SINAMICS S120 Power Drive Systems (PDS) can be operated in the first and second environments. The measures necessary for operation in the respective environment are subsequently listed. Measures for complying with product standard EN 61800‑3 second environmentInterference immunity The SINAMICS S120 drive system is suitable for operation in the second environment. Regarding interference immunity, SINAMICS S120 can be used in the first and second environments. Interference emission – complying with Category C2 second environment Regarding interference emission, to comply with the limit values according to EN 61800‑3 second environment, Category C2, the following measures must be applied: - The drive system must be installed in compliance with EMC regulations by appropriately trained professionals.
- The SINAMICS S120 drive system requires a radio interference suppression filter, Category C2 (integrated as line filter, or as optional external line filter with/without line reactor)
- The pulse frequency is less than or equal to the rated pulse frequency
- The maximum motor cable length is complied with (shielded)
- Line supply with grounded neutral point (TN/TT supply system)
Device-specific assignment of the measures to comply with product standard EN 61800‑3 second environment, Category C2 SINAMICS S120 drive system | Measures for |
|---|
Radio interference suppression filter, Category C2 | Maximum pulse frequency fp | Maximum motor cable length (shielded) |
|---|
Device format | Supply voltage | Frame size | | kHz | m (ft) |
|---|
Booksize Line Modules | 380 ... 480 V 3 AC | – | External line filter required 1) | 4 2) | 350 (1148) | Chassis Active Line Modules Smart Line Modules | 380 ... 480 V 3 AC | FX ... JX | External line filter required | 4 2) | 300 (984) | 500 ... 690 V 3 AC | FX ... JX | External line filter required | 4 2) | 300 (984) | Chassis Basic Line Modules | 380 ... 480 V 3 AC | FB ... GD | External line filter plus line reactor required 1) | 4 2) | 100 (328) | 500 ... 690 V 3 AC | FB ... GD | External line filter plus line reactor required 1) | 4 2) | 100 (328) | Chassis Power Modules | 380 ... 480 V 3 AC | FX and GX | External line filter plus line reactor required 1) | 2 | 100 (328) | Blocksize Power Modules with integrated line filter | 200 ... 240 V 1/3 AC | FSA ... FSC | No measure required, as a line filter is integrated | 4 | 50 (164) | 380 ... 480 V 3 AC | FSA ... FSC | No measure required, as a line filter is integrated | 4 | 50 (164) | FSD ... FSE | No measure required, as a line filter is integrated | 4 | 150 (492) | FSF | No measure required, as a line filter is integrated | 2 | 150 (492) | 500 ... 690 V 3 AC | FSD and FSE | No measure required, as a line filter is integrated | 2 | 100 (328) | FSF | No measure required as a line filter is integrated (Category C3) | 2 | 150 (492) | Blocksize Power Modules without integrated line filter | 200 ... 240 V 3 AC | FSD ... FSF | External line filter required | 4 | 150 (492) | 380 ... 480 V 3 AC | FSA ... FSC | External line filter required 1) | 4 | 50 (164) | FSD ... FSE | External line filter required 1) | 4 | 150 (492) | FSF | External line filter required 1) | 2 | 150 (492) | 500 ... 690 V 3 AC | FSD ... FSF | External line filter required 1) | 2 | 100 (328) |
1) Selection and ordering data for line filters and line reactors see sections Line-side power components. 2) Refers to the pulse frequency of the Motor Modules. Interference emission – complying with Category C3 second environment All Active Line Modules in booksize format, Basic Line Modules in booksize format 100 kW as well as Line Modules in chassis format in the standard version are compliant. A line reactor is required for Power Modules in chassis format. The maximum cable lengths and pulse frequencies (see the previous table) must be taken into account. For Active Line Modules in booksize format, when using an external line filter, the maximum cable length can be increased to 1000 m (3281 ft). Interference emission – complying with Category C4 second environment When connected to IT line supplies, only devices without integrated filter, Basic Line Modules in booksize format up to 40 kW, and all Smart Line Modules in booksize format are permissible. To limit symmetrical interference emission, suitable external filters without capacitors connected to ground must be used. Further selected accessories are available from "Siemens Product Partner for Drives Options": http://www.siemens.com/drives-options-partner Measures for complying with product standard EN 61800‑3 first environmentOnly PM240‑2 Power Modules in blocksize format can be used in the first environment. Interference immunity The SINAMICS S120 drive system is suitable for operation in the second environment. Regarding interference immunity, SINAMICS S120 can be used in the first and second environments. Interference emission – complying with Category C2 first environment For use in the first environment, in addition to the requirements for use in the second environment, device-specific notes to maintain the harmonic current limits must be taken into consideration. Here, EMC product standard EN 61800‑3 makes reference to the standards pertaining to harmonic currents: EN 61000‑3‑2 and EN 61000‑3‑12. Device-specific notes for complying with harmonic current limit values according to EN 61000‑3 - Power Modules with a power PN ≤ 1 kW
Complying with limit values according to EN 61000‑3‑2 cannot be guaranteed in this case. The installation company or company operating professionally used devices must obtain authorization to connect the device to the low-voltage grid from the responsible power utility company. - Power Modules with a power PN > 1 kW and a rated input current Irated, input < 16 A
These devices are not subject to any limit values regarding the harmonic currents, and can therefore be connected to the public low-voltage grid without prior authorization. - Power Modules with a rated input current > 75 A
There are no applicable standards when installing these types of devices. However, it is recommended that the utility company (grid operator) be informed when connecting such a device.
Device-specific measures to comply with harmonic current limit values: Power Modules in blocksize format with a rated input current Irated, input > 16 A and ≤ 75 A | Measures to comply with harmonic current limits according to EN 61000‑3‑12 |
|---|
Rated power | Rated input current Irated, input | Supply voltage | Frame size | Line reactor uk = 4 % | Minimum short-circuit power SSC at the connection point of the customers plant or system |
|---|
3 ... 7.5 kW | 20.7 ... 37 A | 200 ... 240 V 3 AC | FSC | Required 1) | SSC ≥ 120 × √3 × Uline × Irated, input | 5.5 ... 15 kW | 17.2 ... 39.9 A | 380 ... 480 V 3 AC | FSB and FSC | Required 1) | 11 ... 18.5 kW | 40 ... 64 A | 200 ... 240 V 3 AC | FSD | Not required | SSC ≥ 120 × √3 × Uline × Irated, input | 18.5 ... 37 kW | 36 ... 70 A | 380 ... 480 V 3 AC | FSD | Not required |
1) Available from Siemens partners. Here, select "Solution Partner Finder", as technology "Drive Options":http://www.siemens.com/automation/partnerfinder Example of calculating the minimum short-circuit power required Determining the minimum short-circuit power SSC for the Power Module in blocksize format FSD: 37 kW with Uline = 400 V and Irated, input = 70 A SSC ≥ 120 × √3 × Uline × Irated, input The short-circuit power must be greater than 120 × 1.73 × 400 V × 70 A = 5812 kVA As guide value, this typically corresponds to a low-voltage transformer with an apparent power of approximately 300 ... 400 kVA. Note: The installation company or company operating the device is responsible for ensuring that this device is only connected at a connection point with an appropriate short-circuit power (fault level), if this is necessary after consulting the power utility (grid operator). The installation company or company operating the device requires authorization from the power utility (grid operator) in the following situations: - Three-phase connection to a line supply with lower short-circuit power
- Three-phase connection without a line reactor
- Connecting single-phase devices with a rated input current Irated, input >16 A
Maximum permissible cable lengths from the motor to the converter when using output reactors or filters depending on the voltage range and the Power Module being usedThe following load-side power components in the appropriate frame sizes are optionally available for the Power Modules and result in the following maximum cable lengths: | Maximum permissible motor cable lengths (shielded/unshielded) in m (ft) |
|---|
Frame size | FSA | FSB | FSC | FSD | FSE | FSF |
|---|
PM240-2 Power Module with integrated braking chopper | Available frame sizes | | | | | | | | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | | ✓ | ✓ | ✓ | ✓ | ✓ | ✓ | | – | – | – | ✓ | ✓ | ✓ | With optional output reactor | | | | | | | - At 200 ... 240 V 1 AC/3 AC
| 150/225 (492/738) | 150/225 (492/738) | 150/225 (492/738) | – | – | – | | 150/225 (492/738) | 150/225 (492/738) | 150/225 (492/738) | 200/300 (656/984) 3) | 200/300 (656/984) 3) | 300/450 (984/1476) 3) | | 100/150 (328/492) | 100/150 (328/492) | 100/150 (328/492) | 200/300 (656/984) 3) | 200/300 (656/984) 3) | 300/450 (984/1476) 3) | | – | – | – | 200/300 (656/984) 3) | 200/300 (656/984) 3) | 300/450 (984/1476) 3) | With integrated line filter class A | | | | | | | - At 200 ... 240 V 1 AC/3 AC
| 50/- (164/-) | 50/- (164/-) | 50/- (164/-) | – | – | – | | 50/- (164/-) | 100/- (328/-) 2) | 150/- (492/-) 2) | 150/- (492/-) | 150/- (492/-) | 150/- (492/-) | | – | – | – | 100/- (328/-) | 100/- (328/-) | 150/- (492/-) (category C3) | With optional, external line filter class B according to EN 55011 to comply with cable-conducted radio interference emissions according to EN 61800‑3 EMC Category C1 1), together with unfiltered Power Modules | | | | | | | | 50/- (164/-) | 50/- (164/-) | 50/- (164/-) | – | – | – | With optional, external line filter class B according to EN 55011 and output reactor to comply with radio interference emissions according to EN 61800‑3 EMC Category C2 1), together with unfiltered Power Modules | | | | | | | | 150/- (492/-) | 150/- (492/-) | 150/- (492/-) | – | – | – | | 100/- (328/-) | 100/- (328/-) | 100/- (328/-) | – | – | – |
1) Further information is available on the Internet at http://www.siemens.com/sinamics-g120/documentation 2) The values apply for cables with low capacitance, e.g. MOTION‑CONNECT. When using standard CY cables, the maximum motor cable length is 50 m (164 ft) (shielded). 3) The maximal cable lengths for frame sizes FSD to FSF will not be increased with a motor reactor. The motor reactor reduces the load on the motor windings by reducing the voltage gradients (dv/dt).
|