 5 % of the line supply voltage (rated armature/field supply voltage).
2) Fan noise for a unit installed in an IP20 electrical cabinet (door closed, 50 Hz operation or operation at 24 V DC for units with an internal supply).
3) For fan motor type R2D220-AB02-19 in units 6RA8081, 6RA8085, and 6RA8087 with a rated voltage of 400 V or 575 V, UL systems require a Siemens motor circuit breaker of type 3RV1011-0DA1 or 3RV1011-0EA1, set to 0.3 A.
4) For fan motor type RH28M-2DK.3F.1R in units 6RA8090, 6RA8091, 6RA8093, and 6RA8095 with a rated voltage of 400 V or 575 V, UL systems require a Siemens motor circuit breaker of type 3RV1011-0KA1 or 3RV1011-1AA1, set to 1.25 A.
5) For derating factors at higher temperatures and installation altitudes, see „Current derating“.
SINAMICS DC MASTER converters for 690 V 3 AC, 720 to 2600 A, two-quadrant operation
Type
6RA8086- 6KS22-0AA0
6RA8090- 6KS22-0AA0
6RA8093- 4KS22-0AA0
6RA8095- 4KS22-0AA0
6RA8097- 4KS22-0AA0
Rated armature supply voltage 1)
V
690 3 AC (+10/-20 %)
Rated armature input current
A
598
830
1245
1660
2158
Rated supply voltage, electronics power supply
V
380 (-25 %) … 480 (+10 %) 2 AC; In = 1 A or 190 (-25 %) … 240 (+10 %) 2 AC; In = 2 A
Rated fan supply voltage
V
400 V 3 AC ± 10 % (50 Hz) 460 V 3 AC ± 10 % (60 Hz)
1) The armature/field supply voltage may be lower than the rated armature/field voltage (set by parameter). A minimum input voltage of 50 V is permissible for units with a rated voltage of 400 V, 480 V and 575 V, or 85 V for higher rated voltages. The output voltage is reduced accordingly. The specified DC output voltage can be maintained up to an undervoltage of 5 % of the line supply voltage (rated armature/field supply voltage).
2) Fan noise for a unit installed in an IP20 electrical cabinet (door closed, 50 Hz operation or operation at 24 V DC for units with an internal supply).
3) For fan motor type R2D220-AB02-19 in units 6RA8081, 6RA8085, and 6RA8087 with a rated voltage of 400 V or 575 V, UL systems require a Siemens motor circuit breaker of type 3RV1011-0DA1 or 3RV1011-0EA1, set to 0.3 A.
4) For fan motor type RH28M-2DK.3F.1R in units 6RA8090, 6RA8091, 6RA8093, and 6RA8095 with a rated voltage of 400 V or 575 V, UL systems require a Siemens motor circuit breaker of type 3RV1011-0KA1 or 3RV1011-1AA1, set to 1.25 A.
5) For derating factors at higher temperatures and installation altitudes, see „Current derating“.
SINAMICS DC MASTER converters for 830 V 3 AC, 950 to 1900 A and 950 V 3 AC, 2200 A, two-quadrant operation
Type
6RA8088- 6LS22-0AA0
6RA8093- 4LS22-0AA0
6RA8095- 4LS22-0AA0
6RA8096- 4MS22-0AA0
Rated armature supply voltage 1)
V
830 3 AC (+10/-20 %)
950 3 AC (+15/-20 %)
Rated armature input current
A
789
1245
1577
1826
Rated supply voltage, electronics power supply
V
380 (-25 %) … 480 (+10 %) 2 AC; In = 1 A or 190 (-25 %) … 240 (+10 %) 2 AC; In = 2 A
Rated fan supply voltage
V
400 V 3 AC ± 10 % (50 Hz) 460 V 3 AC ± 10 % (60 Hz)
1) The armature/field supply voltage may be lower than the rated armature/field voltage (set by parameter). A minimum input voltage of 50 V is permissible for units with a rated voltage of 400 V, 480 V and 575 V, or 85 V for higher rated voltages. The output voltage is reduced accordingly. The specified DC output voltage can be maintained up to an undervoltage of 5 % of the line supply voltage (rated armature/field supply voltage).
2) Fan noise for a unit installed in an IP20 electrical cabinet (door closed, 50 Hz operation or operation at 24 V DC for units with an internal supply).
3) For fan motor type R2D220-AB02-19 in units 6RA8081, 6RA8085, and 6RA8087 with a rated voltage of 400 V or 575 V, UL systems require a Siemens motor circuit breaker of type 3RV1011-0DA1 or 3RV1011-0EA1, set to 0.3 A.
4) For fan motor type RH28M-2DK.3F.1R in units 6RA8090, 6RA8091, 6RA8093, and 6RA8095 with a rated voltage of 400 V or 575 V, UL systems require a Siemens motor circuit breaker of type 3RV1011-0KA1 or 3RV1011-1AA1, set to 1.25 A.
5) For derating factors at higher temperatures and installation altitudes, see „Current derating“.
SINAMICS DC MASTER converters for 400 V 3 AC, 15 to 125 A, four-quadrant operation
Type
6RA8013- 6DV62-0AA0
6RA8018- 6DV62-0AA0
6RA8025- 6DV62-0AA0
6RA8028- 6DV62-0AA0
6RA8031- 6DV62-0AA0
Rated armature supply voltage 1)
V
400 3 AC (+15/-20 %)
Rated armature input current
A
12
25
50
75
104
Rated supply voltage, electronics power supply
V
380 (-25 %) … 480 (+10 %) 2 AC; In = 1 A or 190 (-25 %) … 240 (+10 %) 2 AC; In = 2 A
1) The armature/field supply voltage may be lower than the rated armature/field voltage (set by parameter). A minimum input voltage of 50 V is permissible for units with a rated voltage of 400 V, 480 V and 575 V, or 85 V for higher rated voltages. The output voltage is reduced accordingly. The specified DC output voltage can be maintained up to an undervoltage of 5 % of the line supply voltage (rated armature/field supply voltage).
2) Fan noise for a unit installed in an IP20 electrical cabinet (door closed, 50 Hz operation or operation at 24 V DC for units with an internal supply).
3) For derating factors at higher temperatures and installation altitudes, see „Current derating“.
SINAMICS DC MASTER converters for 400 V 3 AC, 210 to 850 A, four-quadrant operation
Type
6RA8075- 6DV62-0AA0
6RA8078- 6DV62-0AA0
6RA8081- 6DV62-0AA0
6RA8085- 6DV62-0AA0
6RA8087- 6DV62-0AA0
Rated armature supply voltage 1)
V
400 3 AC (+15/-20 %)
Rated armature input current
A
174
232
332
498
706
Rated supply voltage, electronics power supply
V
380 (-25 %) … 480 (+10 %) 2 AC; In = 1 A or 190 (-25 %) … 240 (+10 %) 2 AC; In = 2 A
Rated fan supply voltage
V
24 V DC internal
400 V 3 AC ± 10 % (50 Hz) 460 V 3 AC ± 10 % (60 Hz)
1) The armature/field supply voltage may be lower than the rated armature/field voltage (set by parameter). A minimum input voltage of 50 V is permissible for units with a rated voltage of 400 V, 480 V and 575 V, or 85 V for higher rated voltages. The output voltage is reduced accordingly. The specified DC output voltage can be maintained up to an undervoltage of 5 % of the line supply voltage (rated armature/field supply voltage).
2) Fan noise for a unit installed in an IP20 electrical cabinet (door closed, 50 Hz operation or operation at 24 V DC for units with an internal supply).
3) For fan motor type R2D220-AB02-19 in units 6RA8081, 6RA8085, and 6RA8087 with a rated voltage of 400 V or 575 V, UL systems require a Siemens motor circuit breaker of type 3RV1011-0DA1 or 3RV1011-0EA1, set to 0.3 A.
4) For derating factors at higher temperatures and installation altitudes, see „Current derating“.
SINAMICS DC MASTER converters for 400 V 3 AC, 1200 to 3000 A, four-quadrant operation
Type
6RA8091- 6DV62-0AA0
6RA8093- 4DV62-0AA0
6RA8095- 4DV62-0AA0
6RA8098- 4DV62-0AA0
Rated armature supply voltage 1)
V
400 3 AC (+15/-20 %)
400 3 AC (+10/-20 %)
Rated armature input current
A
996
1328
1660
2490
Rated supply voltage, electronics power supply
V
380 (-25 %) … 480 (+10 %) 2 AC; In = 1 A or 190 (-25 %) … 240 (+10 %) 2 AC; In = 2 A
Rated fan supply voltage
V
400 V 3 AC ± 10 % (50 Hz) 460 V 3 AC ± 10 % (60 Hz)
1) The armature/field supply voltage may be lower than the rated armature/field voltage (set by parameter). A minimum input voltage of 50 V is permissible for units with a rated voltage of 400 V, 480 V and 575 V, or 85 V for higher rated voltages. The output voltage is reduced accordingly. The specified DC output voltage can be maintained up to an undervoltage of 5 % of the line supply voltage (rated armature/field supply voltage).
2) Fan noise for a unit installed in an IP20 electrical cabinet (door closed, 50 Hz operation or operation at 24 V DC for units with an internal supply).
3) For fan motor type R2D220-AB02-19 in units 6RA8081, 6RA8085, and 6RA8087 with a rated voltage of 400 V or 575 V, UL systems require a Siemens motor circuit breaker of type 3RV1011-0DA1 or 3RV1011-0EA1, set to 0.3 A.
4) For derating factors at higher temperatures and installation altitudes, see „Current derating“.
SINAMICS DC MASTER converters for 480 V 3 AC, 15 to 210 A, four-quadrant operation
Type
6RA8013- 6FV62-0AA0
6RA8018- 6FV62-0AA0
6RA8025- 6FV62-0AA0
6RA8028- 6FV62-0AA0
6RA8031- 6FV62-0AA0
6RA8075- 6FV62-0AA0
Rated armature supply voltage 1)
V
480 3 AC (+15/-20 %)
480 3 AC (+10/-20 %)
Rated armature input current
A
12
25
50
75
104
174
Rated supply voltage, electronics power supply
V
380 (-25 %) … 480 (+10 %) 2 AC; In = 1 A or 190 (-25 %) … 240 (+10 %) 2 AC; In = 2 A
1) The armature/field supply voltage may be lower than the rated armature/field voltage (set by parameter). A minimum input voltage of 50 V is permissible for units with a rated voltage of 400 V, 480 V and 575 V, or 85 V for higher rated voltages. The output voltage is reduced accordingly. The specified DC output voltage can be maintained up to an undervoltage of 5 % of the line supply voltage (rated armature/field supply voltage).
2) Fan noise for a unit installed in an IP20 electrical cabinet (door closed, 50 Hz operation or operation at 24 V DC for units with an internal supply).
3) For derating factors at higher temperatures and installation altitudes, see „Current derating“.
SINAMICS DC MASTER converters for 480 V 3 AC, 280 to 1200 A, four-quadrant operation
Type
6RA8078- 6FV62-0AA0
6RA8082- 6FV62-0AA0
6RA8085- 6FV62-0AA0
6RA8087- 6FV62-0AA0
6RA8091- 6FV62-0AA0
Rated armature supply voltage 1)
V
480 3 AC (+10/-20 %)
Rated armature input current
A
232
374
498
706
996
Rated supply voltage, electronics power supply
V
380 (-25 %) … 480 (+10 %) 2 AC; In = 1 A or 190 (-25 %) … 240 (+10 %) 2 AC; In = 2 A
Rated fan supply voltage
V
24 V DC internal
400 V 3 AC ± 10 % (50 Hz) 460 V 3 AC ± 10 % (60 Hz)
1) The armature/field supply voltage may be lower than the rated armature/field voltage (set by parameter). A minimum input voltage of 50 V is permissible for units with a rated voltage of 400 V, 480 V and 575 V, or 85 V for higher rated voltages. The output voltage is reduced accordingly. The specified DC output voltage can be maintained up to an undervoltage of 5 % of the line supply voltage (rated armature/field supply voltage).
2) Fan noise for a unit installed in an IP20 electrical cabinet (door closed, 50 Hz operation or operation at 24 V DC for units with an internal supply).
3) For fan motor type R2D220-AB02-19 in units 6RA8081, 6RA8085, and 6RA8087 with a rated voltage of 400 V or 575 V, UL systems require a Siemens motor circuit breaker of type 3RV1011-0DA1 or 3RV1011-0EA1, set to 0.3 A.
4) For derating factors at higher temperatures and installation altitudes, see „Current derating“.
SINAMICS DC MASTER converters for 575 V 3 AC, 60 to 850 A, four-quadrant operation
Type
6RA8025- 6GV62-0AA0
6RA8031- 6GV62-0AA0
6RA8075- 6GV62-0AA0
6RA8081- 6GV62-0AA0
6RA8085- 6GV62-0AA0
6RA8087- 6GV62-0AA0
Rated armature supply voltage 1)
V
575 3 AC (+10/-20 %)
Rated armature input current
A
50
104
174
332
498
706
Rated supply voltage, electronics power supply
V
380 (-25 %) … 480 (+10 %) 2 AC; In = 1 A or 190 (-25 %) … 240 (+10 %) 2 AC; In = 2 A
Rated fan supply voltage
V
Self-ventilated
24 V DC internal
400 V 3 AC ± 10 % (50 Hz) 460 V 3 AC ± 10 % (60 Hz)
1) The armature/field supply voltage may be lower than the rated armature/field voltage (set by parameter). A minimum input voltage of 50 V is permissible for units with a rated voltage of 400 V, 480 V and 575 V, or 85 V for higher rated voltages. The output voltage is reduced accordingly. The specified DC output voltage can be maintained up to an undervoltage of 5 % of the line supply voltage (rated armature/field supply voltage).
2) Fan noise for a unit installed in an IP20 electrical cabinet (door closed, 50 Hz operation or operation at 24 V DC for units with an internal supply).
3) For fan motor type R2D220-AB02-19 in units 6RA8081, 6RA8085, and 6RA8087 with a rated voltage of 400 V or 575 V, UL systems require a Siemens motor circuit breaker of type 3RV1011-0DA1 or 3RV1011-0EA1, set to 0.3 A.
4) For derating factors at higher temperatures and installation altitudes, see „Current derating“.
SINAMICS DC MASTER converters for 575 V 3 AC, 1100 to 2800 A, four-quadrant operation
Type
6RA8090- 6GV62-0AA0
6RA8093- 4GV62-0AA0
6RA8095- 4GV62-0AA0
6RA8096- 4GV62-0AA0
6RA8097- 4GV62-0AA0
Rated armature supply voltage 1)
V
575 3 AC (+10/-20 %)
Rated armature input current
A
913
1328
1660
1826
2324
Rated supply voltage, electronics power supply
V
380 (-25 %) … 480 (+10 %) 2 AC; In = 1 A or 190 (-25 %) … 240 (+10 %) 2 AC; In = 2 A
Rated fan supply voltage
V
400 V 3 AC ± 10 % (50 Hz) 460 V 3 AC ± 10 % (60 Hz)
1) The armature/field supply voltage may be lower than the rated armature/field voltage (set by parameter). A minimum input voltage of 50 V is permissible for units with a rated voltage of 400 V, 480 V and 575 V, or 85 V for higher rated voltages. The output voltage is reduced accordingly. The specified DC output voltage can be maintained up to an undervoltage of 5 % of the line supply voltage (rated armature/field supply voltage).
2) Fan noise for a unit installed in an IP20 electrical cabinet (door closed, 50 Hz operation or operation at 24 V DC for units with an internal supply).
3) For fan motor type R2D220-AB02-19 in units 6RA8081, 6RA8085, and 6RA8087 with a rated voltage of 400 V or 575 V, UL systems require a Siemens motor circuit breaker of type 3RV1011-0DA1 or 3RV1011-0EA1, set to 0.3 A.
4) For fan motor type RH28M-2DK.3F.1R in units 6RA8090, 6RA8091, 6RA8093, and 6RA8095 with a rated voltage of 400 V or 575 V, UL systems require a Siemens motor circuit breaker of type 3RV1011-0KA1 or 3RV1011-1AA1, set to 1.25 A.
5) For derating factors at higher temperatures and installation altitudes, see „Current derating“.
SINAMICS DC MASTER converters for 690 V 3 AC, 760 to 2600 A, four-quadrant operation
Type
6RA8086- 6KV62-0AA0
6RA8090- 6KV62-0AA0
6RA8093- 4KV62-0AA0
6RA8095- 4KV62-0AA0
6RA8097- 4KV62-0AA0
Rated armature supply voltage 1)
V
690 3 AC (+10/-20 %)
Rated armature input current
A
631
830
1245
1660
2158
Rated supply voltage, electronics power supply
V
380 (-25 %) … 480 (+10 %) 2 AC; In = 1 A or 190 (-25 %) … 240 (+10 %) 2 AC; In = 2 A
Rated fan supply voltage
V
400 V 3 AC ± 10 % (50 Hz) 460 V 3 AC ± 10 % (60 Hz)
1) The armature/field supply voltage may be lower than the rated armature/field voltage (set by parameter). A minimum input voltage of 50 V is permissible for units with a rated voltage of 400 V, 480 V and 575 V, or 85 V for higher rated voltages. The output voltage is reduced accordingly. The specified DC output voltage can be maintained up to an undervoltage of 5 % of the line supply voltage (rated armature/field supply voltage).
2) Fan noise for a unit installed in an IP20 electrical cabinet (door closed, 50 Hz operation or operation at 24 V DC for units with an internal supply).
3) For fan motor type R2D220-AB02-19 in units 6RA8081, 6RA8085, and 6RA8087 with a rated voltage of 400 V or 575 V, UL systems require a Siemens motor circuit breaker of type 3RV1011-0DA1 or 3RV1011-0EA1, set to 0.3 A.
4) For fan motor type RH28M-2DK.3F.1R in units 6RA8090, 6RA8091, 6RA8093, and 6RA8095 with a rated voltage of 400 V or 575 V, UL systems require a Siemens motor circuit breaker of type 3RV1011-0KA1 or 3RV1011-1AA1, set to 1.25 A.
5) For derating factors at higher temperatures and installation altitudes, see „Current derating“.
SINAMICS DC MASTER converters for 830 V 3 AC, 950 to 1900 A and 950 V 3 AC, 2200 A, four-quadrant operation
Type
6RA8088- 6LV62-0AA0
6RA8093- 4LV62-0AA0
6RA8095- 4LV62-0AA0
6RA8096- 4MV62-0AA0
Rated armature supply voltage 1)
V
830 3 AC (+10/-20 %)
950 3 AC (+15/-20 %)
Rated armature input current
A
789
1245
1577
1826
Rated supply voltage, electronics power supply
V
380 (-25 %) … 480 (+10 %) 2 AC; In = 1 A or 190 (-25 %) … 240 (+10 %) 2 AC; In = 2 A
Rated fan supply voltage
V
400 V 3 AC ± 10 % (50 Hz) 460 V 3 AC ± 10 % (60 Hz)
1) The armature/field supply voltage may be lower than the rated armature/field voltage (set by parameter). A minimum input voltage of 50 V is permissible for units with a rated voltage of 400 V, 480 V and 575 V, or 85 V for higher rated voltages. The output voltage is reduced accordingly. The specified DC output voltage can be maintained up to an undervoltage of 5 % of the line supply voltage (rated armature/field supply voltage).
2) Fan noise for a unit installed in an IP20 electrical cabinet (door closed, 50 Hz operation or operation at 24 V DC for units with an internal supply).
3) For fan motor type R2D220-AB02-19 in units 6RA8081, 6RA8085, and 6RA8087 with a rated voltage of 400 V or 575 V, UL systems require a Siemens motor circuit breaker of type 3RV1011-0DA1 or 3RV1011-0EA1, set to 0.3 A.
4) For fan motor type RH28M-2DK.3F.1R in units 6RA8090, 6RA8091, 6RA8093, and 6RA8095 with a rated voltage of 400 V or 575 V, UL systems require a Siemens motor circuit breaker of type 3RV1011-0KA1 or 3RV1011-1AA1, set to 1.25 A.
5) For derating factors at higher temperatures and installation altitudes, see „Current derating“.