The fuses specified below are the recommended types for protecting the unit on the low-voltage distribution panel. If optionL26(main switch or circuit-breaker) has been selected, the converter itself will provide semiconductor protection. In this case, a fuse of type 3NA can be used on the low-voltage distribution panel.
If optionL26has not been selected, we strongly advise use of fuses of type 3NE1).
Further information about the line contactors, switch disconnectors, fuses and circuit-breakers specified in the tables can be found in Catalogs LV 1 and LV 1 T.
Single circuit
Type rating |
SINAMICS G150 converter |
Fuse |
Fuse | |||||
---|---|---|---|---|---|---|---|---|
(at 400 V, 500 V or 690 V) |
(at 60 Hz 460 V or 575 V) |
Rated current |
Frame size in accordance with DIN 43620?1 |
Rated current |
Frame size in accordance with DIN 43620?1 | |||
kW |
hp |
6SL3710? ... |
Type |
A |
Type |
A |
||
380 ... 480 V 3 AC | ||||||||
110 |
150 |
1GE32?1 . A0 |
3NA3144 |
250 |
2 |
3NE1230?2 |
315 |
1 |
132 |
200 |
1GE32?6 . A0 |
3NA3250 |
300 |
2 |
3NE1331?2 |
350 |
2 |
160 |
250 |
1GE33?1 . A0 |
3NA3254 |
355 |
3 |
3NE1334?2 |
500 |
2 |
200 |
300 |
1GE33?8 . A0 |
3NA3260 |
400 |
3 |
3NE1334?2 |
500 |
2 |
250 |
400 |
1GE35?0 . A0 |
3NA3372 |
630 |
3 |
3NE1436?2 |
630 |
3 |
315 |
500 |
1GE36?1 . A0 |
3NA3475 |
800 |
4 |
3NE1438?2 |
800 |
3 |
400 |
600 |
1GE37?5 . A0 |
3NA3475 |
800 |
4 |
3NE1448?2 |
850 |
3 |
450 |
600 |
1GE38?4 . A0 |
3NA3365 |
2 x 500 |
3 |
3NE1436-2 |
2 x 630 |
3 |
560 |
800 |
1GE41?0 . A0 |
3NA3472 |
2 x 630 |
3 |
3NE1437-2 |
2 x 710 |
3 |
500 ... 600 V 3 AC | ||||||||
110 |
150 |
1GF31?8 . A0 |
3NA3244?6 |
250 |
2 |
3NE1227?2 |
250 |
1 |
132 |
200 |
1GF32?2 . A0 |
3NA3252?6 |
315 |
2 |
3NE1230?2 |
315 |
1 |
160 |
250 |
1GF32?6 . A0 |
3NA3354?6 |
355 |
3 |
3NE1331?2 |
350 |
2 |
200 |
300 |
1GF33?3 . A0 |
3NA3365?6 |
500 |
3 |
3NE1334?2 |
500 |
2 |
250 |
400 |
1GF34?1 . A0 |
3NA3365?6 |
500 |
3 |
3NE1334?2 |
500 |
2 |
315 |
450 |
1GF34?7 . A0 |
3NA3352?6 |
2 ? 315 |
3 |
3NE1435?2 |
560 |
3 |
400 |
500 |
1GF35?8 . A0 |
3NA3354?6 |
2 ? 355 |
3 |
3NE1447?2 |
670 |
3 |
500 |
700 |
1GF37?4 . A0 |
3NA3365?6 |
2 ? 500 |
3 |
3NE1448?2 |
850 |
3 |
560 |
800 |
1GF38?1 . A0 |
3NA3365?6 |
2 ? 500 |
3 |
3NE1343?2 |
2 ? 500 |
2 |
660 ... 690 V 3 AC | ||||||||
75 |
1GH28?5 . A0 |
3NA3132?6 |
125 |
1 |
3NE1022?2 |
125 |
00 | |
90 |
1GH31?0 . A0 |
3NA3132?6 |
125 |
1 |
3NE1022?2 |
125 |
00 | |
110 |
1GH31?2 . A0 |
3NA3136?6 |
160 |
1 |
3NE1224?2 |
160 |
1 | |
132 |
1GH31?5 . A0 |
3NA3240?6 |
200 |
2 |
3NE1225?2 |
200 |
1 | |
160 |
1GH31?8 . A0 |
3NA3244?6 |
250 |
2 |
3NE1227?2 |
250 |
1 | |
200 |
1GH32?2 . A0 |
3NA3252?6 |
315 |
2 |
3NE1230?2 |
315 |
1 | |
250 |
1GH32?6 . A0 |
3NA3354?6 |
355 |
3 |
3NE1331?2 |
350 |
2 | |
315 |
1GH33?3 . A0 |
3NA3365?6 |
500 |
3 |
3NE1334?2 |
500 |
2 | |
400 |
1GH34?1 . A0 |
3NA3365?6 |
500 |
3 |
3NE1334?2 |
500 |
2 | |
450 |
1GH34?7 . A0 |
3NA3352?6 |
2 ? 315 |
3 |
3NE1435?2 |
560 |
3 | |
560 |
1GH35?8 . A0 |
3NA3354?6 |
2 ? 355 |
3 |
3NE1447?2 |
670 |
3 | |
710 |
1GH37?4 . A0 |
3NA3365?6 |
2 ? 500 |
3 |
3NE1448?2 |
850 |
3 | |
800 |
1GH38?1 . A0 |
3NA3365?6 |
2 ? 500 |
3 |
3NE1334?2 |
2 ? 500 |
2 |
Note: The type rating data in hp units are based on the NEC/CEC standards for the North American market.
1) The combined fuses (3NE1., gS class) for cable and semiconductor protection are recommended to protect the converter. These fuses are specially adapted to the requirements of the semiconductors in the input rectifier.
- Superfast
- Adapted to the limit current integral of the semiconductor
- Low arc voltage
- Improved current limiting (lower let-through values).
Note: The type rating data in hp units are based on the NEC/CEC standards for the North American market.
Parallel circuit
(data per converter subsystem)
Type rating |
SINAMICS G150 converter |
Fuse withexisting fuse switch disconnector (option L26) |
Fuse (with semiconductor protection effect)withoutfuse switch disconnector | |||||
---|---|---|---|---|---|---|---|---|
(at 400 V, 500 V or 690 V) |
(at 60 Hz 460 V or 575 V) |
Rated current |
Frame size in accordance with DIN 43620?1 |
Rated current |
Frame size in accordance with DIN 43620?1 | |||
kW |
hp |
6SL3710? ... |
Type |
A |
Type |
A |
||
380 ... 480 V 3 AC | ||||||||
630 |
900 |
2GE41?1AA0 |
3NA3475 |
800 |
4 |
3NE1438?2 |
800 |
3 |
710 |
1200 |
2GE41?4AA0 |
3NA3745 |
800 |
4 |
3NE1448?2 |
850 |
3 |
900 |
1200 |
2GE41?6AA0 |
3NA3365 |
2 ? 500 |
3 |
3NE1436?2 |
2 ? 630 |
3 |
500 ... 600 V 3 AC | ||||||||
630 |
900 |
2GF38?6AA0 |
3NA3352?6 |
2 ? 315 |
3 |
3NE1435?2 |
560 |
3 |
710 |
1000 |
2GF41?1AA0 |
3NA3365?6 |
2 ? 500 |
3 |
3NE1447?2 |
670 |
3 |
1000 |
1600 |
2GF41?4AA0 |
3NA3365?6 |
2 ? 500 |
3 |
3NE1448?2 |
850 |
3 |
660 ... 690 V 3 AC | ||||||||
1000 |
2GH41?1AA0 |
3NA3354?6 |
2 ? 355 |
3 |
3NE1447?2 |
670 |
3 | |
1350 |
2GH41?4AA0 |
3NA3365?6 |
2 ? 500 |
3 |
3NE1448?2 |
850 |
3 | |
1500 |
2GH41?5AA0 |
3NA3365?6 |
2 ? 500 |
3 |
3NE1434?2 |
2 ? 500 |
2 |
Note: The type rating data in hp units are based on the NEC/CEC standards for the North American market.