Данные ухудшения характеристик
Частота импульсов
Ном. мощность |
Ном. выходной ток в A при частоте импульсов в |
|||||||
---|---|---|---|---|---|---|---|---|
кВт |
л.с. |
4 кГц |
6 кГц |
8 кГц |
10 кГц |
12 кГц |
14 кГц |
16 кГц |
0.55 1) |
0.75 |
1.7 |
1.4 |
1.2 |
1.0 |
0.9 |
0.8 |
0.7 |
0.75 1) |
1.0 |
2.2 |
1.9 |
1.5 |
1.3 |
1.1 |
1.0 |
0.9 |
1.1 1) |
1.5 |
3.1 |
2.6 |
2.2 |
1.9 |
1.6 |
1.4 |
1.2 |
1.5 1) |
2.0 |
4.1 |
3.5 |
2.9 |
2.5 |
2.1 |
1.8 |
1.6 |
2.2 1) |
3.0 |
5.6 |
4.8 |
3.9 |
3.4 |
2.8 |
2.5 |
2.2 |
3.0 1) |
4.0 |
7.3 |
6.2 |
5.1 |
4.4 |
3.7 |
3.3 |
2.9 |
4.0 1) |
5.0 |
8.8 |
7.5 |
6.2 |
5.3 |
4.4 |
4.0 |
3.5 |
5.5 |
7.5 |
12.5 |
10.6 |
8.8 |
7.5 |
6.3 |
5.6 |
5.0 |
7.5 |
10 |
16.5 |
14.0 |
11.6 |
9.9 |
8.3 |
7.4 |
6.6 |
11.0 |
15 |
25.0 |
21.3 |
17.5 |
15.0 |
12.5 |
11.3 |
10.0 |
15.0 |
20 |
31.0 |
26.4 |
21.7 |
18.6 |
15.5 |
14.0 |
12.4 |
18.5 |
25 |
37.0 |
31.5 |
25.9 |
22.2 |
18.5 |
16.7 |
14.8 |
1) The permissible motor cable length depends on the cable type and the pulse frequency.
Температура окружающей среды
Высокая перегрузка (High overload HO) и низкая перегрузка (low overload LO)
Высота места установки
Доп. выходной ток в зависимости от высоты места установки
Доп. входное напряжение в зависимости от высоты места установки
Напряжение сети
Доп. выходной ток в зависимости от напряжения сети
Доп. ном. мощность в зависимости от напряжения сети