Input | В |
Measured variable | Differential pressure and flow |
Span (infinitely adjustable) or nominal measuring range and maximum operating pressure (pursuant to 2014/68/EU Pressure Equipment Directive) | HART | PROFIBUS PA and FOUNDATION Fieldbus | В |
Span | Nominal measuring range | Max. perm. operating pressure MAWP (PS) |
1В ...В 20В mbar 0.1 ... 2 kPa 0.4В ...В 8В inH2O | 20В mbar 2 kPa 8В inH2O | 32В bar 3.2 MPa 464В psi |
1В ...В 60В mbar 0.1 ... 6 kPa 0.4В ...В 24В inH2O | 1В ...В 60В mbar 0.1 ... 6 kPa 0.4В ...В 24В inH2O | 160В bar 16 MPa 2320В psi |
2.5В ...В 250В mbar 0.2 ... 25 kPa 1В ...В 100В inH2O | 2.5В ...В 250В mbar 0.2 ... 25 kPa 1В ...В 100В inH2O |
6В ...В 600В mbar 0.6 ... 60 kPa 2.4В ...В 240В inH2O | 6В ...В 600В mbar 0.6 ... 60 kPa 2.4В ...В 240В inH2O |
16В ...В 1600В mbar 1.6 .... 160 kPa 6.4В ...В 642В inH2O | 16В ...В 1600В mbar 1.6 .... 160 kPa 6.4В ...В 642В inH2O |
50В ...В 5000В mbar 5 ... 500 kPa 20В ...В 2000В inH2O | 50В ...В 5000В mbar 5 ... 500 kPa 20В ...В 2000В inH2O |
0.3В ...В 30В bar 0.03 ... 3 MPa 4.35В ...В 435В psi | 0.3В ...В 30В bar 0.03 ... 3 MPa 4.35В ...В 435В psi |
2.5В ...В 250В mbar 0.25 ... 25 kPa 1В ...В 100В inH2O | 2.5В ...В 250В mbar 0.25 ... 25 kPa 1В ...В 100В inH2O | 420В bar 42 MPa 6091 psi (500 bar/50 MPa/7250 psi can be optionally ordered with order code D56) |
6В ...В 600В mbar 0.6 ... 60 kPa 2.4В ...В 240В inH2O | 6В ...В 600В mbar 0.6 ... 60 kPa 2.4В ...В 240В inH2O |
16В ...В 1600В mbar 1.6 ... 160 kPa 6.4В ...В 642В inH2O | 16В ...В 1600В mbar 1.6 ... 160 kPa 6.4В ...В 642В inH2O |
50В ...В 5000В mbar 5 ... 500 kPa 20В ...В 2000В inH2O | 50В ...В 5000В mbar 5 ... 500 kPa 20В ...В 2000В inH2O |
0.3В ...В 30В bar 0.03 ... 3 MPa 4.35В ...В 435В psi | 0.3В ...В 30В bar 0.03 ... 3 MPa 4.35В ...В 435В psi |
Low measuring limit | В |
- Measuring cell with silicone oil filling
| -100% of max. measuring range (-33В % for 30В bar /3 MPa /435 psi measuring cell) or 30В mbarВ a /3 kPa a /0.44 psi a |
- Measuring cell with inert liquid
| В |
- for process temperature -20 °C < ϑ ≤ +60 °C
(-4 °F < ϑ ≤ +140 °F)
| -100% of max. measuring range (-33В % for 30В bar /3 MPa /435 psi measuring cell) or 30В mbarВ a /3 kPa a /0.44 psi a |
- for process temperature 60 °C < ϑ ≤ +100°C (max. 85 °C for measuring cell 30 bar) (140 °F < ϑ ≤ +212 °F (max. 185 °F for measuring cell 435 psi))
| 30 mbar a + 20 mbar a . ( П‘ - 60В В°C)/В°C 3 kPa a + 2 kPa a . ( П‘ - 60В В°C)/В°C 0.44 psi a + 0.29 psi a . ( П‘ - 140В В°F)/В°F |
Upper measuring limit | 100В % of the max. measuring span (for oxygen measurement max. 100 bar/10 MPa/ 1450 psi and 60 В°C (140 В°F) ambient temperature/process temperature |
Start of scale | Between the measuring limits (infinitely adjustable) |
Output | HART | PROFIBUS PA and FOUNDATION Fieldbus |
Output signal | 4В ...В 20 mA | Digital PROFIBUS PA and FOUNDATION Fieldbus signal |
- Lower limit (infinitely adjustable)
| 3.55 mA, factory preset to 3.84 mA | - |
- Upper limit (infinitely adjustable)
| 23В mA, factory preset to 20.5В mA or optionally set to 22.0В mA (with order code D05) | - |
Load | В | В |
| RB ≤ (UH - 10.5 V)/0.023 A in Ω, UH: Power supply in V | - |
| RB = 230 ... 500 О© (SIMATIC PDM) or RB = 230 ... 1100 О© (HART Communicator) | - |
Physical bus | - | IECВ 61158-2 |
Protection against polarity reversal | Protected against short-circuit and polarity reversal. Each connection against the other with max. supply voltage. |
Electrical damping (step width 0.1 s) | Set to 2 s (0 ... 100 s) |
Measuring accuracy | According to IEC 60770-1 |
Reference conditions | - Rising characteristic curve
- Start of scale 0 bar
- Seal diaphragm stainless steel
- Silicone oil filling
- Room temperature 25В В°C (77В В°F)
|
Measuring span ratio r (spread, Turn-Down) | r = maximum measuring span/set measuring span or nominal measuring range |
Error in measurement at limit setting including hysteresis and reproducibility | В |
| В |
| r ≤ 5 : 5 < r ≤ 10 : 10 < r ≤ 20 : | ≤ 0.075 % ≤ (0.0029 · r + 0.071) % ≤ (0.0045 · r + 0.071) % |
| r ≤ 5 : 5 < r ≤ 60 : | ≤ 0.15 % ≤ (0.005 · r + 0.05) % |
- 250 mbar/25 kPa/3.63 psi
600 mbar/60 kPa/8.7 psi 1600 mbar/160 MPa/23.21 psi 5 bar/500 kpa/72.5 psi 30 bar/3 MPa/435 psi
| r ≤ 5 : 5 < r ≤ 100 : | ≤ 0.065 % ≤ (0.004 · r + 0.045) % |
- Square-rooted characteristic (flow > 50%)
| В |
| r ≤ 5 : 5 < r ≤ 10 : 10 < r ≤ 20 : | ≤ 0.075 % ≤ (0.0029 · r + 0.071) % ≤ (0.0045 · r + 0.071) % |
| r ≤ 5 : 5 < r ≤ 60 : | ≤ 0.075 % ≤ (0.005 · r + 0.05) % |
- 250 mbar/25 kPa/3.63 psi
600 mbar/60 kPa/8.7 psi 1600 mbar/160 MPa/23.21 psi 5 bar/500 kpa/72.5 psi 30 bar/3 MPa/435 psi
| r ≤ 5 : 5 < r ≤ 100 : | ≤ 0.065 % ≤ (0.004 · r + 0.045) % |
- Square-rooted characteristic (flow 25В ...В 50%)
| В |
| r ≤ 5 : 5 < r ≤ 10 : 10 < r ≤ 20 : | ≤ 0.15 % ≤ (0.0058 · r + 0.142) % ≤ (0.0095 · r + 0.142) % |
| r ≤ 5 : 5 < r ≤ 60 : | ≤ 0.15 % ≤ (0.01 · r + 0.1) % |
- 250 mbar/25 kPa/3.63 psi
600 mbar/60 kPa/8.7 psi 1600 mbar/160 MPa/23.21 psi 5 bar/500 kpa/72.5 psi 30 bar/3 MPa/435 psi
| r ≤ 5 : 5 < r ≤ 100 : | ≤ 0.13 % ≤ (0.008 · r + 0.09) % |
Influence of ambient temperature (in percent per 28В В°C (50В В°F)) | В |
| ≤ (0.15 · r + 0.1) % |
| ≤ (0.075 · r + 0.1) % |
- 250 mbar/25 kPa/3.63 psi
600 mbar/60 kPa/8.7 psi 1600 mbar/160 MPa/23.21 psi 5 bar/500 kpa/72.5 psi 30 bar/3 MPa/435 psi
| ≤ (0.025 · r + 0.125) % |
Effect of static pressure | В |
| В |
| ≤ (0.15 · r) % per 32 bar (zero-point correction is possible with position error adjustment) |
- 60 mbar/6 kPa/0.87 psi
250 mbar/25 kPa/3.63 psi 600 mbar/60 kPa/8.7 psi 1600 mbar/160 MPa/23.21 psi
| ≤ (0.1 · r) % per 70 bar (zero-point correction is possible with position error adjustment) |
- 5 bar/500 kpa/72.5 psi
30 bar/3 MPa/435 psi
| ≤ (0.2 · r) % per 70 bar (zero-point correction is possible with position error adjustment) |
| В |
| ≤ 0.2% per 32 bar |
- 60 mbar/6 kPa/0.87 psi
250 mbar/25 kPa/3.63 psi 600 mbar/60 kPa/8.7 psi 1600 mbar/160 MPa/23.21 psi 5 bar/500 kpa/72.5 psi 30 bar/3 MPa/435 psi
| ≤ 0.14% per 70 bar |
Long-term stability (temperature change В±30 В°C (В±54 В°F)) | Static pressure max. 70 bar/7 MPa/1015 psi |
| ≤ (0.2 · r) % per year |
- 60 mbar/6 kPa/0.87 psi
30 bar/3 MPa/435 psi
| ≤ (0.25 · r) % in 5 years |
- 250 mbar/25 kPa/3.63 psi
600 mbar/60 kPa/8.7 psi 1600 mbar/160 MPa/23.21 psi 5 bar/500 kpa/72.5 psi
| ≤ (0.125 · r) % in 5 years |
Effect of mounting position (in pressure per change of angle) | ≤ 0.7 mbar/0.07 kPa/0.028 inH2O per 10° incline (zero point correction is possible with position error compensation) |
Effect of auxiliary power (in percent per voltage change) | 0.005 % per 1 V |
Measured-value resolution for PROFIBUS PA and FOUNDATION Fieldbus | 3В В·В 10-5 of nominal measuring range |
Rated conditions | В |
Degree of protection acc. to IEC 60529 | IP66 (optional IP66/IP68), NEMA 4X |
Temperature of medium | В |
- Measuring cell with silicone oil filling
| -40В ...В +100В В°C (-40В ...В +212В В°F) -20В ...В +100В В°C (-4В ...В +212В В°F) with 30 bar measuring cell |
- Measuring cell with inert fill fluid
| -20В ...В +100В В°C (-4В ...В +212В В°F) |
- In conjunction with dust explosion protection
| -20В ...В +60В В°C (-4В ...В +140В В°F) |
Ambient conditions | В |
| В |
| -40В ...В +85В В°C (-40В ...В +185В В°F) -20В ...В +85 В°C (-4В ...В +185В В°F) with 30 bar measuring cell |
| -30В ...В +85В В°C (-22В ...В +185В В°F) |
| -50В ...В +85В В°C (-58В ...В +185В В°F) |
| В |
| Relative humidity 0 ... 100% Condensation permissible, suitable for use in the tropics |
- Electromagnetic compatibility
| В |
- Emitted interference and interference immunity
| According to IECВ 61326 and NAMURВ NEВ 21 |
Design | В |
Weight (without options) | Die-cast aluminum: ≈ 4.5 kg (≈ 9.9 lb) Stainless steel precision casting: ≈ 7.1 kg (≈ 15.6 lb) |
Enclosure material | Low-copper die-cast aluminum, GD-AlSi 12 or stainless steel precision casting, mat. no. 1.4408 |
Wetted parts materials | В |
| Stainless steel, mat. no. 1.4404/316L or Hastelloy C276, mat. no. 2.4819, Monel, mat. no. 2.4360, tantalum or gold |
- Process flanges and sealing screw
| Stainless steel, mat. no. 1.4408, Hastelloy C4, mat. no. 2.4602 or Monel, mat. no. 2.4360 |
| FPM (Viton) or optionally: PTFE, FEP, FEPM and NBR |
Measuring cell filling | Silicone oil or inert fill fluid (for oxygen measurement, maximum pressure 100В bar (1450В psi) at 60В В°C (140В В°F)) |
Process connection | Female thread Вј-18В NPT and flange connection with fastening thread M10 to DINВ 19213 or 7/16-20В UNF to IECВ 61518/DINВ ENВ 61518 |
Material of mounting bracket | В |
| Sheet-steel, mat. no.В 1.0330, chrome-plated |
| Sheet stainless steel, mat. no. 1.4301 (SS 304) |
Auxiliary power UH | HART | PROFIBUS PA/FOUNDATION Fieldbus |
Terminal voltage on transmitter | 10.5 ... 45 V DC 10.5 ... 30 V DC in intrinsically-safe mode | - |
Auxiliary power | В | Bus-powered |
Separate supply voltage | - | Not necessary |
Bus voltage | В | В |
| - | 9 ... 32 V |
- With intrinsically-safe operation
| - | 9 ... 24 V |
Current consumption | В | В |
| - | 12.5 mA |
- Start-up current ≤ basic current
| - | Yes |
- Max. current in event of fault
| - | 15.5 mA |
Fault disconnection electronics (FDE) available | - | Yes |
Certificates and approvals | HART | PROFIBUS PA/FOUNDATION Fieldbus |
Classification according to pressure equipment directive (PEDВ 2014/68/EU) | - PNВ 32/160 (MAWP 464/2320 psi) for gases of fluid groupВ 1 and liquids of fluid groupВ 1; complies with requirements of ArticleВ 4, ParagraphВ 3 (sound engineering practice).
|
- PNВ 420 (MAWP 6092) for gases of fluid groupВ 1 and liquids of fluid groupВ 1; complies with basic safety requirements of ArticleВ 4, ParagraphВ 1 (annexВ 1); assigned to category III, conformity evaluation moduleВ H by the TГњV Nord.
|
Explosion protection | В |
| PTB 13 ATEX 2007 X |
| Ex II 1/2 G Ex ia/ib IIC T4/T5/T6 Ga/Gb |
- Permissible ambient temperature
| -40 ... +85 В°C (-40 ... +185 В°F) temperature class T4; -40 ... +70 В°C (-40 ... +158 В°F) temperature class T5; -40 ... +60 В°C (-40 ... +140 В°F) temperature class T6 |
| To certified intrinsically-safe circuits with peak values: Ui = 30 V, Ii = 100 mA, Pi = 750 mW; RiВ =В 300В О© | FISCO supply unit: Uo = 17.5 V, Io = 380 mA, Po = 5.32 W Linear barrier: Uo = 24 V, Io = 250 mA, Po = 1.2 W |
- Effective internal inductance/capacitance
| Li = 0.4 mH, Ci = 6 nF | Li = 7 ОјH, Ci = 1.1 nF |
| PTB 99 ATEX 1160 |
| Ex II 1/2 G Ex d IIC T4/T6 Gb |
- Permissible ambient temperature
| -40 ... +85 В°C (-40 ... +185 В°F) temperature class T4; -40 ... +60 В°C (-40 ... +140 В°F) temperature class T6 |
| To circuits with operating values: UHВ =В 10.5В ...В 45 V DC | To circuits with operating values: UHВ =В 9В ...В 32 V DC |
- Dust explosion protection for zone 20
| PTB 01 ATEX 2055 |
| Ex II 1 D Ex ta IIIC T120В°C Da Ex II 1/2 D Ex ta/tb IIIC T120В°C Da/Db |
- Permissible ambient temperature
| -40В ...В +85В В°C (-40В ...В +185В В°F) |
| 120 В°C (248 В°F) |
| To certified intrinsically-safe circuits with peak values: Ui = 30 V, Ii = 100 mA, Pi = 750 mW, Ri = 300 О© | FISCO supply unit: Uo = 17.5 V, Io = 380 mA, Po = 5.32 W Linear barrier: Uo = 24 V, Io = 250 mA, Po = 1.2 W |
- Effective internal inductance/capacitance
| Li = 0.4 mH, Ci = 6 nF | Li = 7 ОјH, Ci = 1.1 nF |
- Dust explosion protection for zone 21/22
| PTB 01 ATEX 2055 |
| Ex II 2 D Ex tb IIIC T120В°C Db |
| To circuits with operating values: UHВ =В 10.5В ...В 45 V DC; Pmax = 1.2 W | To circuits with operating values: UHВ =В 9В ...В 32 VВ DC; Pmax = 1 W |
- Type of protection "n" (zone 2)
| PTB 13 ATEX 2007 X |
| Ex II 2/3 G Ex nA IIC T4/T5/T6 Gc Ex II 2/3 G Ex ic IIC T4/T5/T6 Gc |
| Um = 45 V | Um = 32 V |
| To circuits with operating values: Ui = 45 V | FISCO supply unit: Uo = 17.5 V, Io = 570 mA Linear barrier: Uo = 32 V, Io = 132 mA, Po = 1 W |
- Effective internal inductance/capacitance
| Li = 0.4 mH, Ci = 6 nF | Li = 7 ОјH, Ci = 1.1 nF |
- Explosion protection acc. to FM
| Certificate of Compliance 3008490 |
- Designation (XP/DIP) or (IS); (NI)
| CLВ I, DIVВ 1, GP ABCD T4...T6; CLВ II, DIVВ 1, GPВ EFG; CLВ III; CLВ I, ZNВ 0/1 AEx ia IIC T4...T6; CLВ I, DIVВ 2, GPВ ABCD T4...T6; CLВ II, DIVВ 2, GPВ FG; CLВ III |
- Explosion protection to CSA
| Certificate of Compliance 1153651 |
| CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; Ex ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III |