Overload capabilityDuty cycle with previous load Duty cycle with previous load S6 duty cycle with previous load 20 kW (25 hp) and 40 kW (50 hp) Basic Line Modules only Duty cycle with previous load Derating characteristicsOutput power as a funcction of ambient temperature Installation altitude
Braking power with external braking resistorThe following duty cycles are defined for the braking modules of the 20 kW (25 hp) and 40 kW (50 hp) Basic Line Modules: The maximum possible braking power Pmax is calculated using the following formula: Pmax = U2/R U = Activation threshold R = Resistance value of the external braking resistor The maximum braking power is achieved with the smallest permissible resistance value. The maximum possible braking power falls at larger resistance values. Braking power of the 20 kW (25 hp) Basic Line Modules depending on the connected braking resistor When the recommended braking resistor is used, the following values result for the maximum braking power or continuous braking power: Braking resistor 6SE7023-2ES87-2DC0 Braking power of the 40 kW Basic Line Modules depending on the connected braking resistor When the recommended braking resistor is used, the following values result for the maximum braking power or continuous braking power: Braking resistor 6SE7028-0ES87-2DC0 |