Mechanical specifications |
Vibratory load | |
- Transport 1) acc. to EN 60721‑3‑-2
| Class 2M3 |
- Operation acc. to EN 60721‑3‑3
| Class 3M2 |
- Test values according to EN 60068‑2‑6
| Test Fc (sinusoidal) - 10 ... 13 Hz: 0.075 mm amplitude of deflection
- 13 Hz ... 150 Hz: 1 × g acceleration amplitude
- 10 frequency cycles per axis
|
Shock load | |
- Transport 1) acc. to EN 60721‑3‑-2
| Class 2M3 |
- Operation acc. to EN 60721‑3‑3
| Class 3M2 |
- Test values according to EN 60068‑2‑27
| Test Ea (semisinusoidal) - 5 × g peak acceleration
- 30 ms duration
- 3 shocks in all three axes in both directions
|
Environmental conditions |
Protection class According to EN 61800‑5‑1 | Class I (with protective bonding circuit) and class III (PELV or SELV) |
Touch protection According to EN 61800‑5‑1 | DIN VDE 0106 Part 100 and DGUV regulation 3 when used properly |
Permissible ambient temperature (air) in operation | 0 ... 50 °C (32 ... 122 °F) |
Installation altitude | Up to max. 4000 m (13 123 ft) - Up to 1 000 m (3 281 ft) above sea level without derating
- As from 1 000 m (3 281 ft) derating 10% of current or 5 K per 1 000 m (3 281 ft)
- Isolation transformer required as from 2 000 m (6562 ft)
|
Climatic environmental conditions | |
- Storage 2) acc. to EN 60721‑3‑1
| Class 1K4 -25 ... +55 °C (-13 ... +131 °F) |
- Transport 1) acc. to EN 60721‑3‑-2
| Class 2K4 -40 ... +70 °C (-40 ... +158 °F) Max. air humidity: 95% at 40 °C (104 °F) |
- Operation acc. to EN 60721‑3‑3
| Better than class 3K3 0 ... 50 °C (32 ... 122 °F) Relative air humidity: 5 ... 95% Condensation, splashwater, and ice formation not permitted (EN 60204, Part 1) |
Environmental class/harmful chemical substances | |
- Storage 2) acc. to EN 60721‑3‑1
| Class 1C2 |
- Transport 1) acc. to EN 60721‑3‑-2
| Class 2C2 |
- Operation acc. to EN 60721‑3‑3
| Class 3C2 |
Organic/biological influences | |
- Storage 2) acc. to EN 60721‑3‑1
| Class 1B2 |
- Transport 1) acc. to EN 60721‑3‑-2
| Class 2B2 |
- Operation acc. to EN 60721‑3‑3
| Class 3B2 |
Degree of pollution According to EN 61800‑5‑1 | 2 |
Standards |
Certificates of suitability | CE, cULus, RCM, EAC |