Rated voltages | 380 ... 480 V 3 AC, ±10 % (-15 % < 1 min) 500 ... 690 V 3 AC, ±10 % (-15 % < 1 min) |
Line supply types | Grounded TN/TT systems and non-grounded IT systems |
Line frequency | 47 ... 63 Hz |
Overvoltage category | III to EN 61800-5-1 |
Electronics power supply | 24 V DC, -15 % +20 % implemented as PELV circuit in accordance with EN 61800-5-1 Ground = negative pole grounded via the electronics |
Rated short-circuit current SCCR (Short Circuit Current Rating) according to UL508C (up to 600 V), in conjunction with the specified fuses or circuit breakers Rated power | |
| 65 kA |
| 84 kA |
| 170 kA |
| 200 kA |
Control method | Vector/servo control with and without encoder or V/f control |
Fixed speeds | 15 fixed speeds plus 1 minimum speed, parameterizable (in the default setting, 3 fixed setpoints plus 1 minimum speed are selectable using terminal block/PROFIBUS/PROFINET) |
Skipped speed ranges | 4, parameterizable |
Setpoint resolution | 0.001 rpm digital (14 bits + sign) 12 bit analog |
Braking operation | With Active Line Modules and Smart Line Modules, four-quadrant operation as standard (energy recovery). With Basic Line Modules, single-quadrant operation as standard. Braking when the power fails using an optional braking module. |
Mechanical specifications |
Degree of protection | IP00 or IP20 dependent on type |
Protection class | I acc. to EN 61800?5?1 |
Touch protection | EN 50274 / BGV A3 for the intended purpose |
Type of cooling | Forced air cooling through built-in fan |
Ambient conditions | Storage 1) | Transport 1) | Operation |
Ambient temperature | -40 ... +70 °C Class 1K3 acc. to EN 60721-3-1 | -40 ... +70 °C Class 2K4 acc. to EN 60721-3-2 | Line-side components, Power Modules, Line Modules and Motor Modules: 0 … 40 °C without derating Up to +50 °C, see derating data Control Units, supplementary system components, DC link components and Sensor Modules 0 … 50 °C |
Relative humidity Condensation, splashwater, and ice formation not permitted (EN 60204, Part 1) | 5 ... 95 % 2) Class 1K4 acc. to EN 60721?3?1 | 5 ... 95 % at 40 °C Class 2K3 acc. to EN 60721?3?2 | 5 ... 95 % 2) Class 3K3 acc. to EN 60721?3?3 |
Environmental class/harmful chemical substances | Class 1C2 acc. to EN 60721?3?1 | Class 2C2 acc. to EN 60721?3?2 | Class 3C2 acc. to EN 60721?3?3 |
Organic/biological influences | Class 1B1 acc. to EN 60721?3?1 | Class 2B1 acc. to EN 60721?3?2 | Class 3B1 acc. to EN 60721?3?3 |
Degree of pollution | 2 acc. to EN 61800?5?1 | 2 acc. to EN 61800?5?1 | 2 acc. to EN 61800?5?1 |
Installation altitude | Up to 2000 m above sea level without derating > 2000 m above sea level, see derating data |
Mechanical stability | Storage 1) | Transport 1) | Operation |
Vibration load | – | Class 2M2 acc. to EN 60721?3?2 | Test values acc. to EN 60068-2-6 test Fc: - 10 ... 58 Hz with constant deflection 0.075 mm
- 58 ... 150 Hz with the constant acceleration 9.81 m/s2 (1 ? g)
|
Shock load | – | Class 2M2 acc. to EN 60721?3?2 | Test values acc. to EN 60068?2?27 test Ea: 98 m/s2 (10 ? g)/20 ms |
Compliance with standards |
Conformances/ approvals, according to | CE (EMC Directive No. 2004/108/EC and Low-Voltage Directive No. 2006/95/EC) cULus (only for devices connected to line supply voltages 380 ... 480 V 3 AC and 500 ... 600 V 3 AC) |
Radio interference suppression | SINAMICS drive converter systems are not designed for connection to the public network (first environment). Radio interference suppression is compliant with the EMC product standard for variable-speed drives EN 61800-3, "Second environment" (industrial line supplies). The equipment can cause electromagnetic interference when it is connected to the public network. However, if supplementary measures are taken (e.g. > line filter), it can also be operated in the "first environment". |