Electrical specifications |
Line voltage | 380 ... 480 V 3 AC ±10 % (-15 % <1 min) |
Line system configurations | Grounded TN/TT systems and non-grounded IT systems |
Line frequency | 47 ... 63 Hz |
Electronics power supply | 24 V DC -15 %/+20 %1), safety extra low-voltage (PELV/SELV) |
Short-circuit current rating (SCCR) (Short Circuit Current Rating) according to UL 508C (up to 600 V) | 1.1 ... 447 kW: 65 kA |
Electromagnetic compatibility According to EN 61800?3 | Second environment, Category C2/C3 For further information, see section Engineering notes |
Overvoltage category According to IEC/EN 61800?5?1 | III |
Mechanical specifications |
Degree of protection | |
| IP20 |
- According to UL 508C/UL 61800?5?1
| Open type |
Protection class | |
- Line circuits with protective conductor connection according to IEC 61800?5?1
| I |
| Safety extra low-voltage PELV/SELV |
Ambient conditions |
| Storage | Transport | Operation |
In product packaging | In transport packaging | |
Climatic environmental conditions | Class 1K4 acc. to EN 60721?3?1 -25 ... +55 °C (-13 ... +131 °F) | Class 2K4 acc. to EN 60721?3?2 -40 ... +70 °C (-40 ...+158 °F) | Class 3K3 3) acc. to EN 60721?3?3 For operation without derating4): 0 ... +40 °C (32 ...104 °F) For operation with derating: >40 ... +55 °C (>32 ... 131 °F) Relative humidity 5 ... 95 % |
Environmental class/harmful chemical substances | Class 1C2 acc. to EN 60721?3?1 | Class 2C2 acc. to EN 60721?3?2 | Class 3C2 acc. to EN 60721?3?3 |
Organic/biological influences | Class 1B1 acc. to EN 60721?3?1 | Class 2B1 acc. to EN 60721?3?2 | Class 3B1 acc. to EN 60721?3?3 |
Pollution degree 2) acc. to IEC/EN 61800?5?1 | 2 |
Installation altitude | |
- Up to 1000 m (3281 ft) above sea level
| Without derating |
- From 1000 m (3281 ft) up to 2000 m (6562 ft) )above sea level observe the derating characteristics
| - Reduction of the output current by 10 % per 1000 m (3281 ft) or
- Reduction of the ambient temperature by 5 K per 1000 m (3281 ft)
|
- From 2000 m (6562 ft) up to 4000 m (13123 ft) above sea level observe the derating characteristics
| |
| - Reduction of the output current by 10 % per 1000 m (3281 ft) or
- Reduction of the ambient temperature by 5 K per 1000 m (3281 ft)
and additionally: - Operation on line supply systems with grounded neutral point, or
- Operation with an isolating transformer with secondary grounded neutral point
|
| - Reduction of the ambient temperature by 5 K per 1000 m (3281 ft)
|
Mechanical strength |
| Storage | Transport | Operation |
In product packaging | In transport packaging | |
Vibratory load | Class 1M2 acc. to EN 60721?3?1 | Class 2M3 acc. to EN 60721?3?2 | Class 3M1 acc. to EN 60721?3?3 Test values acc. to EN 60068?2?6 : 10 oscillations per axis in the range: 10 ... 57 Hz constant deflection 0.075 mm 57 ... 150 Hz constant acceleration 9.81 m/s2 (1 ? g) |
Shock load | Class 1M2 acc. to EN 60721?3?1 | Class 2M3 acc. to EN 60721?3?2 | Class 3M1 acc. to EN 60721?3?3 Test values acc. to EN 60068?2?27 : 3 shocks per axis in both directions Peak acceleration 49 m/s2 (5 ? g); duration 30 ms |
Certificates |
Declarations of conformity | CE (Low Voltage, EMC and M?achinery Directive) |
Certificates of suitability | cULus |