Input | В |
Measured variable | Gauge pressure |
Span (fully adjustable) or nominal measuring range, max. operating pressure (in accordance with 2014/68/EU Pressure Equipment Directive) and max. test pressure (pursuant to DINВ 16086) | Span | Max. perm. operating pressure MAWP (PS) | Max. permissible test pressure |
0.01 ... 1 bar 1 ... 100 kPa 0.15 ... 14.5 psi | 4 bar 400 kPa 58 psi | 6 bar 600 kPa 87 psi |
0.04 ... 4 bar 4 ... 400 kPa 0.58 ... 58 psi | 7 bar 0.7 Mpa 102 psi | 10 bar 1 MPa 145 psi |
0.16 ... 16 bar 16 ... 1600 kPa 2.3 ... 232 psi | 21 bar 2.1 MPa 305 psi | 32 bar 3.2 MPa 464 psi |
0.63 ... 63 bar 63 ... 6300 kPa 9.1 ... 914 psi | 67 bar 6.7 MPa 972 psi | 100 bar 10 MPa 1450 psi |
1.6 ... 160 bar 0.16 ... 16 MPa 23 ... 2321 psi | 167 bar 16.7 MPa 2422 psi | 250 bar 25 MPa 3626 psi |
4 ... 400 bar 0.4 ... 40 MPa 58 ... 5802 psi | 400 bar 40 MPa 5802 psi | 600 bar 60 MPa 8702 psi |
7 ... 700 bar 0.7 ... 70 MPa 102 ... 10153 psi | 800 bar 80 MPa 11603 psi | 800 bar 80 MPa 11603 psi |
Low measuring limit | В |
- Measuring cell with silicone oil filling
| 30 mbar a/3 kPa a/0.44 psia |
Upper measuring limit | 100 % of max. span |
Start of scale | Between the measuring limits (continuously adjustable) |
Output | В |
Output signal | 4В ...В 20 mA |
- Lower limit (fully adjustable)
| 3.55 mA, factory preset to 3.84 mA |
- Upper limit (fully adjustable)
| 23 mA, factory preset to 20.5 mA or optionally set to 22.0 mA |
Load | В |
| RB ≤ (UH - 10.5 V)/0.023 A in Ω, UH: Power supply in V |
| RB = 230 ... 500 О© (SIMATIC PDM) or RB = 230 ... 1100 О© (HART Communicator) |
Protection against polarity reversal | Protected against short-circuit and polarity reversal. Each connection against the other with max. supply voltage. |
Electrical damping (step width 0.1 s) | Set to 2 s (0 ... 100 s) |
Measuring accuracy | According to IEC 60770-1 |
Reference conditions | - Rising characteristic curve
- Start of scale 0 bar
- Seal diaphragm stainless steel
- Silicone oil filling
- Room temperature 25В В°C (77В В°F)
|
Measuring span ratio r (spread, Turn-Down) | r = maximum measuring span/set measuring span |
Error in measurement at limit setting including hysteresis and reproducibility | В |
| В |
- 1 bar/100 kPa/3.6 psi
4 bar/400 kPa/58 psi 16 bar/1.6 MPa/232 psi 63 bar/6.3 MPa/914 psi 160 bar/16 MPa/2321 psi
| r ≤ 5 5 < r ≤ 100 | ≤ 0.075 % ≤ (0.005 · r + 0.07) % |
- 400 bar/40 MPa/5802 psi
700 bar/70 MPa/10152 psi
| r ≤ 3 3 < r ≤ 100 | ≤ 0.075 % ≤ (0.005 · r + 0.07) % |
Influence of ambient temperature (in percent per 28В В°C (50В В°F)) | В |
- At -40 … +85 °C (-40 … 185 °F)
| ≤ (0.15 · r + 0.25) % |
Long-term stability (temperature change ±30 °C (±54 °F)) | ≤ (0.25 · r) % in 5 years |
Influence of mounting position | ≤ 0.05 mbar/0.005 kPa/0.000725 psi per 10° incline (zero point correction is possible with position error compensation) |
Effect of auxiliary power (in percent per voltage change) | 0.005 % per 1 V |
Rated conditions | В |
Degree of protection according to IECВ 60529 | IP66 (optional IP66/IP68), NEMA 4X |
Temperature of medium | В |
- Measuring cell with silicone oil filling
| -40В ...В +100В В°C (-40В ...В +212В В°F) |
- In conjunction with dust explosion protection
| -20В ...В +60В В°C (-4В ...В +140В В°F) |
Ambient conditions | В |
| В |
| -40В ...В +85В В°C (-40В ...В +185В В°F) |
| -30В ...В +85В В°C (-22В ...В +185В В°F) |
| -50В ...В +85В В°C (-58В ...В +185В В°F) |
| В |
| Relative humidity 0 ... 100 % Condensation permissible, suitable for use in the tropics |
- Electromagnetic compatibility
| В |
- Emitted interference and interference immunity
| According to IECВ 61326 and NAMURВ NEВ 21 |
Design | В |
Weight (without options) | Die-cast aluminum: ≈ 2.0 kg (≈ 4.4 lb) Stainless steel precision casting: ≈ 4.6 kg (≈ 10.1 lb) |
Enclosure material | Low-copper die-cast aluminum, GD-AlSi 12 or stainless steel precision casting, mat. no. 1.4408 |
Wetted parts materials | В |
| Stainless steel, mat. no.В 1.4404/316L or HastelloyВ C4, mat. no.В 2.4602 |
| Stainless steel, mat. no. 1.4404/316L or Hastelloy C276, mat. no. 2.4819 |
Measuring cell filling | Silicone oil or inert fill fluid (for oxygen measurement, maximum pressure 100В bar (1450В psi) at 60В В°C (140В В°F)) |
Process connection | GВЅB connection shank according to DIN ENВ 837-1; female thread ВЅ-14В NPT or external thread M20x1.5 |
Material of mounting bracket | В |
Steel | Sheet-steel, mat. no.В 1.0330, chrome-plated |
Stainless steel | Sheet stainless steel, mat. no. 1.4301 (SS 304) |
Power supply UH | В |
Terminal voltage on transmitter | 10.5 ... 45 V DC 10.5 ... 30 V DC in intrinsically-safe mode |
Certificates and approvals | HART |
Classification according to pressure equipment directive (PEDВ 2014/68/EU) | For gases of fluid group 1 and liquids of fluid groupВ 1; complies with requirements of articleВ 4, paragraphВ 3 (sound engineering practice) |
Explosion protection | В |
| PTB 13 ATEX 2007 X |
| Ex II 1/2 G Ex ia/ib IIC T4/T5/T6 Ga/Gb |
- Permissible ambient temperature
| -40 ... +85 В°C (-40 ... +185 В°F) temperature class T4; -40 ... +70 В°C (-40 ... +158 В°F) temperature class T5; -40 ... +60 В°C (-40 ... +140 В°F) temperature class T6 |
| To certified intrinsically-safe circuits with peak values: Ui = 30 V, Ii = 100 mA, Pi = 750 mW; RiВ =В 300В О© |
- Effective internal inductance/capacitance
| Li = 0.4 mH, Ci = 6 nF |
| PTB 99 ATEX 1160 |
| Ex II 1/2 G Ex d IIC T4/T6 Gb |
- Permissible ambient temperature
| -40 ... +85 В°C (-40 ... +185 В°F) temperature class T4; -40 ... +60 В°C (-40 ... +140 В°F) temperature class T6 |
| To circuits with operating values: UHВ =В 10.5В ...В 45 V DC |
- Dust explosion protection for zone 20
| PTB 01 ATEX 2055 |
| Ex II 1 D Ex ta IIIC T120 В°C Da Ex II 1/2 D Ex ta/tb IIIC T120 В°C Da/Db |
- Perm. Ambient temperature
| -40В ...В +85В В°C (-40В ...В +185В В°F) |
| 120 В°C (248 В°F) |
| To certified intrinsically-safe circuits with peak values: Ui = 30 V, Ii = 100 mA, Pi = 750 mW, Ri = 300 О© |
- Effective internal inductance/capacitance
| Li = 0.4 mH, Ci = 6 nF |
- Dust explosion protection for zone 21/22
| PTB 01 ATEX 2055 |
| Ex II 2 D Ex tb IIIC T120 В°C Db |
| To circuits with operating values: UHВ =В 10.5В ...В 45 V DC; Pmax = 1.2 W |
- Type of protection "n" (zone 2)
| PTB 13 ATEX 2007 X |
| Ex II 2/3 G Ex nA IIC T4/T5/T6 Gc Ex II 2/3 G Ex ic IIC T4/T5/T6 Gc |
| Um = 45 V |
| To circuits with operating values: Ui = 45 V |
- Effective internal inductance/capacitance
| Li = 0.4 mH, Ci = 6 nF |
- Explosion protection acc. to FM
| Certificate of Compliance 3008490 |
- Marking (XP/DIP) or (IS); (NI)
| CLВ I, DIVВ 1, GP ABCD T4...T6; CLВ II, DIVВ 1, GPВ EFG; CLВ III; CLВ I, ZNВ 0/1 AEx ia IIC T4...T6; CLВ I, DIVВ 2, GPВ ABCD T4...T6; CLВ II, DIVВ 2, GPВ FG; CLВ III |
- Explosion protection to CSA
| Certificate of Compliance 1153651 |
| CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; Ex ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III |
Communication | В |
HART | 230В ...В 1100В О© |
Protocol | HART Version 5.x |
Software for computer | SIMATICВ PDM |