Recommended line-side components for Smart Line ModulesSuitable line-side power components are assigned depending on the power rating of the Smart Line Module. The tables below list recommended components. Additional information about the line-side power components can be found in Catalogs LV 10, IC 10 and IC 10 AO as well as the Industry Mall. Assignment of line-side power components to Smart Line Modules in booksize or booksize compact formatRated power | Suitable for Smart Line Module in booksize or booksize compact format | Line contactor | Circuit breaker IEC 60947 | Circuit breaker UL489/CSA C22.2 No. 5-02 | Main switch |
|---|
kW (hp) | Type | Type | Article No. | Article No. | Article No. |
|---|
Line voltage 380 ... 480 V 3 AC | 5 (5) | 6SL3130-6AE15-0AB1 | 3RT1023 | 3RV2021-4BA10 | 3VL1102-2KM30-.... *) | 3LD2003-0TK51 | 10 (10) | 6SL3130-6AE21-0AB1 | 3RT1026 | 3RV1031-4FA10 | 3VL1135-2KM30-.... *) | 3LD2203-0TK51 | 16 (18) | 6SL3130-6TE21-6AA4 6SL3430-6TE21-6AA1 | 3RT1035 | 3RV1031-4FA10 | 3VL1135-2KM30-.... *) | 3LD2504-0TK51 | 36 (40) | 6SL3130-6TE23-6AA3 | 3RT1045 | 3RV1041-4LA10 | 3VL2508-2KN30-.... *) | 3LD2704-0TK51 | 55 (60) | 6SL3130-6TE25-5AA3 | 3RT1054 | 3VL2712-1DC33-.... *) | 3VL2512-2KN30-.... *) | 3KA5330-1GE01 |
Rated power | Suitable for Smart Line Module in booksize or booksize compact format | Fuse switch disconnector | Switch disconnector with fuse holders | LV HRC fuse (gL/gG) | UL/CSA fuse, Class J Available from: Mersen http://www.ep.mersen.com |
|---|
kW (hp) | Type | Article No. | Article No. | Rated current | Size | Article No. | Rated current | Size mm (in) | Reference No. |
|---|
Line voltage 380 ... 480 V 3 AC | 5 (5) | 6SL3130-6AE15-0AB1 | 3NP1123-1CA20 | 3KL5030-1GB01 | 16 A | 000 | 3NA3805 | 17.5 A | 21 ? 57 (0.83 ? 2.24) | AJT17-1/2 | 10 (10) | 6SL3130-6AE21-0AB1 | 3NP1123-1CA20 | 3KL5030-1GB01 | 35 A | 000 | 3NA3814 | 35 A | 27 ? 60 (1.06 ? 2.36) | AJT35 | 16 (18) | 6SL3130-6TE21-6AA4 6SL3430-6TE21-6AA1 | 3NP1123-1CA20 | 3KL5030-1GB01 | 35 A | 000 | 3NA3814 | 35 A | 27 ? 60 (1.06 ? 2.36) | AJT35 | 36 (40) | 6SL3130-6TE23-6AA3 | 3NP1123-1CA20 | 3KL5230-1GB01 | 80 A | 000 | 3NA3824 | 80 A | 29 ? 117 (1.14 ? 4.61) | AJT80 | 55 (60) | 6SL3130-6TE25-5AA3 | 3NP1143-1DA20 | 3KL5530-1GB01 | 125 A | 000 | 3NA3132 | 125 A | 41 ? 146 (1.61 ? 5.75) | AJT125 |
*) See Catalog LV 10 for Article No. supplements.
|