Overload capabilityThe power units of the Line Modules, Motor Modules and Power Modules are designed for brief overloads, i.e. the Modules are capable of supplying more than the rated current Irated for short periods. In this instance, the thermal capacity of the heat sink is utilized, allowing for the relevant thermal time constants. The power semiconductors and actual current sensing circuit are rated for a maximum current Imax which must not be exceeded. The overload capability is determined by Imax, Irated and the thermal time constants. A number of characteristic duty cycles are defined in the technical specifications for the power units. The SIZER for Siemens Drives engineering tool calculates the load on the basis of a specified duty cycle with optional time characteristic and then identifies the power unit which is required. The thermal time constant of a power semiconductor chip is typically within the range of 100 ms. With frequencies below 10 Hz, the overload capacity is therefore limited. The software takes account of these limitations by means of a thermal model and protects the devices against overload in all operating states. It must be noted, especially at frequencies around 0 Hz, that the specified rated current Irated is the root-mean-square value of a sinusoidal current. If the frequency of the three-phase system is reduced to 0 Hz, a pure direct current flows in all phases at standstill. The root-mean-square value of this direct current can reach the peak value of the sinusoidal current depending on the phase relation. The output current in this state is greater than the rated current Irated by a factor of √2. The individual motor terminals and cables are designed thermically for the rated current in normal operation, so the devices are protected against this overload while taking account of the thermal time constant. Derating characteristicsThe power units can be operated with their rated current or power and the specified pulse frequency up to an ambient temperature of 40 °C (104 °F). The heat sink reaches the maximum permissible temperature at this operating point. If the ambient temperature increases above 40 °C (104 °F), the resulting heat loss must be reduced to prevent the heat sink from overheating. At a given current, the heat loss increases in proportion to the pulse frequency. The rated output current Irated must be reduced to ensure that the maximum heat loss or heat sink temperature for higher pulse frequencies is not exceeded. When the correction factor kf for the pulse frequency is applied, the rated output current Iratedf that is valid for the selected pulse frequency is adjusted. When configuring a drive, please note that power units may not be capable of supplying the full current or power in the temperature range between 40 °C (104 °F) and 55 °C (131 °F). The power units measure the heat sink temperature and protect themselves against thermal overloading at temperatures > 40 °C (104 °F). The air pressure, and therefore air density, drops at altitudes above sea level. At these altitudes, the same quantity of air does not have the same cooling effect and the air gap between two electrical conductors can only insulate a lower voltage. Typical air pressure values are: 0 m (0 ft) above sea level: 100 kPa 2000 m (6562 ft) above sea level: 80 kPa 3000 m (9843 ft) above sea level: 70 kPa 4000 m (13124 ft) above sea level: 62 kPa 5000 m (16405 ft) above sea level: 54 kPa At installation altitudes above 2000 m (6562 ft), the line voltage must not exceed certain limits to ensure that surge voltages can be insulated in accordance with EN 60664‑1 for surge voltage category III. If the line voltage is higher than this limit at installation altitudes > 2000 m (6562 ft), measures must be taken to reduce transient category III surge voltages to category II values, e.g. equipment must be supplied via an isolating transformer. In order to calculate the permissible output current or power, the derating factors must be multiplied for the effects described above. The derating factor kI for current as a function of installation altitude can be offset against the derating factor kT for ambient temperature. If the result of multiplying derating factor kT by derating factor kI is greater than 1, then the calculation must be based on a rated current of Irated or Iratedf. If the result is < 1, then it must be multiplied by the rated current Irated or Iratedf to calculate the maximum permissible continuous current. The derating factor k = kf × kT × kI calculated by this method to obtain the total derating value must be applied to all current values in the specified duty cycles (Irated, IH, IL). The derating characteristic curves of Power Modules, Line Modules and Motor Modules can be found in the technical specifications of the relevant modules (see section SINAMICS S120 drive system). Examples of derating characteristic curves and calculation of the permissible output current: Current derating as a function of the ambient temperature Current derating as a function of the installation altitude Voltage derating as a function of the installation altitude Example 1 A drive system is to be operated at an altitude of 2500 m (8203 ft) at a maximum ambient temperature of 30 °C (86 °F) and rated pulse frequency. Since the ambient temperature is below 40 °C (104 °F), a compensation calculation (installation altitude/ambient temperature) can be applied. Installation altitude 2500 m (8203 ft): Derating factor kI = 0.965, kU = 0.94 Max. ambient temperature 30 °C (86 °F): Derating factor kT = 1.133 kI × kT = 0.965 × 1.133 = 1.093 ⇒ 1.0 due to installation altitude/ambient temperature compensation k = kf × (kI × kT) = 1.0 × (1.0) = 1.0 Result: Current derating is not required. However, IEC 60664‑1 stipulates that voltage derating is required. The units in voltage range 380 V to 480 V can be operated up to a voltage of 480 V x 0.94 = 451 V, and the units in voltage range 660 V to 690 V up to 690 V × 0.94 = 648 V. Example 2 When a drive line-up is configured, a Motor Module with Article No. 6SL3320‑1TE32‑1AA0 is selected (rated output current 210 A, base load current for high overload 178 A). The drive line-up is to be operated at an altitude of 3000 m (9843 ft) where ambient temperatures could reach 35 °C (95 °F) as a result of the installation conditions. The pulse frequency must be set to 4 kHz to provide the required dynamic response. Installation altitude 3000 m (9843 ft): Derating factor kI = 0.925, kU = 0.88 Max. ambient temperature 35 °C (95 °F): Derating factor kT = 1.066 kI × kT = 0.925 × 1.066 = 0.987 ⇒ not fully compensated by installation altitude/ambient temperature k = kf × (kI × kT) = 0.82 × (0.925 × 1.066) = 0.809 Result: Current derating is required. Where these boundary conditions apply,
IEC 60664‑1 stipulates that voltage derating is required. The selected unit can be operated up to a voltage of 480 V 3 AC × 0.88 or 720 V DC× 0.88 = 422 V 3 AC or 634 V DC. This means that a 400 V asynchronous (induction) motor can be operated without any restrictions. Due to the installation altitude, however, derating might be required for the asynchronous motor (induction motor). Selection of the Power Module or Motor ModuleThe Motor Module is selected initially on the basis of standstill current I0 100 K (rated current for winding temperature rise 100 K) for synchronous motors and the rated current Irated for asynchronous motors (induction motors), and is specified in the motor description. Dynamic overloads, e.g. during acceleration, must be taken into account by duty cycles and may demand a more powerful Power Module or Motor Module. In this context, it is also important to remember that the output current of the Power Module or Motor Module decreases as a function of installation altitude, ambient temperature and pulse frequency setting (see explanations of derating characteristics). For an optimum configuration, the rms motor current Iload calculated from the duty cycle is replicated on the Power Module or Motor Module. The following must apply: Irated, module ≥ Iload Irated, module = permissible continuous current of Power Module or Motor Module taking derating characteristic curves into account The Power Modules or Motor Modules can be required to supply a higher output current for specific time periods. The characteristics or overload capability must be noted (see section SINAMICS S120 drive system) when modules are engineered for overload. The SIZER for Siemens Drives engineering tool is capable of performing precise overload calculations. Rated current – permissible and non-permissible motor/converter combinations
Using pulse width modulation, the Power Modules or Motor Modules generate an AC voltage to feed the connected motor from the DC voltage of the DC link. The magnitude of the DC link voltage is determined by the line voltage and, in the case of a Motor Module, by the Line Module used and thus the maximum possible output voltage (see section SINAMICS S120 drive system). The speed and loading of the connected motor define the required motor voltage. The maximum possible output voltage must be greater than or equal to the required motor voltage; it may be necessary to select a motor with a different winding. It is not possible to utilize all modes of pulse width modulation when a sine-wave filter is connected. The maximum possible output voltage (see sine-wave filter) is lower as a result. Long motor cablesUsing pulse width modulation, the Power Modules or Motor Modules generate an AC voltage to feed the connected motor from the DC voltage of the DC link. Capacitive leakage currents are generated in clocked operation and these limit the permissible length of the motor cable. The maximum permissible motor cable length is specified for each Power Module or Motor Module in the component description. Motor reactors limit the rate of rise and magnitude of the capacitive leakage currents, thereby allowing longer motor cables to be used. The motor reactor and motor cable capacitance form an oscillating circuit which must not be stimulated by the pulse pattern of the output voltage. The resonant frequency of this oscillating circuit must therefore be significantly higher than the pulse frequency. The longer the motor cable, the higher the cable capacitance and the lower the resonant frequency. To provide a sufficient safety margin between this resonant frequency and the pulse frequency, the maximum possible motor cable length is limited, even when several motor reactors are connected in series. The maximum cable lengths in combination with motor reactors are specified in the technical specifications for the motor reactors. Where a longer motor cable is required, a higher rating power unit must be selected or the permissible continuous output current Icontinuous must be reduced in relation to the rated output current Irated.
The permissible cable length for an unshielded motor cable is 150 % of the length for a shielded motor cable. Motor reactors can be used for frame sizes FSA to FSC to allow longer motor cables to be used. Sine-wave filters are recommended for frame sizes FSD to FSF. The maximum cable lengths are shorter in order to comply with EMC compatibility according to EN 61800‑3. See section EMC notes. Line ModulesIn multi-axis drive applications, a number of Motor Modules are operated on a common DC link, which is supplied with power by a Line Module. The first task is to decide whether a Basic Line Module, Smart Line Module or an Active Line Module will be used. On one hand, this depends on whether the drive must be capable of regenerative feedback into the line supply and, on the other hand, whether the line infeed is uncontrolled, and therefore dependent on the line supply voltage, or controlled to obtain a constant DC link voltage. For an uncontrolled infeed Basic Line Modules/Smart Line Modules, line voltage changes can influence the output power of the Line Modules. The chassis format units are available in the 380 V to 480 V voltage range, but also include units in the 500 V to 690 V range. Basic Line Modules are designed for infeed operation only. Active Line Modules have regulated infeeds which feature a step-up function. In order to calculate the required DC link power and select the correct Line Module, it is important to analyse the entire operating sequence of the drive line-up connected to the DC link. Factors such as partial load, redundancies, duty cycles, coincidence factors and the operating mode (motor / generator mode) must be taken into account. The DC link power Pd of a single Motor Module is calculated from the shaft output Pmech of the motor and the efficiency of the motor ηm and Motor Module ηwr. The following applies in motor mode: Pd = Pmech / (ηm × ηwr) The following applies in generator mode: Pd = Pmech × ηm × ηwr The motor and generator outputs must be added with the corresponding sign in order to calculate the total DC link power. For the power calculation, the DC link voltage Ud can be assumed to be constant. Therefore, the required DC link current can be calculated as Id = Pd/Ud Basic Line Modules The DC link voltage Ud of the Basic Line Modules is load-dependent. Under no-load conditions, the DC link is charged to the line voltage crest value UL, i.e. Ud = √2 × UL, e.g. Ud = 566 V when a 400 V supply system is connected. Under load conditions, the DC link voltage reaches the average value of the rectified line voltage applied to the terminals. This mean value results from the line voltage times a factor of 1.35. Under full load, the voltage in the DC link is slightly less than the theoretical value due to the voltage drop across the line reactor and the line feeder cable. In practice, the range of the DC link voltage Ud is as follows: 1.41 × UL > Ud > 1.32 × UL (no load → rated power) Smart Line Modules The DC link voltage Ud of Smart Line Modules is regulated to the average value of the rectified line voltage UL, i.e. Ud ≈ 1.35 × UL Due to the voltage drop across the line reactor and in the line feeder cable, the DC link voltage decreases in motor operation and increases in generator operation. The DC link voltage Ud thus varies within the same range as on drives with a Basic Line Module: 1.41 × UL > Ud > 1.32 × UL (rated power, generating → rated power, motoring) Active Line Modules The DC link voltage Ud is regulated to an adjustable value (Active Mode). An Active Line Module can also be switched to Smart Mode and then operates like a Smart Line Module. In Active Mode, the Active Line Module draws a virtually sinusoidal current from the supply system. The rated infeed power of the Line Module refers to a line voltage of 380 V, 400 V or 690 V (690 V applies only to chassis format Line Modules). Depending on the ambient conditions (installation altitude, ambient temperature), the rated infeed power of the Line Modules may need to be reduced (see section SINAMICS S120 drive system). The coincidence factor takes into account the time characteristic of the torque for each individual axis. On the basis of these principles, the following procedure can be used to dimension the Line Module: The following factors must also be taken into account when dimensioning the DC link: Braking operation As device losses are important in motor mode, the dimensioning for motor mode is also applicable to generator mode. With respect to motor braking operation, check that the energy fed back into the DC link does not exceed the permissible peak load capability of the Line Module. In the case of higher regenerative outputs and to control the "line failure" operating scenario, a Braking Module must be provided, the Smart or Active Line Module must be overdimensioned or the regenerative output reduced by longer braking times. For the configuration of the "EMERGENCY STOP" operating scenario, the Line Module must either be overdimensioned or an additional Braking Module must be used, so that the DC link energy can be dissipated as quickly as possible. Checking the DC link capacitance During power-up, the Line Modules limit the charging current for the DC link capacitors. Due to the limits imposed by the precharging circuit, it is essential to observe the maximum permissible DC link capacitance values for the drive line-up specified in the technical specifications. Frequency with which the DC link is precharged For chassis format Line Modules, the maximum permissible DC link pre-charging interval is 3 minutes. Parallel connection of power unitsUp to 4 Motor Modules or Line Modules in chassis format can be connected in parallel. Parallel connections can operate only in the Vector Control mode. Parallel connections may only include Motor Modules or Line Modules of the same type and with the same voltage and output ratings. Mixtures of different modules, e.g. Basic Line Modules and Active Line Modules, cannot be connected in parallel. The CU320-2, SIMOTION D4x5-2 or CX32-2 Control Unit can control only one drive object of type "Parallel connection Line Modules" and one of type "Parallel connection Motor Modules". It is assumed that all Line Modules or Motor Modules linked to the Control Unit are connected in parallel. A Control Unit can control, for example, the following components:
Combinations such as the following are not permissible: 2 Line Modules + 2 parallel-connected Motor Modules + 1 Motor Module Further information can be found in the following Engineering Manual: System disturbancesThe voltage drops across the impedance between the supply system and a load as soon as the load draws current. In a symmetrical three-phase supply system, this is the network impedance Zn which is calculated from the impedance Zs of the supply system and the line-side impedance Ze of the load. Effective impedances when a load is connected to a three-phase supply system ZN = Zs + Ze = Rs + j Xs + Re + j Xe = Rn + j Xn On a variable-speed drive, the line-side impedance Ze is normally the total impedance provided by the line reactor and the feeder cable up to the PCC (Point of Common Coupling) for further loads. The ohmic component Rn is generally negligible as compared to the inductive component Xn. The inductance of an RI suppression filter is irrelevant for the purpose of this calculation, as this inductance is effective only for asymmetrical interference voltages, but not for a symmetrical line current. If a load causes voltage drops across the impedance Zs, this system disturbance has an impact at the PCC and thus also in the supply voltage to all other loads. The voltage drop is proportional to current Ie and the impedance. To facilitate comparison of voltage drops under different supply and load conditions, the voltage drop is specified – normally at rated current – with reference to the phase voltage Uo. The calculation formula, e.g. for the per unit voltage drop uk across an impedance Z is as follows: uk = Z × Ie / Uo Example 1: A Power Module with rated line current Ie is directly connected to a low-voltage transformer and the PCC is the transformer connection terminal. The equation for the ratio between rated line current Ie of the Power Module and rated current Irated of the transformer is Ie = 0.25 × Irated. The per unit voltage drop uk of the 400 V transformer is 4 %. If the transformer is loaded with its rated current Irated, the voltage drop across impedance Zs is 9.2 V (corresponding to 4 % of the phase voltage Uo = 230 V). uk = (Zs × Irated) / 230 V = 0.04 The following formula applies to the rated line current Ie of the Power Module: Ie = k × Irated The per unit voltage drop across the transformer when loaded with Ie is thus: uk = Zs × Ie / Uo = Zs × k × Irated / Uo With the specified ratio between Ie and Irated, the per unit voltage drop is calculated as uk = 1 % or 2.3 V. In relation to the Power Module, this transformer therefore functions like a line impedance in accordance with uk = 1 %. The magnitude of system disturbance in converter systems is assessed on the basis of short-circuit power ratio Rsc: Rsc = Scν / P According to this definition in accordance with EN 60146‑1, P is the fundamental-wave apparent power drawn by the converter. Scν ≈ 3 × Uo2 / Xn and thus Rsc ≈ 3 × Uo2 / (Xn × P) The short-circuit power ratio Rsc is therefore dependent on the current output power P of the converter and is determined by network impedance Xn. If we assume the power to be P ≈ 3 × Uo × Ie = √3 × Urated × Ie the short-circuit power ratio Rsc is in inverse proportion to the per unit voltage drop uk across the effective line impedance. Rsc ≈ 3 × Uo2 / (Xn × P) = 3 × Uo2 / (Xn × 3 × Uo × Ie) = Uo / (Xn × Ie) = 1 / uk The short-circuit power ratio for example 1 is Rsc ≈ 100 if no line reactor is installed (Ze = 0). Note: The term "short-circuit power ratio" as used in technical standards is not a harmonized definition. The short-circuit power ratio Rsce defined according to IEC 61000-3-12 is calculated from the short-circuit power SSC at the PCC referred to the power Sequ = 3 × Uo × Ie consumed by the load. Basic Line Modules and Power Modules are designed with a rectifier bridge on the line side. An inherent feature of the principle of rectification with load-side capacitance for DC link voltage smoothing are harmonics in the line current which result in a non-sinusoidal power input. The diagram shows the basic current waveform of a Power Module or Basic Line Module as a function of short-circuit power ratio Rsc. Active Line Modules generate virtually no current harmonics (Active Mode) at all and are employed when system disturbance needs to be minimized, e.g. stipulation of IEEE 519 that THD (Total Harmonic Distortion) must be < 10 %. The SIZER for Siemens Drives engineering tool calculates the line harmonic distortion on the basis of the supply data entered and lists them against the limit values of relevant standards. Line current of a Basic Line Module or Power Module as a function of the short-circuit power ratio Rsc The rms of the line current Ie for which the line-side components must be rated comprises fundamental wave Ie1 and the current harmonics, which increase in relation to the rise in short-circuit power ratio Rsc. If the DC link power Pd has been calculated (see Line Modules), the required line-side active power is a known quantity with Line Module efficiency, or the rectifier efficiency in the case of a Power Module. However, this active power is connected only with the current fundamental wave Ie1. The rms of the line current Ie is always greater than Ie1 as a result of the current harmonics. The following applies for a short-circuit power ratio Rsc = 100: Ie ≈ 1.3 × Ie1 The apparent power of a transformer selected to supply the drive must be greater than the drive power by a factor of about 1.3. The harmonic currents produce only alternating power, but no active power. The following applies to the apparent power S on the line side: S2 = P2 + Q12 + D2
The ratio between active power and apparent power is referred to as power factor λ or total power factor: Typical waveform of the line current with Power Modules and Line Modules Line-side power options (main switch, fuses, line filters, etc.)The following line-side options are recommended for the drive configuration: General overview of line infeed The main switch may take various formats:
To protect the units against line-side surge voltages, it is advisable to install overvoltage protection directly at the infeed point (upcircuit of main switch). Surge protection is essential in order to satisfy the requirements of Canadian standard CSA C22.2 No. 14-05. For examples of suitable surge voltage arresters, go to Depending on the power rating required, a fuse switch disconnector combined with a contactor or a circuit breaker can be used as the main switch. A line contactor can be used, for example, if the drive has to be disconnected from the line supply in the event of a fault or for remote tripping. Follow the instructions in the SINAMICS S120 Configuration Guides to interlock the line contactor in the context of safety functions. A line filter should be used on TN (grounded) systems to reduce system disturbance. |
skener.ru Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Àðìàòóðà DENDOR Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Äàò÷èêè è èçìåðèòåëè Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Ðåãóëÿòîðû è ðåãèñòðàòîðû Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Ïíåâìàòè÷åñêîå îáîðóäîâàíèå Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Êðàíû è Êëàïàíû Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Èçìåðèòåëüíûå ïðèáîðû Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Ñèñòåìû áåñïðîâîäíîãî óïðàâëåíèÿ «óìíûé äîì» Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Áåñêîíòàêòíûå âûêëþ÷àòåëè Êîíå÷íûå âûêëþ÷àòåëè Îïòè÷åñêèå äàò÷èêè Ýíêîäåðû Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 SKW-FS - Óñòàíîâêà óìÿã÷åíèÿ Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30 SKW-FK - Óñòàíîâêà îáåçæåëåçèâàíèÿ |
Êàòàëîã 2018 | Êàòàëîã 2017 | Êàòàëîã 2016 | Êàòàëîã 2015 | Êàòàëîã 2014 | Êàòàëîã 2013 | Êàòàëîã 2012 | Ñåðòèôèêàò | Êîíòàêòû | Êàðòà ñàéòà | Ïîèñê |