Recommendation for applications in DC systems according to VDV 525
Full protection for the catenary is provided by installing outdoor surge arresters with VDV 525 “A1”designation at:
Additional “A1” surge arresters are recommended if sections are often hit by lightning strikes, e.g. on bridges or on open stretches. Lightning protection of supply and return lines at substations requires:
Even though MOV surge arresters have failure rates well below 0.1 percent per year, a failure may occur and lead to permanent conductivity of the “A1” type surge arresters, resulting in inadmissibly high fault voltage on the ground electrode for a long time. An additional “A2” type surge arrester with a low continuous operating voltage (120 V ≤ Uc ≤ 300 V) connected between the ground electrode and the return line is intentionally overloaded in this case to limit the fault voltage and trip the section circuit breaker due to feeding from the catenary system. |