510 ... 720 V DC (line supply voltage 380 ... 480 V 3 AC) or 675 ... 1035 V DC (line supply voltage 500 ... 690 V 3 AC)
Output frequency 1)
Control type Servo
0 … 650 Hz
Control type Vector
0 … 600 Hz
Control type V/f
0 … 600 Hz
Conformity
CE (EMC Directive No. 2004/108/EC and Low-Voltage Directive No. 2006/95/EC)
Approvals, according to
cULus (only for drive units connected to line voltages 380 ... 480 V 3 AC and 500 ... 600 V 3 AC)
Safety Integrated
Safety Integrity Level 2 (SIL2) acc. to IEC 61508, Performance Level d (PLd) acc. to EN ISO 13849-1 and Control Category 3 acc. to EN ISO 13849-1 (previously EN 954-1).
1) Please note: - The correlation between the maximum output frequency, pulse frequency and current derating. Higher output frequencies for specific configurations are available on request. - The correlation between the minimum output frequency and permissible output current (current derating). Information is provided in the SINAMICS Low Voltage Engineering Manual.
Line voltage 380 … 480 V 3 AC DC link voltage 510 … 720 V DC
Motor Modules
6SL3320-1TE32-1AA3
6SL3320-1TE32-6AA3
6SL3320-1TE33-1AA3
6SL3320-1TE33-8AA3
6SL3320-1TE35-0AA3
Type rating
For IL (50 Hz 400 V) 1)
kW
110
132
160
200
250
For IH (50 Hz 400 V) 1)
kW
90
110
132
160
200
For IL (60 Hz 460 V) 2)
hp
150
200
250
300
400
For IH (60 Hz 460 V) 2)
hp
150
200
200
250
350
Output current
Rated current IN A
A
210
260
310
380
490
Base load current IL 3)
A
205
250
302
370
477
Base load current IH 4)
A
178
233
277
340
438
Maximum current Imax A
A
307
375
453
555
715
DC link current
Rated current IN DC when supplied from
Basic/Smart Line Module
A
252
312
372
456
588
Active Line Module
A
227
281
335
411
529
Base load current IL DC 3) when supplied from
Basic/Smart Line Module
A
245
304
362
444
573
Active Line Module
A
221
273
326
400
515
Base load current IH DC 4) when supplied from
Basic/Smart Line Module
A
224
277
331
405
523
Active Line Module
A
202
250
298
365
470
Current demand
24 V DC auxiliary power supply
A
0.8
0.8
0.9
0.9
0.9
400 V AC
A
0.63
1.13
1.8
1.8
1.8
DC link capacitance
?F
4200
5200
6300
7800
9600
Pulse frequency 5)
Rated frequency
kHz
2
2
2
2
2
Pulse frequency, max.
Without current derating
kHz
2
2
2
2
2
With current derating
kHz
8
8
8
8
8
Power loss, max. 6)
At 50 Hz 400 V
kW
1.86
2.5
2.96
3.67
4.28
At 60 Hz 460 V
kW
1.94
2.6
3.1
3.8
4.5
Cooling air requirement
m3/s
0.17
0.23
0.36
0.36
0.36
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
64/67
64/67
69/73
69/73
69/73
DC link connection
DCP, DCN
M10 screw
M10 screw
M10 screw
M10 screw
M10 screw
Conductor cross-section, max. (IEC)
mm2
2 ? 185
2 ? 185
2 ? 240
2 ? 240
2 ? 240
Motor connection
U2, V2, W2
M10 screw
M10 screw
M10 screw
M10 screw
M10 screw
Conductor cross-section, max. (IEC)
mm2
2 ? 185
2 ? 185
2 ? 240
2 ? 240
2 ? 240
Cable length, max. 7)
Shielded
m
300
300
300
300
300
Unshielded
m
450
450
450
450
450
PE1/GND connection
M10 screw
M10 screw
M10 screw
M10 screw
M10 screw
Conductor cross-section, max. (IEC)
mm2
2 ? 185
2 ? 185
2 ? 240
2 ? 240
2 ? 240
PE2/GND connection
M10 screw
M10 screw
M10 screw
M10 screw
M10 screw
Conductor cross-section, max. (IEC)
mm2
2 ? 185
2 ? 185
2 ? 240
2 ? 240
2 ? 240
Degree of protection
IP20
IP20
IP20
IP20
IP20
Dimensions
Width
mm
326
326
326
326
326
Height
mm
1400
1400
1533
1533
1533
Depth
mm
356
356
545
545
545
Weight, approx.
kg
95
95
136
136
136
Frame size
FX
FX
GX
GX
GX
1) Rated power of a typ. 6-pole standard induction motor based on IL or IH with 400 V 3 AC 50 Hz.
2) Rated power of a typ. 6-pole standard induction motor based on IL or IH with 460 V 3 AC 60 Hz.
3) The base load current IL is the basis for a duty cycle of 110 % for 60 s or 150 % for 10 s with a duty cycle duration of 300 s.
4) The base load current IH is the basis for a duty cycle of 150 % for 60 s or 160 % for 10 s with a duty cycle duration of 300 s.
5)Information regarding the correlation between the pulse frequency and maximum output current/output frequency is provided in the SINAMICS Low Voltage Engineering Manual.
6) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions.
7) Sum of all motor cables and DC link. Longer cable lengths for specific configurations are available on request. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.
Line voltage 380 … 480 V 3 AC DC link voltage 510 … 720 V DC
Motor Modules
6SL3320-1TE36-1AA3
6SL3320-1TE37-5AA3
6SL3320-1TE38-4AA3
Type rating
For IL (50 Hz 400 V) 1)
kW
315
400
450
For IH (50 Hz 400 V) 1)
kW
250
315
400
For IL (60 Hz 460 V) 2)
hp
500
600
700
For IH (60 Hz 460 V) 2)
hp
350
450
600
Output current
Rated current IN A
A
605
745
840
Base load current IL 3)
A
590
725
820
Base load current IH 4)
A
460
570
700
Maximum current Imax A
A
885
1087
1230
DC link current
Rated current IN DC when supplied from
Basic/Smart Line Module
A
726
894
1008
Active Line Module
A
653
805
907
Base load current IL DC 3) when supplied from
Basic/Smart Line Module
A
707
871
982
Active Line Module
A
636
784
884
Base load current IH DC 4) when supplied from
Basic/Smart Line Module
A
646
795
897
Active Line Module
A
581
716
807
Current demand
24 V DC auxiliary power supply
A
1.0
1.0
1.0
400 V AC
A
3.6
3.6
3.6
DC link capacitance
?F
12600
15600
16800
Pulse frequency
Rated frequency
kHz
1.25
1.25
1.25
Pulse frequency, max.
Without current derating
kHz
1.25
1.25
1.25
With current derating
kHz
7.5
7.5
7.5
Power loss, max. 6)
At 50 Hz 400 V
kW
5.84
6.68
7.15
At 60 Hz 460 V
kW
6.3
7.3
7.8
Cooling air requirement
m3/s
0.78
0.78
0.78
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
70/73
70/73
70/73
DC link connection
DCP, DCN
4 ? hole for M10 Busbar
4 ? hole for M10 Busbar
4 ? hole for M10 Busbar
Motor connection
U2, V2, W2
2 ? M12 screw
2 ? M12 screw
2 ? M12 screw
Conductor cross-section, max. (IEC)
mm2
4 ? 240
4 ? 240
4 ? 240
Cable length, max. 7)
Shielded
m
300
300
300
Unshielded
m
450
450
450
PE1/GND connection
M12 screw
M12 screw
M12 screw
Conductor cross-section, max. (IEC)
mm2
240
240
240
PE2/GND connection
2 ? M12 screw
2 ? M12 screw
2 ? M12 screw
Conductor cross-section, max. (IEC)
mm2
2 ? 240
2 ? 240
2 ? 240
Degree of protection
IP00
IP00
IP00
Dimensions
Width
mm
503
503
503
Height
mm
1475
1475
1475
Depth
mm
547
547
547
Weight, approx.
kg
290
290
290
Frame size
HX
HX
HX
1) Rated power of a typ. 6-pole standard induction motor based on IL or IH with 400 V 3 AC 50 Hz.
2) Rated power of a typ. 6-pole standard induction motor based on IL or IH with 460 V 3 AC 60 Hz.
3) The base load current IL is the basis for a duty cycle of 110 % for 60 s or 150 % for 10 s with a duty cycle duration of 300 s.
4) The base load current IH is the basis for a duty cycle of 150 % for 60 s or 160 % for 10 s with a duty cycle duration of 300 s.
5)Information regarding the correlation between the pulse frequency and maximum output current/output frequency is provided in the SINAMICS Low Voltage Engineering Manual.
6) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions.
7) Sum of all motor cables and DC link. Longer cable lengths for specific configurations are available on request. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.
Line voltage 380 … 480 V 3 AC DC link voltage 510 … 720 V DC
Motor Modules
6SL3320-1TE41-0AA3
6SL3320-1TE41-2AA3
6SL3320-1TE41-4AA3
Type rating
For IL (50 Hz 400 V) 1)
kW
560
710
800
For IH (50 Hz 400 V) 1)
kW
450
560
710
For IL (60 Hz 460 V) 2)
hp
800
1000
1150
For IH (60 Hz 460 V) 2)
hp
700
900
1000
Output current
Rated current IN A
A
985
1260
1405
Base load current IL 3)
A
960
1230
1370
Base load current IH 4)
A
860
1127
1257
Maximum current Imax A
A
1440
1845
2055
DC link current
Rated current IN DC when supplied from
Basic/Smart Line Module
A
1182
1512
1686
Active Line Module
A
1064
1361
1517
Base load current IL DC 3) when supplied from
Basic/Smart Line Module
A
1152
1474
1643
Active Line Module
A
1037
1326
1479
Base load current IH DC4) when supplied from
Basic/Smart Line Module
A
1051
1345
1500
Active Line Module
A
946
1211
1350
Current demand
24 V DC auxiliary power supply
A
1.25
1.40
1.40
400 V AC
A
5.4
5.4
5.4
DC link capacitance
?F
18900
26100
28800
Pulse frequency 5)
Rated pulse frequency
kHz
1.25
1.25
1.25
Pulse frequency, max.
Without current derating
kHz
1.25
1.25
1.25
With current derating
kHz
7.5
7.5
7.5
Power loss, max. 6)
At 50 Hz 400 V
kW
9.5
11.1
12.0
At 60 Hz 460 V
kW
10.2
12.0
13.0
Cooling air requirement
m3/s
1.1
1.1
1.1
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
71/73
71/73
71/73
DC link connection
DCP, DCN
4 ? hole for M10 Busbar
4 ? hole for M10 Busbar
4 ? hole for M10 Busbar
Motor connection
U2, V2, W2
3 ? M12 screw
3 ? M12 screw
3 ? M12 screw
Conductor cross-section, max. (IEC)
mm2
6 ? 240
6 ? 240
6 ? 240
Cable length, max. 7)
Shielded
m
300
300
300
Unshielded
m
450
450
450
PE1/GND connection
M12 screw
M12 screw
M12 screw
Conductor cross-section, max. (IEC)
mm2
240
240
240
PE2/GND connection
3 ? M12 screw
3 ? M12 screw
3 ? M12 screw
Conductor cross-section, max. (IEC)
mm2
3 ? 240
3 ? 240
3 ? 240
Degree of protection
IP00
IP00
IP00
Dimensions
Width
mm
704
704
704
Height
mm
1475
1475
1475
Depth
mm
549
549
549
Weight, approx.
kg
450
450
450
Frame size
JX
JX
JX
1) Rated power of a typ. 6-pole standard induction motor based on IL or IH with 400 V 3 AC 50 Hz.
2) Rated power of a typ. 6-pole standard induction motor based on IL or IH with 460 V 3 AC 60 Hz.
3) The base load current IL is the basis for a duty cycle of 110 % for 60 s or 150 % for 10 s with a duty cycle duration of 300 s.
4) The base load current IH is the basis for a duty cycle of 150 % for 60 s or 160 % for 10 s with a duty cycle duration of 300 s.
5)Information regarding the correlation between the pulse frequency and maximum output current/output frequency is provided in the SINAMICS Low Voltage Engineering Manual.
6) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions.
7) Sum of all motor cables and DC link. Longer cable lengths for specific configurations are available on request. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.
Line voltage 500 … 690 V 3 AC DC link voltage 675 … 1035 V DC
Motor Modules
6SL3320-1TG28-5AA3
6SL3320-1TG31-0AA3
6SL3320-1TG31-2AA3
6SL3320-1TG31-5AA3
Type rating
For IL (50 Hz 690 V) 1)
kW
75
90
110
132
For IH (50 Hz 690 V) 1)
kW
55
75
90
110
For IL (50 Hz 500 V) 1)
kW
55
55
75
90
For IH (50 Hz 500 V) 1)
kW
45
55
75
90
For IL (60 Hz 575 V) 2)
hp
75
75
100
150
For IH (60 Hz 575 V) 2)
hp
75
75
100
125
Output current
Rated current IN A
A
85
100
120
150
Base load current IL 3)
A
80
95
115
142
Base load current IH 4)
A
76
89
107
134
Maximum current Imax A
A
120
142
172
213
DC link current
Rated current IN DC when supplied from
Basic/Smart Line Module
A
102
120
144
180
Active Line Module
A
92
108
130
162
Base load current IL DC 3) when supplied from
Basic/Smart Line Module
A
99
117
140
175
Active Line Module
A
89
105
126
157
Base load current IH DC 4) when supplied from
Basic/Smart Line Module
A
90
106
128
160
Active Line Module
A
81
96
115
144
Current demand
24 V DC auxiliary power supply
A
0.8
0.8
0.8
0.8
500 V AC
A
0.7
0.7
0.7
0.7
690 V AC
A
0.4
0.4
0.4
0.4
DC link capacitance
?F
1200
1200
1600
2800
Pulse frequency 5)
Rated frequency
kHz
1.25
1.25
1.25
1.25
Pulse frequency, max.
Without current derating
kHz
1.25
1.25
1.25
1.25
With current derating
kHz
7.5
7.5
7.5
7.5
Power loss, max. 6)
At 50 Hz 690 V
kW
1.17
1.43
1.89
1.80
At 60 Hz 575 V
kW
1.1
1.3
1.77
1.62
Cooling air requirement
m3/s
0.17
0.17
0.17
0.17
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
64/67
64/67
64/67
64/67
DC link connection
DCP, DCN
M10 screw
M10 screw
M10 screw
M10 screw
Conductor cross-section, max. (IEC)
mm2
2 ? 185
2 ? 185
2 ? 185
2 ? 185
Motor connection
U2, V2, W2
M10 screw
M10 screw
M10 screw
M10 screw
Conductor cross-section, max. (IEC)
mm2
2 ? 185
2 ? 185
2 ? 185
2 ? 185
Cable length, max. 7)
Shielded
m
300
300
300
300
Unshielded
m
450
450
450
450
PE1/GND connection
M10 screw
M10 screw
M10 screw
M10 screw
Conductor cross-section, max. (IEC)
mm2
2 ? 185
2 ? 185
2 ? 185
2 ? 185
PE2/GND connection
M10 screw
M10 screw
M10 screw
M10 screw
Conductor cross-section, max. (IEC)
mm2
2 ? 185
2 ? 185
2 ? 185
2 ? 185
Degree of protection
IP20
IP20
IP20
IP20
Dimensions
Width
mm
326
326
326
326
Height
mm
1400
1400
1400
1400
Depth
mm
356
356
356
356
Weight, approx.
kg
95
95
95
95
Frame size
FX
FX
FX
FX
1) Rated power of a typ. 6-pole standard induction motor based on IL or IH at 500 V or 690 V 3 AC 50 Hz.
2) Rated power of a typ. 6-pole standard induction motor based on IL or IH at 575 V 3 AC 60 Hz.
3) The base load current IL is the basis for a duty cycle of 110 % for 60 s or 150 % for 10 s with a duty cycle duration of 300 s.
4) The base load current IH is the basis for a duty cycle of 150 % for 60 s or 160 % for 10 s with a duty cycle duration of 300 s.
5)Information regarding the correlation between the pulse frequency and maximum output current/output frequency is provided in the SINAMICS Low Voltage Engineering Manual.
6) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions.
7) Sum of all motor cables and DC link. Longer cable lengths for specific configurations are available on request. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.
Line voltage 500 … 690 V 3 AC DC link voltage 675 … 1035 V DC
Motor Modules
6SL3320-1TG31-8AA3
6SL3320-1TG32-2AA3
6SL3320-1TG32-6AA3
6SL3320-1TG33-3AA3
Type rating
For IL (50 Hz 690 V) 1)
kW
160
200
250
315
For IH (50 Hz 690 V) 1)
kW
132
160
200
250
For IL (50 Hz 500 V) 1)
kW
110
132
160
200
For IH (50 Hz 500 V) 1)
kW
90
110
132
160
For IL (60 Hz 575 V) 2)
hp
150
200
250
300
For IH (60 Hz 575 V) 2)
hp
150
200
200
250
Output current
Rated current IN A
A
175
215
260
330
Base load current IL 3)
A
171
208
250
320
Base load current IH 4)
A
157
192
233
280
Maximum current Imax A
A
255
312
375
480
DC link current
Rated current IN DC when supplied from
Basic/Smart Line Module
A
210
258
312
396
Active Line Module
A
189
232
281
356
Base load current IL DC 3) when supplied from
Basic/Smart Line Module
A
204
251
304
386
Active Line Module
A
184
226
273
347
Base load current IH DC 4) when supplied from
Basic/Smart Line Module
A
186
229
277
352
Active Line Module
A
168
206
250
316
Current demand
24 V DC auxiliary power supply
A
0.9
0.9
0.9
0.9
500 V AC
A
1.5
1.5
1.5
1.5
690 V AC
A
1.0
1.0
1.0
1.0
DC link capacitance
?F
2800
2800
3900
4200
Pulse frequency
Rated frequency
kHz
1.25
1.25
1.25
1.25
Pulse frequency, max.
Without current derating
kHz
1.25
1.25
1.25
1.25
With current derating
kHz
7.5
7.5
7.5
7.5
Power loss, max. 6)
At 50 Hz 690 V
kW
2.67
3.09
3.62
4.34
At 60 Hz 575 V
kW
2.5
2.91
3.38
3.98
Cooling air requirement
m3/s
0.36
0.36
0.36
0.36
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
69/73
69/73
69/73
69/73
DC link connection
DCP, DCN
M10 screw
M10 screw
M10 screw
M10 screw
Conductor cross-section, max. (IEC)
mm2
2 ? 240
2 ? 240
2 ? 240
2 ? 240
Motor connection
U2, V2, W2
M10 screw
M10 screw
M10 screw
M10 screw
Conductor cross-section, max. (IEC)
mm2
2 ? 240
2 ? 240
2 ? 240
2 ? 240
Cable length, max. 7)
Shielded
m
300
300
300
300
Unshielded
m
450
450
450
450
PE1/GND connection
M10 screw
M10 screw
M10 screw
M10 screw
Conductor cross-section, max. (IEC)
mm2
2 ? 240
2 ? 240
2 ? 240
2 ? 240
PE2/GND connection
M10 screw
M10 screw
M10 screw
M10 screw
Conductor cross-section, max. (IEC)
mm2
2 ? 240
2 ? 240
2 ? 240
2 ? 240
Degree of protection
IP20
IP20
IP20
IP20
Dimensions
Width
mm
326
326
326
326
Height
mm
1533
1533
1533
1533
Depth
mm
545
545
545
545
Weight, approx.
kg
136
136
136
136
Frame size
GX
GX
GX
GX
1) Rated power of a typ. 6-pole standard induction motor based on IL or IH at 500 V or 690 V 3 AC 50 Hz.
2) Rated power of a typ. 6-pole standard induction motor based on IL or IH at 575 V 3 AC 60 Hz.
3) The base load current IL is the basis for a duty cycle of 110 % for 60 s or 150 % for 10 s with a duty cycle duration of 300 s.
4) The base load current IH is the basis for a duty cycle of 150 % for 60 s or 160 % for 10 s with a duty cycle duration of 300 s.
5)Information regarding the correlation between the pulse frequency and maximum output current/output frequency is provided in the SINAMICS Low Voltage Engineering Manual.
6) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions.
7) Sum of all motor cables and DC link. Longer cable lengths for specific configurations are available on request. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.
Line voltage 500 … 690 V 3 AC DC link voltage 675 … 1035 V DC
Motor Modules
6SL3320-1TG34-1AA3
6SL3320-1TG34-7AA3
6SL3320-1TG35-8AA3
6SL3320-1TG37-4AA3
Type rating
For IL (50 Hz 690 V) 1)
kW
400
450
560
710
For IH (50 Hz 690 V) 1)
kW
315
400
450
630
For IL (50 Hz 500 V) 1)
kW
250
315
400
500
For IH (50 Hz 500 V) 1)
kW
200
250
315
450
For IL (60 Hz 575 V) 2)
hp
400
450
600
700
For IH (60 Hz 575 V) 2)
hp
350
450
500
700
Output current
Rated current IN A
A
410
465
575
735
Base load current IL 3)
A
400
452
560
710
Base load current IH 4)
A
367
416
514
657
Maximum current Imax A
A
600
678
840
1065
DC link current
Rated current IN DC when supplied from
Basic/Smart Line Module
A
492
558
690
882
Active Line Module
A
443
502
621
794
Base load current IL DC 3) when supplied from
Basic/Smart Line Module
A
479
544
672
859
Active Line Module
A
431
489
605
774
Base load current IH DC 4) when supplied from
Basic/Smart Line Module
A
437
496
614
784
Active Line Module
A
394
446
552
706
Current demand
24 V DC auxiliary power supply
A
1.0
1.0
1.0
1.25
500 V AC
A
3.0
3.0
3.0
4.4
690 V AC
A
2.1
2.1
2.1
3.1
DC link capacitance
?F
7400
7400
7400
11100
Pulse frequency 5)
Rated frequency
kHz
1.25
1.25
1.25
1.25
Pulse frequency, max.
Without current derating
kHz
1.25
1.25
1.25
1.25
With current derating
kHz
7.5
7.5
7.5
7.5
Power loss, max. 6)
At 50 Hz 690 V
kW
6.13
6.80
10.3
10.9
At 60 Hz 575 V
kW
5.71
6.32
9.7
10
Cooling air requirement
m3/s
0.78
0.78
0.78
1.474
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
70/73
70/73
70/73
71/73
DC link connection
DCP, DCN
4 ? hole for M10 Busbar
4 ? hole for M10 Busbar
4 ? hole for M10 Busbar
4 ? hole for M10 Busbar
Motor connection
U2, V2, W2
2 ? M12 screw
2 ? M12 screw
2 ? M12 screw
3 ? M12 screw
Conductor cross-section, max. (IEC)
mm2
4 ? 240
4 ? 240
4 ? 240
6 ? 240
Cable length, max. 7)
Shielded
m
300
300
300
300
Unshielded
m
450
450
450
450
PE1/GND connection
M12 screw
M12 screw
M12 screw
M12 screw
Conductor cross-section, max. (IEC)
mm2
240
240
240
240
PE2/GND connection
2 ? M12 screw
2 ? M12 screw
2 ? M12 screw
3 ? M12 screw
Conductor cross-section, max. (IEC)
mm2
2 ? 240
2 ? 240
2 ? 240
3 ? 240
Degree of protection
IP00
IP00
IP00
IP00
Dimensions
Width
mm
503
503
503
704
Height
mm
1475
1475
1475
1475
Depth
mm
547
547
547
550
Weight, approx.
kg
290
290
290
450
Frame size
HX
HX
HX
JX
1) Rated power of a typ. 6-pole standard induction motor based on IL or IH at 500 V or 690 V 3 AC 50 Hz.
2) Rated power of a typ. 6-pole standard induction motor based on IL or IH at 575 V 3 AC 60 Hz.
3) The base load current IL is the basis for a duty cycle of 110 % for 60 s or 150 % for 10 s with a duty cycle duration of 300 s.
4) The base load current IH is the basis for a duty cycle of 150 % for 60 s or 160 % for 10 s with a duty cycle duration of 300 s.
5)Information regarding the correlation between the pulse frequency and maximum output current/output frequency is provided in the SINAMICS Low Voltage Engineering Manual.
6) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions.
7) Sum of all motor cables and DC link. Longer cable lengths for specific configurations are available on request. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.
Line voltage 500 … 690 V 3 AC DC link voltage 675 … 1035 V DC
Motor Modules
6SL3320-1TG38-1AA3
6SL3320-1TG38-8AA3
6SL3320-1TG41-0AA3
6SL3320-1TG41-3AA3
Type rating
For IL (50 Hz 690 V) 1)
kW
800
900
1000
1200
For IH (50 Hz 690 V) 1)
kW
710
800
900
1000
For IL (50 Hz 500 V) 1)
kW
560
630
710
900
For IH (50 Hz 500 V) 1)
kW
500
560
630
800
For IL (60 Hz 575 V) 2)
hp
800
900
1000
1250
For IH (60 Hz 575 V) 2)
hp
700
800
900
1000
Output current
Rated current IN A
A
810
910
1025
1270
Base load current IL 3)
A
790
880
1000
1230
Base load current IH 4)
A
724
814
917
1136
Maximum current Imax A
A
1185
1320
1500
1845
DC link current
Rated current IN DC when supplied from
Basic/Smart Line Module
A
972
1092
1230
1524
Active Line Module
A
875
983
1107
1372
Base load current IL DC 3) when supplied from
Basic/Smart Line Module
A
947
1064
1199
1485
Active Line Module
A
853
958
1079
1337
Base load current IH DC 4) when supplied from
Basic/Smart Line Module
A
865
971
1094
1356
Active Line Module
A
778
874
985
1221
Current demand
24 V DC auxiliary power supply
A
1.25
1.4
1.4
1.4
500 V AC
A
4.4
4.4
4.4
4.4
690 V AC
A
3.1
3.1
3.1
3.1
DC link capacitance
?F
11100
14400
14400
19200
Pulse frequency 5)
Rated frequency
kHz
1.25
1.25
1.25
1.25
Pulse frequency, max.
Without current derating
kHz
1.25
1.25
1.25
1.25
With current derating
kHz
7.5
7.5
7.5
7.5
Power loss, max. 6)
At 50 Hz 690 V
kW
11.5
11.7
13.2
16.0
At 60 Hz 575 V
kW
10.5
10.6
12.0
14.2
Cooling air requirement
m3/s
1.474
1.474
1.474
1.474
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
71/73
71/73
71/73
71/73
DC link connection
DCP, DCN
4 ? hole for M10 Busbar
4 ? hole for M10 Busbar
4 ? hole for M10 Busbar
4 ? hole for M10 Busbar
Motor connection
U2, V2, W2
3 ? M12 screw
3 ? M12 screw
3 ? M12 screw
3 ? M12 screw
Conductor cross-section, max. (IEC)
mm2
6 ? 240
6 ? 240
6 ? 240
6 ? 240
Cable length, max. 7)
Shielded
m
300
300
300
300
Unshielded
m
450
450
450
450
PE1/GND connection
M12 screw
M12 screw
M12 screw
M12 screw
Conductor cross-section, max. (IEC)
mm2
240
240
240
240
PE2/GND connection
3 ? M12 screw
3 ? M12 screw
3 ? M12 screw
3 ? M12 screw
Conductor cross-section, max. (IEC)
mm2
3 ? 240
3 ? 240
3 ? 240
3 ? 240
Degree of protection
IP00
IP00
IP00
IP00
Dimensions
Width
mm
704
704
704
704
Height
mm
1480
1480
1480
1475
Depth
mm
549
549
549
550
Weight, approx.
kg
450
450
450
450
Frame size
JX
JX
JX
JX
1) Rated power of a typ. 6-pole standard induction motor based on IL or IH at 500 V or 690 V 3 AC 50 Hz.
2) Rated power of a typ. 6-pole standard induction motor based on IL or IH at 575 V 3 AC 60 Hz.
3) The base load current IL is the basis for a duty cycle of 110 % for 60 s or 150 % for 10 s with a duty cycle duration of 300 s.
4) The base load current IH is the basis for a duty cycle of 150 % for 60 s or 160 % for 10 s with a duty cycle duration of 300 s.
5) Information regarding the correlation between the pulse frequency and maximum output current/output frequency is provided in the SINAMICS Low Voltage Engineering Manual.
6) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions.
7) Sum of all motor cables and DC link. Longer cable lengths for specific configurations are available on request. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.
skener.ru
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Àðìàòóðà DENDOR
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Äàò÷èêè è èçìåðèòåëè
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ðåãóëÿòîðû è ðåãèñòðàòîðû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ïíåâìàòè÷åñêîå îáîðóäîâàíèå
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Êðàíû è Êëàïàíû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Èçìåðèòåëüíûå ïðèáîðû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ñèñòåìû áåñïðîâîäíîãî óïðàâëåíèÿ «óìíûé äîì»
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Áåñêîíòàêòíûå âûêëþ÷àòåëè Êîíå÷íûå âûêëþ÷àòåëè Îïòè÷åñêèå äàò÷èêè Ýíêîäåðû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FS - Óñòàíîâêà óìÿã÷åíèÿ
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FK - Óñòàíîâêà îáåçæåëåçèâàíèÿ