Line voltage (up to 2000 m (6562 ft) above sea level) | 380 ... 480 V 3 AC ±10 % (-15 % <1 min) |
Line frequency | 47 ... 63 Hz |
SCCR (short-circuit current rating) | 65 kA in conjunction with the recommended Class J fuse, or circuit breaker according to UL489 / CSA 22.2 No. 5-02 see recommended line-side components |
Line power factor at rated power | |
| >0.96 |
| 0.75 ... 0.93 |
Overvoltage category according to EN 60664?1 | Class III |
DC link voltage, approx. | 1.35 ? line voltage 1) |
Electronics power supply | 24 V DC -15 %/+20 % |
Radio interference suppression | |
| |
- 20 kW and 40 kW (25 hp and 40 hp) Basic Line Modules
| No radio interference suppression |
- 100 kW (125 hp) Basic Line Module
| Category C3 to EN 61800?3 Total cable length up to 350 m (1148 ft) (shielded) |
| Category C2 to EN 61800?3 Total cable length up to 350 m (1148 ft) (shielded) |
Type of cooling | Internal air cooling (power units with increased air cooling by built-in fan) |
Permissible ambient and coolant temperature (air) during operation for line-side components, Line Modules and Motor Modules | 0 ... 40 °C (32 ... 104 °F) without derating, > 40 ... 55 °C (104 ... 131 °F), see derating characteristics |
Installation altitude | Up to 1000 m (3281 ft) above sea level without derating, > 1000 ... 4000 m (3281 ... 13124 ft) above sea level, see derating characteristics |
Declarations of conformity | CE (Low Voltage and EMC Directives) |
Certificate of suitability | cULus |