General technical specifications

Electrical specifications

Efficiency

98.5 %

DC link voltage

(up to 2000 m (6562 ft) above sea level)

510 ... 720 V DC (line voltage 380 ... 480 V 3 AC) or
675 ... 1035 V DC (line voltage 500 ... 690 V 3 AC)

Output frequency 1)

 

  • Control type Servo

0 ... 550 Hz

  • Control type Vector

0 ... 550 Hz

  • Control mode V/f

0 ... 550 Hz

Safety Integrated

Safety Integrity Level 2 (SIL2) acc. to IEC 61508, Performance Level d (PLd) acc. to EN ISO 13849‑1 and Control Category 3 acc. to EN ISO 13849‑1.



1) Please note:

• The correlation between the maximum output frequency, pulse frequency and current derating. Higher output frequencies on request. For further information, see https://support.industry.siemens.com/cs/document/104020669

• The correlation between the minimum output frequency and permissible output current (current derating). Information is provided in the SINAMICS Low Voltage Engineering Manual.

Line voltage 380 ... 480 V 3 AC
DC link voltage 510 ... 720 V DC

Motor Modules

 

6SL3325-1TE32-1AA3

6SL3325-1TE32-6AA3

6SL3325-1TE33-1AA3

6SL3325-1TE35-0AA3

Type rating

 

 

 

 

 

  • At IL (50 Hz 400 V) 1)

kW

110

132

160

250

  • At IH (50 Hz 400 V) 1)

kW

90

110

132

200

  • At IL (60 Hz 460 V) 2)

hp

150

200

250

400

  • At IH (60 Hz 460 V) 2)

hp

150

200

200

350

Output current

 

 

 

 

 

  • Rated current Irated O

A

210

260

310

490

  • Base-load current I3)

A

205

250

302

477

  • Base-load current I4)

A

178

233

277

438

  • Maximum current Imax O

A

307

375

453

715

DC link current

 

 

 

 

 

  • Rated current Irated DC
    when supplied via

 

 

 

 

 

  • Basic Line Module

A

256

317

380

600

  • Active Line Module

A

230

287

340

538

  • Base-load current IL DC 3)
    when supplied via

 

 

 

 

 

  • Basic Line Module

A

250

305

368

581

  • Active Line Module

A

225

274

331

522

  • Base-load current IH DC 4)
    when supplied via

 

 

 

 

 

  • Basic Line Module

A

227

284

338

534

  • Active Line Module

A

195

255

303

480

Current demand

 

 

 

 

 

  • 24 V DC auxiliary power supply

A

1.4

1.4

1.5

1.5

DC link capacitance

μF

4800

5800

8400

9600

Pulse frequency 5)

 

 

 

 

 

  • Rated frequency

kHz

2

2

2

2

  • Pulse frequency, max.

 

 

 

 

 

  • Without current derating

kHz

2

2

2

2

  • With current derating

kHz

8

8

8

8

Power loss, max. 6)

 

 

 

 

 

  • At 50 Hz 400 V

kW

1.61

1.95

2.29

3.56

  • At 60 Hz 460 V

kW

1.68

2.06

2.38

3.74

  • Dissipated to ambient air

kW

0.06

0.07

0.09

0.14

Coolant volume flow 7)

l/min (US gal./min)

9 (2.38)

9 (2.38)

12 (3.17)

12 (3.17)

Liquid volume

of the integrated heat exchanger

dm3

0.31

0.31

0.91

0.91

Pressure drop, typ. 8)

for volume flow

Pa

70000

70000

70000

70000

Heat exchanger material

 

Stainless steel

Stainless steel

Stainless steel

Stainless steel

Coolant connections

Intake/return

 

Pipe thread ISO 228 G 3/4 B
(external thread 3/4", flat-sealing)

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

52

52

52

52

DC link connection

DCP, DCN

 

2 Ã— hole for M12

Busbar

2 Ã— hole for M12

Busbar

2 Ã— hole for M12

Busbar

2 Ã— hole for M12

Busbar

Motor connection

U2, V2, W2

 

Hole for M12

Hole for M12

Hole for M12

Hole for M12

  • Conductor cross-section, max. (IEC)

mm2

2 Ã— 95

2 Ã— 95

2 Ã— 240

2 Ã— 240

PE/GND connection

 

2 Ã— hole for M12

2 Ã— hole for M12

2 Ã— hole for M12

2 Ã— hole for M12

  • Conductor cross-section, max. (IEC)

mm2

2 Ã— 95

2 Ã— 95

2 Ã— 240

2 Ã— 240

Cable length, max 9)

 

 

 

 

 

  • Shielded

m (ft)

300 (984)

300 (984)

300 (984)

300 (984)

  • Unshielded

m (ft)

450 (1476)

450 (1476)

450 (1476)

450 (1476)

Dimensions

 

 

 

 

 

  • Width

mm (in)

150 (5.91)

150 (5.91)

150 (5.91)

150 (5.91)

  • Height

mm (in)

746 (29.4)

746 (29.4)

1172 (46.1)

1172 (46.1)

  • Depth

mm (in)

545 (21.5)

545 (21.5)

545 (21.5)

545 (21.5)

Weight, approx.

kg (lb)

41 (90.4)

41 (90.4)

80 (176)

80 (176)

Frame size

 

FXL

FXL

GXL

GXL



1) Rated output of a typical 6‑pole standard induction motor based on IL or IH for 400 V 3 AC 50 Hz.

2) Rated output of a typical 6‑pole standard induction motor based on IL or IH for 460 V 3 AC 60 Hz.

3) The base-load current IL is based on a duty cycle of 110 % for 60 s or 150 % for 10 s with a duty cycle duration of 300 s.

4) The base-load current IH is based on a duty cycle of 150 % for 60 s or 160 % for 10 s with a duty cycle duration of 300 s.

5)Additional notes regarding the correlation between the pulse frequency and maximum output current/output frequency is provided in the SINAMICS Low Voltage Engineering Manual.

6) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions. To ensure safe dissipation of the minor power loss released to the ambient air, it is important to follow the instructions pertaining to control cabinet installation in the SINAMICS Low Voltage Engineering Manual.

7) The value applies to coolants comprising water and a mixture of water and antifreeze agent.

8) The value is valid for water as coolant. Additional information and notes on other coolants are provided in the SINAMICS Low Voltage Engineering Manual.

9) Total of all motor cables. Longer cable lengths for specific configurations are available on request. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.

Line voltage 380 ... 480 V 3 AC
DC link voltage 510 ... 720 V DC

Motor Modules

 

6SL3325-1TE37-5AA7

6SL3325-1TE41-0AA7

6SL3325-1TE41-2AA7

6SL3325-1TE41-4AA7

Type rating

 

 

 

 

 

  • At IL (50 Hz 400 V) 1)

kW

400

560

710

800

  • At IH (50 Hz 400 V) 1)

kW

315

450

630

710

  • At IL (60 Hz 460 V) 2)

hp

600

800

1000

1150

  • At IH (60 Hz 460 V) 2)

hp

450

700

900

1000

Output current

 

 

 

 

 

  • Rated current Irated O

A

745

985

1260

1405

  • Base-load current I3)

A

725

960

1230

1370

  • Base-load current I4)

A

570

860

1127

1257

  • Maximum current Imax O

A

1087

1440

1845

2055

DC link current

 

 

 

 

 

  • Rated current Irated DC
    when supplied via

 

 

 

 

 

  • Basic Line Module

A

894

1202

1512

1714

  • Active Line Module

A

805

1080

1361

1544

  • Base-load current IL DC 3)
    when supplied via

 

 

 

 

 

  • Basic Line Module

A

871

1170

1474

1670

  • Active Line Module

A

784

1051

1326

1500

  • Base-load current IH DC 4)
    when supplied via

 

 

 

 

 

  • Basic Line Module

A

795

1048

1345

1532

  • Active Line Module

A

716

942

1211

1377

Current demand

 

 

 

 

 

  • 24 V DC auxiliary power supply

A

1.6

1.46

1.46

1.46

DC link capacitance

μF

17400

21000

29000

29000

Pulse frequency 5)

 

 

 

 

 

  • Rated frequency

kHz

1.25

1.25

1.25

1.25

  • Pulse frequency, max.

 

 

 

 

 

  • Without current derating

kHz

1.25

1.25

1.25

1.25

  • With current derating

kHz

7.5

7.5

7.5

7.5

Power loss, max. 6)

 

 

 

 

 

  • At 50 Hz 400 V

kW

5.1

7.9

9.15

10.2

  • At 60 Hz 460 V

kW

5.61

8.55

10.05

11.2

  • Dissipated to ambient air

kW

0.2

0.44

0.56

0.62

Coolant volume flow 7)

l/min (US gal./min)

16 (4.23)

27 (7.13)

27 (7.13)

27 (7.13)

Liquid volume

of the integrated heat exchanger

dm3

0.74

1.56

1.56

1.56

Pressure drop, typ. 8)

for volume flow

Pa

70000

70000

70000

70000

Heat exchanger material

 

Copper-nickel alloy

Copper-nickel alloy

Copper-nickel alloy

Copper-nickel alloy

Coolant connections

Intake/return

 

Pipe thread ISO 228 G 3/4 B
(external thread 3/4", flat-sealing)

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

54

56

56

56

DC link connection

DCP, DCN

 

2 Ã— hole for M12

Busbar

2 Ã— hole for M12

Busbar

2 Ã— hole for M12

Busbar

2 Ã— hole for M12

Busbar

Motor connection

U2, V2, W2

 

2 Ã— hole for M12

2 Ã— hole for M12

2 Ã— hole for M12

2 Ã— hole for M12

  • Conductor cross-section, max. (IEC)

mm2

4 Ã— 185

4 Ã— 240

4 Ã— 240

4 Ã— 240

PE/GND connection

 

2 Ã— hole for M12

2 Ã— hole for M12

2 Ã— hole for M12

2 Ã— hole for M12

  • Conductor cross-section, max. (IEC)

mm2

4 Ã— 185

Busbar

Busbar

Busbar

Cable length, max 9)

 

 

 

 

 

  • Shielded

m (ft)

300 (984)

300 (984)

300 (984)

300 (984)

  • Unshielded

m (ft)

450 (1476)

450 (1476)

450 (1476)

450 (1476)

Dimensions

 

 

 

 

 

  • Width

mm (in)

265 (10.4)

295 (11.6)

295 (11.6)

295 (11.6)

  • Height

mm (in)

987 (38.9)

1510 (59.4)

1510 (59.4)

1510 (59.4)

  • Depth

mm (in)

545 (21.5)

545 (21.5)

545 (21.5)

545 (21.5)

Weight, approx.

kg (lb)

125 (276)

230 (507)

230 (507)

230 (507)

Frame size

 

HXL

JXL

JXL

JXL



1) Rated output of a typical 6‑pole standard induction motor based on IL or IH for 400 V 3 AC 50 Hz.

2) Rated output of a typical 6‑pole standard induction motor based on IL or IH for 460 V 3 AC 60 Hz.

3) The base-load current IL is based on a duty cycle of 110 % for 60 s or 150 % for 10 s with a duty cycle duration of 300 s.

4) The base-load current IH is based on a duty cycle of 150 % for 60 s or 160 % for 10 s with a duty cycle duration of 300 s.

5)Additional notes regarding the correlation between the pulse frequency and maximum output current/output frequency is provided in the SINAMICS Low Voltage Engineering Manual.

6) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions. To ensure safe dissipation of the minor power loss released to the ambient air, it is important to follow the instructions pertaining to control cabinet installation in the SINAMICS Low Voltage Engineering Manual.

7) The value applies to coolants comprising water and a mixture of water and antifreeze agent.

8) The value is valid for water as coolant. Additional information and notes on other coolants are provided in the SINAMICS Low Voltage Engineering Manual.

9) Total of all motor cables. Longer cable lengths for specific configurations are available on request. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.

Line voltage 500 ... 690 V 3 AC
DC link voltage 675 ... 1035 V DC

Motor Modules

 

6SL3325-1TG31-0AA3

6SL3325-1TG31-5AA3

6SL3325-1TG32-2AA3

6SL3325-1TG33-3AA3

Type rating

 

 

 

 

 

  • At IL (50 Hz 690 V) 1)

kW

90

132

200

315

  • At IH (50 Hz 690 V) 1)

kW

75

110

160

250

  • At IL (50 Hz 500 V) 1)

kW

55

90

132

200

  • At IH (50 Hz 500 V) 1)

kW

55

90

132

200

  • At IL (60 Hz 575 V) 2)

hp

75

150

200

300

  • At IH (60 Hz 575 V) 2)

hp

75

125

200

250

Output current

 

 

 

 

 

  • Rated current Irated O

A

100

150

215

330

  • Base-load current I3)

A

95

142

208

320

  • Base-load current I4)

A

89

134

192

280

  • Maximum current Imax O

A

142

213

312

480

DC link current

 

 

 

 

 

  • Rated current Irated DC
    when supplied via

 

 

 

 

 

  • Basic Line Module

A

122

183

263

403

  • Active Line Module

A

110

165

237

363

  • Base-load current IL DC 3)
    when supplied via

 

 

 

 

 

  • Basic Line Module

A

116

173

253

390

  • Active Line Module

A

105

156

229

352

  • Base-load current IH DC 4)
    when supplied via

 

 

 

 

 

  • Basic Line Module

A

108

163

234

341

  • Active Line Module

A

98

147

211

308

Current demand

 

 

 

 

 

  • 24 V DC auxiliary power supply

A

1.0

1.0

1.5

1.5

DC link capacitance

μF

2800

2800

4200

5800

Pulse frequency 5)

 

 

 

 

 

  • Rated frequency

kHz

1.25

1.25

1.25

1.25

  • Pulse frequency, max.

 

 

 

 

 

  • Without current derating

kHz

1.25

1.25

1.25

1.25

  • With current derating

kHz

7.5

7.5

7.5

7.5

Power loss, max. 6)

 

 

 

 

 

  • At 50 Hz 690 V

kW

1.15

1.64

2.34

3.38

  • At 60 Hz 575 V

kW

1.02

1.45

2.05

2.96

  • Dissipated to ambient air

kW

0.06

0.07

0.09

0.12

Coolant volume flow 7)

l/min (US gal./min)

9 (2.38)

9 (2.38)

12 (3.17)

12 (3.17)

Liquid volume

of the integrated heat exchanger

dm3

0.31

0.31

0.91

0.91

Pressure drop, typ. 8)

for volume flow

Pa

70000

70000

70000

70000

Heat exchanger material

 

Stainless steel

Stainless steel

Stainless steel

Stainless steel

Coolant connections

Intake/return

 

Pipe thread ISO 228 G 3/4 B
(external thread 3/4", flat-sealing)

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

52

52

52

52

DC link connection

DCP, DCN

 

2 Ã— hole for M12

Busbar

2 Ã— hole for M12

Busbar

2 Ã— hole for M12

Busbar

2 Ã— hole for M12

Busbar

Motor connection

U2, V2, W2

 

Hole for M12

Hole for M12

Hole for M12

Hole for M12

  • Conductor cross-section, max. (IEC)

mm2

2 Ã— 95

2 Ã— 95

4 Ã— 240

4 Ã— 240

PE/GND connection

 

2 Ã— hole for M12

2 Ã— hole for M12

2 Ã— hole for M12

2 Ã— hole for M12

  • Conductor cross-section, max. (IEC)

mm2

2 Ã— 95

2 Ã— 95

2 Ã— 240

2 Ã— 240

Cable length, max 9)

 

 

 

 

 

  • Shielded

m (ft)

300 (984)

300 (984)

300 (984)

300 (984)

  • Unshielded

m (ft)

450 (1476)

450 (1476)

450 (1476)

450 (1476)

Dimensions

 

 

 

 

 

  • Width

mm (in)

150 (5.91)

150 (5.91)

150 (5.91)

150 (5.91)

  • Height

mm (in)

728 (28.7)

728 (28.7)

1172 (46.1)

1172 (46.1)

  • Depth

mm (in)

545 (21.5)

545 (21.5)

545 (21.5)

545 (21.5)

Weight, approx.

kg (lb)

41 (90.4)

41 (90.4)

80 (176)

80 (176)

Frame size

 

FXL

FXL

GXL

GXL



1) Rated output of a typical 6‑pole standard induction motor based on IL or IH for 500 V or 690 V 3 AC 50 Hz.

2) Rated output of a typical 6‑pole standard induction motor based on IL or IH for 575 V 3 AC 60 Hz.

3) The base-load current IL is based on a duty cycle of 110 % for 60 s or 150 % for 10 s with a duty cycle duration of 300 s.

4) The base-load current IH is based on a duty cycle of 150 % for 60 s or 160 % for 10 s with a duty cycle duration of 300 s.

5)Additional notes regarding the correlation between the pulse frequency and maximum output current/output frequency is provided in the SINAMICS Low Voltage Engineering Manual.

6) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions. To ensure safe dissipation of the minor power loss released to the ambient air, it is important to follow the instructions pertaining to control cabinet installation in the SINAMICS Low Voltage Engineering Manual.

7) The value applies to coolants comprising water and a mixture of water and antifreeze agent.

8) The value is valid for water as coolant. Additional information and notes on other coolants are provided in the SINAMICS Low Voltage Engineering Manual.

9) Total of all motor cables. Longer cable lengths for specific configurations are available on request. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.

Line voltage 500 ... 690 V 3 AC
DC link voltage 675 ... 1035 V DC

Motor Modules

 

6SL3325-1TG34-7AA7

6SL3325-1TG35-8AA7

Type rating

 

 

 

  • At IL (50 Hz 690 V) 1)

kW

450

560

  • At IH (50 Hz 690 V) 1)

kW

400

450

  • At IL (50 Hz 500 V) 1)

kW

315

400

  • At IH (50 Hz 500 V) 1)

kW

250

315

  • At IL (60 Hz 575 V) 2)

hp

450

600

  • At IH (60 Hz 575 V) 2)

hp

450

500

Output current

 

 

 

  • Rated current Irated O

A

465

575

  • Base-load current I3)

A

452

560

  • Base-load current I4)

A

416

514

  • Maximum current Imax O

A

678

840

DC link current

 

 

 

  • Rated current Irated DC
    when supplied via

 

 

 

  • Basic Line Module

A

558

702

  • Active Line Module

A

502

632

  • Base-load current IL DC 3)
    when supplied via

 

 

 

  • Basic Line Module

A

544

683

  • Active Line Module

A

489

616

  • Base-load current IH DC 4)
    when supplied via

 

 

 

  • Basic Line Module

A

496

627

  • Active Line Module

A

446

565

Current demand

 

 

 

  • 24 V DC auxiliary power supply

A

1.6

1.6

DC link capacitance

μF

9670

9670

Pulse frequency 5)

 

 

 

  • Rated frequency

kHz

1.25

1.25

  • Pulse frequency, max.

 

 

 

  • Without current derating

kHz

1.25

1.25

  • With current derating

kHz

7.5

7.5

Power loss, max. 6)

 

 

 

  • At 50 Hz 690 V

kW

5.44

5.61

  • At 60 Hz 575 V

kW

5.1

5.45

  • Dissipated to ambient air

kW

0.14

0.16

Coolant volume flow 7)

l/min (US gal./min)

16 (4.23)

16 (4.23)

Liquid volume

of the integrated heat exchanger

dm3

0.74

0.74

Pressure drop, typ. 8)

for volume flow

Pa

70000

70000

Heat exchanger material

 

Copper-nickel alloy

Copper-nickel alloy

Coolant connections

Intake/return

 

Pipe thread ISO 228 G 3/4 B
(external thread 3/4", flat-sealing)

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

54

54

DC link connection

DCP, DCN

 

2 Ã— hole for M12

Busbar

2 Ã— hole for M12

Busbar

Motor connection

U2, V2, W2

 

2 Ã— hole for M12

2 Ã— hole for M12

  • Conductor cross-section, max. (IEC)

mm2

4 Ã— 185

4 Ã— 185

PE/GND connection

 

2 Ã— hole for M12

2 Ã— hole for M12

  • Conductor cross-section, max. (IEC)

mm2

4 Ã— 185

4 Ã— 185

Cable length, max 9)

 

 

 

  • Shielded

m (ft)

300 (984)

300 (984)

  • Unshielded

m (ft)

450 (1476)

450 (1476)

Dimensions

 

 

 

  • Width

mm (in)

265 (10.4)

265 (10.4)

  • Height

mm (in)

987 (38.9)

987 (38.9)

  • Depth

mm (in)

545 (21.5)

545 (21.5)

Weight, approx.

kg (lb)

125 (276)

125 (276)

Frame size

 

HXL

HXL



1) Rated output of a typical 6‑pole standard induction motor based on IL or IH for 500 V or 690 V 3 AC 50 Hz.

2) Rated output of a typical 6‑pole standard induction motor based on IL or IH for 575 V 3 AC 60 Hz.

3) The base-load current IL is based on a duty cycle of 110 % for 60 s or 150 % for 10 s with a duty cycle duration of 300 s.

4) The base-load current IH is based on a duty cycle of 150 % for 60 s or 160 % for 10 s with a duty cycle duration of 300 s.

5)Additional notes regarding the correlation between the pulse frequency and maximum output current/output frequency is provided in the SINAMICS Low Voltage Engineering Manual.

6) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions. To ensure safe dissipation of the minor power loss released to the ambient air, it is important to follow the instructions pertaining to control cabinet installation in the SINAMICS Low Voltage Engineering Manual.

7) The value applies to coolants comprising water and a mixture of water and antifreeze agent.

8) The value is valid for water as coolant. Additional information and notes on other coolants are provided in the SINAMICS Low Voltage Engineering Manual.

9) Total of all motor cables. Longer cable lengths for specific configurations are available on request. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.

Line voltage 500 ... 690 V 3 AC
DC link voltage 675 ... 1035 V DC

Motor Modules

 

6SL3325-1TG38-1AA7

6SL3325-1TG41-0AA7

6SL3325-1TG41-3AA7 1)

6SL3325-1TG41-6AA7 1)

Type rating

 

 

 

 

 

  • At IL (50 Hz 690 V) 2)

kW

800

1000

1200

1500

  • At IH (50 Hz 690 V) 2)

kW

710

900

1000

1260

  • At IL (50 Hz 500 V) 2)

kW

560

710

900

1000

  • At IH (50 Hz 500 V) 2)

kW

560

630

800

900

  • At IL (60 Hz 575 V) 3)

hp

800

1000

1250

1500

  • At IH (60 Hz 575 V) 3)

hp

700

900

1000

1250

Output current

 

 

 

 

 

  • Rated current Irated O

A

810

1025

1270

1560

  • Base-load current I4)

A

790

1000

1230

1500

  • Base-load current I 5)

A

724

917

1136

1284

  • Maximum current Imax O

A

1185

1500

1600

1950

DC link current

 

 

 

 

 

  • Rated current Irated DC
    when supplied via

 

 

 

 

 

  • Basic Line Module

A

990

1250

1550

1903

  • Active Line Module

A

891

1125

1395

1714

  • Base-load current IL DC 4)
    when supplied via

 

 

 

 

 

  • Basic Line Module

A

963

1219

1500

1800

  • Active Line Module

A

869

1100

1353

1650

  • Base-load current IH DC 5)
    when supplied via

 

 

 

 

 

  • Basic Line Module

A

883

1118

1384

1680

  • Active Line Module

A

796

1009

1250

1550

Current demand

 

 

 

 

 

  • 24 V DC auxiliary power supply

A

1.46

1.46

1.46

1.46

DC link capacitance

μF

14000

16000

19330

21000

Pulse frequency 6)

 

 

 

 

 

  • Rated frequency

kHz

1.25

1.25

1.25

1.25

  • Pulse frequency, max.

 

 

 

 

 

  • Without current derating

kHz

1.25

1.25

1.25

1.25

  • With current derating

kHz

7.5

7.5

7.5

7.5

Power loss, max. 7)

 

 

 

 

 

  • At 50 Hz 690 V

kW

9.56

10.87

13.49

17.9

  • At 60 Hz 575 V

kW

8.34

9.55

11.84

15.7

  • Dissipated to ambient air

kW

0.43

0.53

0.57

0.78

Coolant volume flow 8)

l/min (US gal./min)

27 (7.13)

27 (7.13)

27 (7.13)

27 (7.13)

Liquid volume

of the integrated heat exchanger

dm3

1.56

1.56

1.56

1.56

Pressure drop, typ. 9)

for volume flow

Pa

70000

70000

70000

70000

Heat exchanger material

 

Copper-nickel alloy

Copper-nickel alloy

Copper-nickel alloy

Copper-nickel alloy

Coolant connections

Intake/return

 

Pipe thread ISO 228 G 3/4 B
(external thread 3/4", flat-sealing)

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

56

56

56

56

DC link connection

DCP, DCN

 

2 Ã— hole for M12

Busbar

2 Ã— hole for M12

Busbar

2 Ã— hole for M12

Busbar

2 Ã— hole for M12

Busbar

Motor connection

U2, V2, W2

 

2 Ã— hole for M12

2 Ã— hole for M12

2 Ã— hole for M12

2 Ã— hole for M12

  • Conductor cross-section, max. (IEC)

mm2

Busbar

Busbar

Busbar

Busbar

PE/GND connection

 

2 Ã— hole for M12

2 Ã— hole for M12

2 Ã— hole for M12

2 Ã— hole for M12

  • Conductor cross-section, max. (IEC)

mm2

Busbar

Busbar

Busbar

Busbar

Cable length, max. 10)

 

 

 

 

 

  • Shielded

m (ft)

300 (984)

300 (984)

300 (984)

300 (984)

  • Unshielded

m (ft)

450 (1476)

450 (1476)

450 (1476)

450 (1476)

Dimensions

 

 

 

 

 

  • Width

mm (in)

295 (11.6)

295 (11.6)

295 (11.6)

295 (11.6)

  • Height

mm (in)

1510 (59.4)

1510 (59.4)

1510 (59.4)

1510 (59.4)

  • Depth

mm (in)

545 (21.5)

545 (21.5)

545 (21.5)

545 (21.5)

Weight, approx.

kg (lb)

230 (507)

230 (507)

230 (507)

240 (529)

Frame size

 

JXL

JXL

JXL

JXL



1) The short-time current for 10 s for low overload must be reduced from 150 % to 130 % for this Motor Module. At 10 s and 60 s, the short-time current for high overload must be reduced to 130 % for this Motor Module. The duty cycle remains unchanged.

2) Rated output of a typical 6‑pole standard induction motor based on IL or IH for 500 V or 690 V 3 AC 50 Hz.

3) Rated output of a typical 6‑pole standard induction motor based on IL or IH for 575 V 3 AC 60 Hz.

4) The base-load current IL is based on a duty cycle of 110 % for 60 s or 150 % for 10 s with a duty cycle duration of 300 s.

5) The base-load current IH is based on a duty cycle of 150 % for 60 s or 160 % for 10 s with a duty cycle duration of 300 s.

6)Additional notes regarding the correlation between the pulse frequency and maximum output current/output frequency are provided in the SINAMICS Low Voltage Engineering Manual.

7) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions. To ensure safe dissipation of the minor power loss released to the ambient air, it is important to follow the instructions pertaining to control cabinet installation in the SINAMICS Low Voltage Engineering Manual.

8) The value applies to coolants comprising water and a mixture of water and antifreeze agent.

9) The value is valid for water as coolant. Additional information and notes on other coolants are provided in the SINAMICS Low Voltage Engineering Manual.

10) Sum of all motor cables. Longer cable lengths for specific configurations are available on request. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.

















skener.ru

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Àðìàòóðà DENDOR

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Äàò÷èêè è èçìåðèòåëè

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ðåãóëÿòîðû è ðåãèñòðàòîðû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ïíåâìàòè÷åñêîå îáîðóäîâàíèå

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Êðàíû è Êëàïàíû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Èçìåðèòåëüíûå ïðèáîðû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ñèñòåìû áåñïðîâîäíîãî óïðàâëåíèÿ «óìíûé äîì»

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Áåñêîíòàêòíûå âûêëþ÷àòåëè Êîíå÷íûå âûêëþ÷àòåëè Îïòè÷åñêèå äàò÷èêè Ýíêîäåðû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FS - Óñòàíîâêà óìÿã÷åíèÿ

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FK - Óñòàíîâêà îáåçæåëåçèâàíèÿ

  © ÎÎÎ "ÑÊ ÝÍÅÐÃÎ" 2007-2022
  (4872) 700-366  skenergo@mail.ru
ßíäåêñ.Ìåòðèêà