General technical specificationsUnless explicitly specified otherwise, the following technical specifications are valid for all PM240‑2 Power Modules in the blocksize format, FSA to FSF. Note: When engineering the complete SINAMICS S120 drive, the system data of the associated Control Units, supplementary system components, DC link components and Sensor Modules must be taken into consideration. Electrical specifications | Line voltage | | - Blocksize format FSA ... FSC
| 200 to 240 V 1 AC ±10% 200 to 240 V 3 AC ±10% 380 to 480 V 3 AC ±10% | - Blocksize format FSD to FSF
| 200 … 240 V 3 AC ±10 % (in operation -20 % <1 min) 380 ... 480 V 3 AC ±10 % (in operation -20 % <1 min) 500 … 690 V 3 AC ±10 % (in operation -20 % <1 min) | Line system configurations | Grounded TN/TT systems and non-grounded IT systems | Line frequency | 47 ... 63 Hz | Line power factor for a 3 AC line supply voltage and output power | | - Blocksize format FSA ... FSC
| | - Fundamental power factor (cos φ1)
| >0.96 | | > 0.7 - 0.85 | - Blocksize format FSD to FSF
| | - Fundamental power factor (cos φ1)
| > 0.98 - 0.99 | | > 0.9 - 0.92 | Electromagnetic compatibility1) | | | All PM240-2 Power Modules are suitable for use in both the first and second environments. | - Interference emission acc. to EN 61800‑3
Second environment
| | - For devices with integrated radio suppression interference filter
| Category C2 | - For devices with integrated radio suppression interference filter, format FSF with a line supply voltage of 690 V
| Category C3 | - For devices without integrated radio interference suppression filter with optional external radio interference filter for grounded line supplies
| Category C2 (recommended for operation in conjunction with a residual current protective device RCD) | - For devices without integrated radio interference suppression filter for operation on IT line supplies
| Category C4 | - Interference emission acc. to EN 61800‑3
First environment
| Can be used in the first environment when taking into consideration the additional secondary conditions listed in Section, EMC notes | Overvoltage category acc. to IEC/EN 61800‑5‑1 | III | Electronics power supply implemented as PELV circuit according to IEC/EN 61800‑5‑1 | 24 V DC, -15 % +20 % Ground = negative pole grounded via the electronics | Short-circuit current rating (SCCR) (Short Circuit Current Rating) Applies to industrial control cabinet installations according to NEC Article 409 or UL 508A | 100 kA See the recommended line-side components – the value depends on the fuses and circuit breakers used | Rated pulse frequency | | - For devices with a rated voltage of 200 V 1/3 AC, 400 V 3 AC and a type rating ≤ 90 kW based on Irated
| 4 kHz | - For devices with a rated voltage of 690 V 3 AC and a type rating ≥ 110 kW based on Irated
| 2 kHz | Output voltage, max. | Approximately 0.95 × line voltage (at 200 V 1 AC, approximately 0.74 × line voltage) | Output frequency | 0 ... 550 Hz (dependencies on the control mode and pulse frequency must be taken into account) | Mechanical specifications | Type of cooling | Internal air cooling, power units with forced air cooling using integrated fans External air cooling (push-through cooling) for push-through device versions | Degree of protection acc. to EN 60529 | IP20 | Protection class | | - Line circuits with protective conductor connection according to IEC/EN 61800‑5‑1
| I | | Safety extra low-voltage PELV/SELV | Touch protection according to EN 50274/DGUV regulation 3 when used as intended | | | Forced air cooling AF to EN 60146 | | Push-through cooling for push-through device versions | Ambient conditions | | Storage | Transport | Operation | In the product packaging | In transport packaging | | Ambient temperature | Class 1K4 acc. to EN 60721‑3‑1 -25 ... +55 °C (-13 ... +131 °F) | Class 2K4 acc. to EN 60721‑3‑2 -40 ... +70 °C (-40 ... +158 °F) | Class 3K3 2) acc. to EN 60721‑3‑3 For operation without derating3): -10 ... +40 °C (14 ... 104 °F) (for operation with low overload) -10 ... +50 °C (14 ... 122 °F) (for operation with high overload) For operation with derating: >40 ... +60 °C (104 ... 140 °F) | Relative humidity (oil mist, salt mist, ice, condensation, dripping water, spraying water and water jets are not permitted) | Class 1K4 acc. to EN 60721‑3‑1 5 ... 95 % | Class 2K3 acc. to EN 60721‑3‑2 5 ... 95 % at 40 °C | Class 3K3 2) acc. to EN 60721‑3‑3 5 ... 95 % | Environmental class/harmful chemical substances | Class 1C2 acc. to EN 60721‑3‑1 | Class 2C2 acc. to EN 60721‑3‑2 | Class 3C2 acc. to EN 60721‑3‑3 | Organic/biological influences | Class 1B1 acc. to EN 60721‑3‑1 | Class 2B1 acc. to EN 60721‑3‑2 | Class 3B1 acc. to EN 60721‑3‑3 | Degree of pollution acc. to IEC/EN 61800‑5‑1 (condensation not permissible) | 2 | Installation altitude | | - For operation with low overload
| Up to 1000m (3281 ft) above sea level without derating | - For operation with high overload
| Up to 2000 m (6562 ft) above sea level without derating | - From 2000 m up to 4000 m (6562 ft to 13124 ft) above sea level observe the derating characteristics
| See characteristic for current derating as a function of the installation altitude and/or reduction of the ambient temperature by 3.5 K per 500 m (1640 ft) | Mechanical strength | | Storage | Transport | Operation | In the product packaging | In transport packaging | | Vibratory load | Class 1M2 acc. to EN 60721‑3‑1 | Class 2M3 acc. to EN 60721‑3‑2 | Class 3M1 acc. to EN 60721‑3‑3 Test values acc. to EN 60068‑2‑6 | Shock load | Class 1M2 acc. to EN 60721‑3‑1 | Class 2M3 acc. to EN 60721‑3‑2 | Class 3M1 acc. to EN 60721‑3‑3 Test values acc. to EN 60068‑2‑27 | Certificates | Declarations of conformity | CE (Low Voltage, EMC and M​achinery Directives) | Certificates of suitability | | - Blocksize format FSA ... FSC
| cULus according to UL 61800‑5‑1; CSA only with external surge voltage protection device; RCM; SEMI F47 | - Blocksize format FSD to FSF
| cULus acc. to UL 61800‑5‑1; CSA only with external surge voltage protection device; RCM; SEMI F47 KCC only with internal or external line filters, Category C2; RoHS; EAC WEEE (Waste Electrical & Electronic Equipment) |
1) Observe the EMC notes in section Configuration notes. 2) Better than 3K3 through increased ruggedness regarding the temperature range and humidity. 3) Also carefully observe the permissible temperatures for the Control Unit and where relevant, the operator panel (IOP or BOP‑2) PM240‑2 Power Modules standard variantLine voltage 200 ... 240 V 1 AC/3 AC | PM240‑2 Power Modules standard variant |
---|
Without integrated line filter | 6SL3210-1PB13-0UL0 | 6SL3210-1PB13-8UL0 | 6SL3210-1PB15-5UL0 | 6SL3210-1PB17-4UL0 | 6SL3210-1PB21-0UL0 |
---|
With integrated line filter class A | 6SL3210-1PB13-0AL0 | 6SL3210-1PB13-8AL0 | 6SL3210-1PB15-5AL0 | 6SL3210-1PB17-4AL0 | 6SL3210-1PB21-0AL0 |
---|
Output current at 50 Hz 230 V 1 AC | | | | | | | | A | 3 | 3.9 | 5.5 | 7.4 | 10.4 | | A | 3.3 | 4.3 | 6.1 | 8.2 | 11.5 | | A | 2.3 | 3 | 3.9 | 5.5 | 7.4 | | A | 4.6 | 6 | 8.3 | 11.1 | 15.6 | Type rating | | | | | | | | kW (hp) | 0.55 (0.75) | 0.75 (1) | 1.1 (1.5) | 1.5 (2) | 2.2 (3) | | kW (hp) | 0.37 (0.5) | 0.55 (0.75) | 0.75 (1) | 1.1 (1.5) | 1.5 (2) | Rated pulse frequency | kHz | 4 | 4 | 4 | 4 | 4 | Efficiency η | % | >96 | >96 | >96 | >96 | >96 | Power loss 3) at rated current | kW | 0.04 | 0.04 | 0.05 | 0.07 | 0.12 | Cooling air requirement | m3/s (ft3/s) | 0.005 (0.18) | 0.005 (0.18) | 0.0092 (0.325) | 0.0092 (0.325) | 0.0092 (0.325) | Sound pressure level LpA (1 m) | dB | <50 | <50 | <62 | <62 | <62 | 24 V DC power supply for Control Unit | A | 1 | 1 | 1 | 1 | 1 | Input current 4) | | | | | | | | A | 7.5/4.3 | 9.6/5.5 | 13.5/7.8 | 18.1/10.5 | 24/13.9 | | A | 6.6/3.8 | 8.4/4.8 | 11.8/6.8 | 15.8/9.1 | 20.9/12.1 | Line supply connection U1/L1, V1/L2, W1/L3 | | Terminal connector | Terminal connector | Terminal connector | Terminal connector | Terminal connector | | mm2 | 1.5 ... 2.5 | 1.5 ... 2.5 | 1.5 ... 6 | 1.5 ... 6 | 1.5 ... 6 | Motor connection U2, V2, W2 | | Terminal connector | Terminal connector | Terminal connector | Terminal connector | Terminal connector | | mm2 | 1.5 ... 2.5 | 1.5 ... 2.5 | 1.5 ... 6 | 1.5 ... 6 | 1.5 ... 6 | PE connection | | Included in terminal connector | Included in terminal connector | Included in terminal connector | Included in terminal connector | Included in terminal connector | Motor cable length, max. | | | | | | | | m (ft) | 50 (164) | 50 (164) | 50 (164) | 50 (164) | 50 (164) | | m (ft) | 100 (328) | 100 (328) | 100 (328) | 100 (328) | 100 (328) | Degree of protection | | IP20 | IP20 | IP20 | IP20 | IP20 | Dimensions | | | | | | | | mm (in) | 73 (2.87) | 73 (2.87) | 100 (3.94) | 100 (3.94) | 100 (3.94) | | mm (in) | 196 (7.72) | 196 (7.72) | 291 (11.46) | 291 (11.46) | 291 (11.46) | - Depth without operator panel
| mm (in) | 165 (6.50) | 165 (6.50) | 165 (6.50) | 165 (6.50) | 165 (6.50) | Frame size | | FSA | FSA | FSB | FSB | FSB | Weight, approx. | | | | | | | - Without integrated line filter
| kg (lb) | 1.4 (3.09) | 1.4 (3.09) | 2.9 (6.39) | 2.9 (6.39) | 2.9 (6.39) | - With integrated line filter
| kg (lb) | 1.6 (3.53) | 1.6 (3.53) | 3.1 (6.84) | 3.1 (6.84) | 3.1 (6.84) |
1) The rated output current Irated is based on the duty cycle for low overload (LO). 2) The base-load current IH is based on the duty cycle for high overload (HO). 3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311 4) The input current depends on the motor load and line impedance. The input currents apply for a load with the type rating (based on Irated) for a line impedance corresponding to uk = 1%. The current values are specified on the rating plate of the Power Module. Line voltage 200 ... 240 V 1 AC/3 AC | PM240‑2 Power Modules standard variant |
---|
Without integrated line filter | 6SL3210-1PB21-4UL0 | 6SL3210-1PB21-8UL0 |
---|
With integrated line filter class A | 6SL3210-1PB21-4AL0 | 6SL3210-1PB21-8AL0 |
---|
Output current at 50 Hz 230 V 1 AC | | | | | A | 13.6 | 17.5 | | A | 15 | 19.3 | | A | 10.4 | 13.6 | | A | 20.8 | 27.2 | Type rating | | | | | kW (hp) | 3 (4) | 4 (5) | | kW (hp) | 2.2 (3) | 3 (4) | Rated pulse frequency | kHz | 4 | 4 | Efficiency η | % | >96 | >96 | Power loss 3) at rated current | kW | 0.14 | 0.18 | Cooling air requirement | m3/s (ft3/s) | 0.0185 (0.65) | 0.0185 (0.65) | Sound pressure level LpA (1 m) | dB | <65 | <65 | 24 V DC power supply for Control Unit | A | 1 | 1 | Input current 4) | | | | | A | 35.9/20.7 | 43/24.8 | | A | 31.3/18.1 | 37.5/21.7 | Line supply connection U1/L1, V1/L2, W1/L3 | | Terminal connector | Terminal connector | | mm2 | 6 ... 16 | 6 ... 16 | Motor connection U2, V2, W2 | | Terminal connector | Terminal connector | | mm2 | 6 ... 16 | 6 ... 16 | PE connection | | Included in terminal connector | Included in terminal connector | Motor cable length, max. | | | | | m (ft) | 50 (164) | 50 (164) | | m (ft) | 100 (328) | 100 (328) | Degree of protection | | IP20 | IP20 | Dimensions | | | | | mm (in) | 140 (5.51) | 140 (5.51) | | mm (in) | 355 (13.98) | 355 (13.98) | - Depth without operator panel
| mm (in) | 165 (6.50) | 165 (6.50) | Frame size | | FSC | FSC | Weight, approx. | | | | - Without integrated line filter
| kg (lb) | 5 (11) | 5 (11) | - With integrated line filter
| kg (lb) | 5.2 (11.5) | 5.2 (11.5) |
1) The rated output current Irated is based on the duty cycle for low overload (LO). 2) The base-load current IH is based on the duty cycle for high overload (HO). 3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311 4) The input current depends on the motor load and line impedance. The input currents apply for a load with the type rating (based on Irated) for a line impedance corresponding to uk = 1%. The current values are specified on the rating plate of the Power Module. Line voltage 200 ... 240 V 3 AC | PM240‑2 Power Modules standard variant |
---|
Without integrated line filter | 6SL3210-1PC22-2UL0 | 6SL3210-1PC22-8UL0 | 6SL3210-1PC24-2UL0 | 6SL3210-1PC25-4UL0 | 6SL3210-1PC26-8UL0 |
---|
With integrated line filter class A | 6SL3210-1PC22-2AL0 | 6SL3210-1PC22-8AL0 | – | – | – |
---|
Output current at 50 Hz 230 V 3 AC | | | | | | | | A | 22 | 28 | 42 | 54 | 68 | | A | 24.2 | 30.8 | 50 | 64 | 81 | | A | 17.5 | 22 | 35 | 42 | 54 | | A | 35 | 44 | 70 | 84 | 108 | Type rating | | | | | | | | kW (hp) | 5.5 (7.5) | 7.5 (10) | 11 (15) | 15 (20) | 18.5 (25) | | kW (hp) | 4 (5) | 5.5 (7.5) | 7.5 (10) | 11 (15) | 15 (20) | Rated pulse frequency | kHz | 4 | 4 | 4 | 4 | 4 | Efficiency η | % | >97 | >97 | >97 | >97 | >97 | Power loss 3) at rated current | kW | 0.2 | 0.26 | 0.42 | 0.57 | 0.76 | Cooling air requirement | m3/s (ft3/s) | 0.0185 (0.65) | 0.0185 (0.65) | 0.055 (1.9) | 0.055 (1.9) | 0.055 (1.9) | Sound pressure level LpA (1 m) | dB | <65 | <65 | 45 ... 65 4) | 45 ... 65 4) | 45 ... 65 4) | 24 V DC power supply for Control Unit | A | 1 | 1 | 1 | 1 | 1 | Input current 5) | | | | | | | | A | 28.6 | 36.4 | 44 | 56 | 70 | | A | 26.2 | 33 | 36 | 43 | 56 | Line supply connection U1/L1, V1/L2, W1/L3 | | Terminal connector | Terminal connector | Screw terminals | Screw terminals | Screw terminals | | mm2 | 6 ... 16 | 6 ... 16 | 10 ... 35 | 10 ... 35 | 10 ... 35 | Motor connection U2, V2, W2 | | Terminal connector | Terminal connector | Screw terminals | Screw terminals | Screw terminals | | mm2 | 6 ... 16 | 6 ... 16 | 10 ... 35 | 10 ... 35 | 10 ... 35 | PE connection | | Included in terminal connector | Included in terminal connector | Screw terminals | Screw terminals | Screw terminals | Motor cable length, max. | | | | | | | | m (ft) | 50 (164) | 50 (164) | 200 (656) | 200 (656) | 200 (656) | | m (ft) | 100 (328) | 100 (328) | 300 (984) | 300 (984) | 300 (984) | Degree of protection | | IP20 | IP20 | IP20 | IP20 | IP20 | Dimensions | | | | | | | | mm (in) | 140 (5.51) | 140 (5.51) | 200 (7.87) | 200 (7.87) | 200 (7.87) | | mm (in) | 355 (13.98) | 355 (13.98) | 472 (18.58) | 472 (18.58) | 472 (18.58) | - Depth without operator panel
| mm (in) | 165 (6.50) | 165 (6.50) | 237 (9.33) | 237 (9.33) | 237 (9.33) | Frame size | | FSC | FSC | FSD | FSD | FSD | Weight, approx. | | | | | | | - Without integrated line filter
| kg (lb) | 5 (11) | 5 (11) | 17 (37.5) | 17 (37.5) | 17 (37.5) | - With integrated line filter
| kg (lb) | 5.2 (11.5) | 5.2 (11.5) | – | – | – |
1) The rated output current Irated is based on the duty cycle for low overload (LO). 2) The base-load current IH is based on the duty cycle for high overload (HO). 3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311 4) Values dependent on ambient temperature and utilization. 5) The input current depends on the motor load and line impedance. The input currents apply for a load with the type rating (based on Irated) for a line impedance corresponding to uk = 1%. The current values are specified on the rating plate of the Power Module. Line voltage 200 ... 240 V 3 AC | PM240‑2 Power Modules standard variant |
---|
Without integrated line filter | 6SL3210-1PC28-0UL0 | 6SL3210-1PC31-1UL0 | 6SL3210-1PC31-3UL0 | 6SL3210-1PC31-6UL0 | 6SL3210-1PC31-8UL0 |
---|
With integrated line filter class A | – | – | – | – | – |
---|
Output current at 50 Hz 230 V 3 AC | | | | | | | | A | 80 | 104 | 130 | 154 | 178 | | A | 96 | 124 | 156 | 184 | 213 | | A | 68 | 80 | 104 | 130 | 154 | | A | 136 | 160 | 208 | 260 | 308 | Type rating | | | | | | | | kW (hp) | 22 (30) | 30 (40) | 37 (50) | 45 (60) | 55 (75) | | kW (hp) | 18.5 (25) | 22 (30) | 30 (40) | 37 (50) | 45 (60) | Rated pulse frequency | kHz | 4 | 4 | 4 | 4 | 4 | Efficiency η | % | >97 | >97 | >97 | >97 | >97 | Power loss 3) at rated current | kW | 0.85 | 1.2 | 1.44 (3.53) | 1.79 | 2.18 (3.53) | Cooling air requirement | m3/s (ft3/s) | 0.083 (2.9) | 0.083 (2.9) | 0.153 (5.4) | 0.153 (5.4) | 0.153 (5.4) | Sound pressure level LpA (1 m) | dB | 44 ... 62 4) | 44 ... 62 4) | 56 ... 68 4) | 56 ... 68 4) | 56 ... 68 4) | 24 V DC power supply for Control Unit | A | 1 | 1 | 1 | 1 | 1 | Input current 5) | | | | | | | | A | 83 | 107 | 134 | 158 | 183 | | A | 71 | 83 | 110 | 138 | 164 | Line supply connection U1/L1, V1/L2, W1/L3 | | Screw terminals | Screw terminals | M10 screw stud | M10 screw stud | M10 screw stud | | mm2 | 25 ... 70 | 25 ... 70 | 35 ... 2 × 120 | 35 ... 2 × 120 | 35 ... 2 × 120 | Motor connection U2, V2, W2 | | Screw terminals | Screw terminals | M10 screw stud | M10 screw stud | M10 screw stud | | mm2 | 25 ... 70 | 25 ... 70 | 35 ... 2 × 120 | 35 ... 2 × 120 | 35 ... 2 × 120 | PE connection | | Screw terminals | Screw terminals | M10 screw stud | M10 screw stud | M10 screw stud | Motor cable length, max. | | | | | | | | m (ft) | 200 (656) | 200 (656) | 300 (984) | 300 (984) | 300 (984) | | m (ft) | 300 (984) | 300 (984) | 450 (1476) | 450 (1476) | 450 (1476) | Degree of protection | | IP20 | IP20 | IP20 | IP20 | IP20 | Dimensions | | | | | | | | mm (in) | 275 (10.83) | 275 (10.83) | 305 (12.01) | 305 (12.01) | 305 (12.01) | | mm (in) | 551 (21.69) | 551 (21.69) | 708 (27.87) | 708 (27.87) | 708 (27.87) | - Depth without operator panel
| mm (in) | 237 (9.33) | 237 (9.33) | 357 (14.06) | 357 (14.06) | 357 (14.06) | Frame size | | FSE | FSE | FSF | FSF | FSF | Weight, approx. | | | | | | | - Without integrated line filter
| kg (lb) | 26 (57.3) | 26 (57.3) | 57 (126) | 57 (126) | 57 (126) | - With integrated line filter
| kg (lb) | – | – | – | – | – |
1) The rated output current Irated is based on the duty cycle for low overload (LO). 2) The base-load current IH is based on the duty cycle for high overload (HO). 3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311 4) Values dependent on ambient temperature and utilization. 5) The input current depends on the motor load and line impedance. The input currents apply for a load with the type rating (based on Irated) for a line impedance corresponding to uk = 1%. The current values are specified on the rating plate of the Power Module. Line voltage 380 ... 480 V 3 AC | PM240‑2 Power Modules standard variant |
---|
Without integrated line filter | 6SL3210-1PE11-8UL1 | 6SL3210-1PE12-3UL1 | 6SL3210-1PE13-2UL1 | 6SL3210-1PE14-3UL1 | 6SL3210-1PE16-1UL1 | 6SL3210-1PE18-0UL1 |
---|
With integrated line filter class A | 6SL3210-1PE11-8AL1 | 6SL3210-1PE12-3AL1 | 6SL3210-1PE13-2AL1 | 6SL3210-1PE14-3AL1 | 6SL3210-1PE16-1AL1 | 6SL3210-1PE18-0AL1 |
---|
Output current at 50 Hz 400 V 3 AC | | | | | | | | | A | 1.7 | 2.2 | 3.1 | 4.1 | 5.9 | 7.7 | | A | 2 | 2.5 | 3.5 | 4.5 | 6.5 | 8.5 | | A | 1.3 | 1.7 | 2.2 | 3.1 | 4.1 | 5.9 | | A | 2.6 | 3.4 | 4.7 | 6.2 | 8.9 | 11.8 | Type rating | | | | | | | | | kW (hp) | 0.55 (0.75) | 0.75 (1) | 1.1 (1.5) | 1.5 (2) | 2.2 (3) | 3 (4) | | kW (hp) | 0.37 (0.5) | 0.55 (0.75) | 0.75 (1) | 1.1 (1.5) | 1.5 (2) | 2.2 (3) | Rated pulse frequency | kHz | 4 | 4 | 4 | 4 | 4 | 4 | Efficiency η | % | >96 | >96 | >96 | >96 | >96 | >96 | Power loss 3) at rated current | kW | 0.04 | 0.04 | 0.04 | 0.07 | 0.1 | 0.12 | Cooling air requirement | m3/s (ft3/s) | 0.005 (0.18) | 0.005 (0.18) | 0.005 (0.18) | 0.005 (0.18) | 0.005 (0.18) | 0.005 (0.18) | Sound pressure level LpA (1 m) | dB | <50 | <50 | <50 | <50 | < 56.3 | < 56.3 | 24 V DC power supply for Control Unit | A | 1 | 1 | 1 | 1 | 1 | 1 | Input current 4) | | | | | | | | | A | 2.3 | 2.9 | 4.1 | 5.5 | 7.7 | 10.1 | | A | 2 | 2.6 | 3.3 | 4.7 | 6.1 | 8.8 | Line supply connection U1/L1, V1/L2, W1/L3 | | Terminal connector | Terminal connector | Terminal connector | Terminal connector | Terminal connector | Terminal connector | | mm2 | 1 ... 2.5 | 1 ... 2.5 | 1 ... 2.5 | 1 ... 2.5 | 1 ... 2.5 | 1 ... 2.5 | Motor connection U2, V2, W2 | | Terminal connector | Terminal connector | Terminal connector | Terminal connector | Terminal connector | Terminal connector | | mm2 | 1 ... 2.5 | 1 ... 2.5 | 1 ... 2.5 | 1 ... 2.5 | 1 ... 2.5 | 1 ... 2.5 | PE connection | | Included in terminal connector | Included in terminal connector | Included in terminal connector | Included in terminal connector | Included in terminal connector | Included in terminal connector | Motor cable length, max. | | | | | | | | - Without filter, shielded/unshielded
| m (ft) | 150/150 (492/492) | 150/150 (492/492) | 150/150 (492/492) | 150/150 (492/492) | 150/150 (492/492) | 150/150 (492/492) | - With integrated filter class A, shielded/unshielded
| m (ft) | 50/100 (164/328) | 50/100 (164/328) | 50/100 (164/328) | 50/100 (164/328) | 50/100 (164/328) | 50/100 (164/328) | Degree of protection | | IP20 | IP20 | IP20 | IP20 | IP20 | IP20 | Dimensions | | | | | | | | | mm (in) | 73 (2.87) | 73 (2.87) | 73 (2.87) | 73 (2.87) | 73 (2.87) | 73 (2.87) | | mm (in) | 196 (7.72) | 196 (7.72) | 196 (7.72) | 196 (7.72) | 196 (7.72) | 196 (7.72) | - Depth without operator panel
| mm (in) | 165 (6.50) | 165 (6.50) | 165 (6.50) | 165 (6.50) | 165 (6.50) | 165 (6.50) | Frame size | | FSA | FSA | FSA | FSA | FSA | FSA | Weight, approx. | | | | | | | | - Without integrated line filter
| kg (lb) | 1.4 (3.09) | 1.4 (3.09) | 1.4 (3.09) | 1.4 (3.09) | 1.4 (3.09) | 1.4 (3.09) | - With integrated line filter
| kg (lb) | 1.5 (3.31) | 1.5 (3.31) | 1.5 (3.31) | 1.5 (3.31) | 1.5 (3.31) | 1.5 (3.31) |
1) The rated output current Irated is based on the duty cycle for low overload (LO). 2) The base-load current IH is based on the duty cycle for high overload (HO). 3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311 4) The input current depends on the motor load and line impedance. The input currents apply for a load with the type rating (based on Irated) for a line impedance corresponding to uk = 1%. The current values are specified on the rating plate of the Power Module. Line voltage 380 ... 480 V 3 AC | PM240‑2 Power Modules standard variant |
---|
Without integrated line filter | 6SL3210-1PE21-1UL0 | 6SL3210-1PE21-4UL0 | 6SL3210-1PE21-8UL0 | 6SL3210-1PE22-7UL0 | 6SL3210-1PE23-3UL0 |
---|
With integrated line filter class A | 6SL3210-1PE21-1AL0 | 6SL3210-1PE21-4AL0 | 6SL3210-1PE21-8AL0 | 6SL3210-1PE22-7AL0 | 6SL3210-1PE23-3AL0 |
---|
Output current at 50 Hz 400 V 3 AC | | | | | | | | A | 10.2 | 13.2 | 18 | 26 | 32 | | A | 11.2 | 14.5 | 19.8 | 28.6 | 37.1 | | A | 7.7 | 10.2 | 13.2 | 18 | 26 | | A | 15.4 | 20.4 | 27 | 39 | 52 | Type rating | | | | | | | | kW (hp) | 4 (5) | 5.5 (7.5) | 7.5 (10) | 11 (15) | 15 (20) | | kW (hp) | 3 (4) | 4 (5) | 5.5 (7.5) | 7.5 (10) | 11 (15) | Rated pulse frequency | kHz | 4 | 4 | 4 | 4 | 4 | Efficiency η | % | >97 | >97 | >97 | >97 | >97 | Power loss 3) at rated current | kW | 0.11 | 0.15 | 0.2 | 0.3 | 0.37 | Cooling air requirement | m3/s (ft3/s) | 0.0092 (0.32) | 0.0092 (0.32) | 0.0092 (0.32) | 0.0185 (0.65) | 0.0185 (0.65) | Sound pressure level LpA (1 m) | dB | <62 | <62 | <62 | <65 | <65 | 24 V DC power supply for Control Unit | A | 1 | 1 | 1 | 1 | 1 | Input current 4) | | | | | | | | A | 13.3 | 17.2 | 22.2 | 32.6 | 39.9 | | A | 11.6 | 15.3 | 19.8 | 27 | 36 | Line supply connection U1/L1, V1/L2, W1/L3 | | Terminal connector | Terminal connector | Terminal connector | Terminal connector | Terminal connector | | mm2 | 1.5 ... 6 | 1.5 ... 6 | 1.5 ... 6 | 6 ... 16 | 6 ... 16 | Motor connection U2, V2, W2 | | Terminal connector | Terminal connector | Terminal connector | Terminal connector | Terminal connector | | mm2 | 1.5 ... 6 | 1.5 ... 6 | 1.5 ... 6 | 6 ... 16 | 6 ... 16 | PE connection | | Included in terminal connector | Included in terminal connector | Included in terminal connector | Included in terminal connector | Included in terminal connector | Motor cable length, max. | | | | | | | - Without filter, shielded/unshielded
| m (ft) | 150/150 (492/492) | 150/150 (492/492) | 150/150 (492/492) | 150/150 (492/492) | 150/150 (492/492) | - With integrated filter class A, shielded/unshielded
| m (ft) | 100/100 (328/328) 5) | 100/100 (328/328) 5) | 100/100 (328/328) 5) | 150/150 (492/492) 5) | 150/150 (492/492) 5) | Degree of protection | | IP20 | IP20 | IP20 | IP20 | IP20 | Dimensions | | | | | | | | mm (in) | 100 (3.94) | 100 (3.94) | 100 (3.94) | 140 (5.51) | 140 (5.51) | | mm (in) | 291 (11.46) | 291 (11.46) | 291 (11.46) | 355 (13.98) | 355 (13.98) | - Depth without operator panel
| mm (in) | 165 (6.50) | 165 (6.50) | 165 (6.50) | 165 (6.50) | 165 (6.50) | Frame size | | FSB | FSB | FSB | FSC | FSC | Weight, approx. | | | | | | | - Without integrated line filter
| kg (lb) | 2.9 (6.39) | 2.9 (6.39) | 3 (6.62) | 4.7 (10.4) | 4.8 (10.6) | - With integrated line filter
| kg (lb) | 3.1 (6.84) | 3.1 (6.84) | 3.2 (7.06) | 5.3 (11.7) | 5.4 (11.9) |
1) The rated output current Irated is based on the duty cycle for low overload (LO). 2) The base-load current IH is based on the duty cycle for high overload (HO). 3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311 4) The input current depends on the motor load and line impedance. The input currents apply for a load with the type rating (based on Irated) for a line impedance corresponding to uk = 1%. The current values are specified on the rating plate of the Power Module. 5) The values are applicable for low capacitance cables, e.g. MOTION‑CONNECT. For standard CY cables the max. permissible motor cable length is 50 m (164 ft) (shielded). Line voltage 380 ... 480 V 3 AC | PM240‑2 Power Modules standard variant |
---|
Without integrated line filter | 6SL3210-1PE23-8UL0 | 6SL3210-1PE24-5UL0 | 6SL3210-1PE26-0UL0 | 6SL3210-1PE27-5UL0 | 6SL3210-1PE28-8UL0 | 6SL3210-1PE31-1UL0 |
---|
With integrated line filter class A | 6SL3210-1PE23-8AL0 | 6SL3210-1PE24-5AL0 | 6SL3210-1PE26-0AL0 | 6SL3210-1PE27-5AL0 | 6SL3210-1PE28-8AL0 | 6SL3210-1PE31-1AL0 |
---|
Output current at 50 Hz 400 V 3 AC | | | | | | | | | A | 38 | 45 | 60 | 75 | 90 | 110 | | A | 45 | 54 | 72 | 90 | 108 | 132 | | A | 32 | 38 | 45 | 60 | 75 | 90 | | A | 64 | 76 | 90 | 120 | 150 | 180 | Type rating | | | | | | | | | kW (hp) | 18.5 (25) | 22 (30) | 30 (40) | 37 (50) | 45 (60) | 55 (75) | | kW (hp) | 15 (20) | 18.5 (25) | 22 (30) | 30 (40) | 37 (50) | 45 (60) | Rated pulse frequency | kHz | 4 | 4 | 4 | 4 | 4 | 4 | Efficiency η | % | >97 | >97 | >97 | >97 | >97 | >97 | Power loss 3) at rated current | kW | 0.55 (0.74) | 0.68 | 0.77 | 1.02 | 1.2 | 1.55 | Cooling air requirement | m3/s (ft3/s) | 0.055 (1.9) | 0.055 (1.9) | 0.055 (1.9) | 0.055 (1.9) | 0.083 (2.9) | 0.083 (2.9) | Sound pressure level LpA (1 m) | dB | 45 ... 65 4) | 45 ... 65 4) | 45 ... 65 4) | 45 ... 65 4) | 44 ... 62 4) | 44 ... 62 4) | 24 V DC power supply for Control Unit | A | 1 | 1 | 1 | 1 | 1 | 1 | Input current 5) | | | | | | | | | A | 39 | 47 | 62 ( | 77 | 93 | 113 | | A | 33 | 38 | 47 | 62 | 78 | 94 | Line supply connection U1/L1, V1/L2, W1/L3 | | Screw terminals | Screw terminals | Screw terminals | Screw terminals | Screw terminals | Screw terminals | | mm2 | 10 ... 35 | 10 ... 35 | 10 ... 35 | 10 ... 35 | 25 ... 70 | 25 ... 70 | Motor connection U2, V2, W2 | | Screw terminals | Screw terminals | Screw terminals | Screw terminals | Screw terminals | Screw terminals | | mm2 | 10 ... 35 | 10 ... 35 | 10 ... 35 | 10 ... 35 | 25 ... 70 | 25 ... 70 | PE connection | | Screw terminals | Screw terminals | Screw terminals | Screw terminals | Screw terminals | Screw terminals | Motor cable length, max. | | | | | | | | | m (ft) | 200 (656) | 200 (656) | 200 (656) | 200 (656) | 200 (656) | 200 (656) | | m (ft) | 300 (984) | 300 (984) | 300 (984) | 300 (984) | 300 (984) | 300 (984) | Degree of protection | | IP20 | IP20 | IP20 | IP20 | IP20 | IP20 | Dimensions | | | | | | | | | mm (in) | 200 (7.87) | 200 (7.87) | 200 (7.87) | 200 (7.87) | 275 (10.83) | 275 (10.83) | | mm (in) | 472 (18.58) | 472 (18.58) | 472 (18.58) | 472 (18.58) | 551 (21.69) | 551 (21.69) | - Depth without operator panel
| mm (in) | 237 (9.33) | 237 (9.33) | 237 (9.33) | 237 (9.33) | 237 (9.33) | 237 (9.33) | Frame size | | FSD | FSD | FSD | FSD | FSE | FSE | Weight, approx. | | | | | | | | - Without integrated line filter
| kg (lb) | 16 (35.3) | 16 (35.3) | 17 (37.5) | 17 (37.5) | 26 (57.3) | 26 (57.3) | - With integrated line filter
| kg (lb) | 17.5 (38.6) | 17.5 (38.6) | 18.5 (40.8) | 18.5 (40.8) | 28 (61.7) | 28 (61.7) |
1) The rated output current Irated is based on the duty cycle for low overload (LO). 2) The base-load current IH is based on the duty cycle for high overload (HO). 3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311 4) Values dependent on ambient temperature and utilization. 5) The input current depends on the motor load and line impedance. The input currents apply for a load with the type rating (based on Irated) for a line impedance corresponding to uk = 1%. The current values are specified on the rating plate of the Power Module. Line voltage 380 ... 480 V 3 AC | PM240‑2 Power Modules standard variant |
---|
Without integrated line filter | 6SL3210-1PE31-5UL0 | 6SL3210-1PE31-8UL0 | 6SL3210-1PE32-1UL0 | 6SL3210-1PE32-5UL0 |
---|
With integrated line filter class A | 6SL3210-1PE31-5AL0 | 6SL3210-1PE31-8AL0 | 6SL3210-1PE32-1AL0 | 6SL3210-1PE32-5AL0 |
---|
Output current at 50 Hz 400 V 3 AC | | | | | | | A | 145 | 178 | 205 | 250 | | A | 174 | 213 | 246 | 300 | | A | 110 | 145 | 178 | 205 | | A | 220 | 290 | 356 | 410 | Type rating | | | | | | | kW (hp) | 75 (100) | 90 (125) | 110 (150) | 132 (200) | | kW (hp) | 55 (75) | 75 (100) | 90 (125) | 110 (150) | Rated pulse frequency | kHz | 4 | 4 | 2 | 2 | Efficiency η | % | >97 | >97 | >97 | >97 | Power loss 3) at rated current | kW | 1.79 | 2.33 | 2.17 | 2.84 | Cooling air requirement | m3/s (ft3/s) | 0.2 (7.1) | 0.2 (7.1) | 0.2 (7.1) | 0.2 (7.1) | Sound pressure level LpA (1 m) | dB | 56 ... 68 4) | 56 ... 68 4) | 56 ... 68 4) | 56 ... 68 4) | 24 V DC power supply for Control Unit | A | 1 | 1 | 1 | 1 | Input current 5) | | | | | | | A | 149 | 183 | 211 | 257 | | A | 117 | 154 | 189 | 218 | Line supply connection U1/L1, V1/L2, W1/L3 | | M10 screw stud | M10 screw stud | M10 screw stud | M10 screw stud | | mm2 | 35 ... 2 × 120 | 35 ... 2 × 120 | 35 ... 2 × 120 | 35 ... 2 × 120 | Motor connection U2, V2, W2 | | M10 screw stud | M10 screw stud | M10 screw stud | M10 screw stud | | mm2 | 35 ... 2 × 120 | 35 ... 2 × 120 | 35 ... 2 × 120 | 35 ... 2 × 120 | PE connection | | M10 screw stud | M10 screw stud | M10 screw stud | M10 screw stud | Motor cable length, max. | | | | | | | m (ft) | 300 (984) | 300 (984) | 300 (984) | 300 (984) | | m (ft) | 450 (1476) | 450 (1476) | 450 (1476) | 450 (1476) | Degree of protection | | IP20 | IP20 | IP20 | IP20 | Dimensions | | | | | | | mm (in) | 305 (12.01) | 305 (12.01) | 305 (12.01) | 305 (12.01) | | mm (in) | 708 (27.87) | 708 (27.87) | 708 (27.87) | 708 (27.87) | - Depth without operator panel
| mm (in) | 357 (14.06) | 357 (14.06) | 357 (14.06) | 357 (14.06) | Frame size | | FSF | FSF | FSF | FSF | Weight, approx. | | | | | | - Without integrated line filter
| kg (lb) | 57 (126) | 57 (126) | 61 (135) | 61 (135) | - With integrated line filter
| kg (lb) | 63 (139) | 63 (139) | 65 (143) | 65 (143) |
1) The rated output current Irated is based on the duty cycle for low overload (LO). 2) The base-load current IH is based on the duty cycle for high overload (HO). 3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311 4) Values dependent on ambient temperature and utilization. 5) The input current depends on the motor load and line impedance. The input currents apply for a load with the type rating (based on Irated) for a line impedance corresponding to uk = 1%. The current values are specified on the rating plate of the Power Module. Line voltage 500 ... 690 V 3 AC | PM240‑2 Power Modules standard variant |
---|
Without integrated line filter | 6SL3210-1PH21-4UL0 | 6SL3210-1PH22-0UL0 | 6SL3210-1PH22-3UL0 | 6SL3210-1PH22-7UL0 | 6SL3210-1PH23-5UL0 | 6SL3210-1PH24-2UL0 |
---|
With integrated line filter class A | 6SL3210-1PH21-4AL0 | 6SL3210-1PH22-0AL0 | 6SL3210-1PH22-3AL0 | 6SL3210-1PH22-7AL0 | 6SL3210-1PH23-5AL0 | 6SL3210-1PH24-2AL0 |
---|
Output current at 50 Hz 690 V 3 AC | | | | | | | | | A | 14 | 19 | 23 | 27 | 35 | 42 | | A | 16 | 22 | 27 | 32 | 42 | 50 | | A | 11 | 14 | 19 | 23 | 27 | 35 | | A | 22 | 29 | 38 | 46 | 54 | 70 | Type rating | | | | | | | | | kW (hp) | 11 (10) | 15 (15) | 18.5 (20) | 22 (25) | 30 (30) | 37 (40) | | kW (hp) | 7.5 (7.5) | 11 (10) | 15 (15) | 18.5 (20) | 22 (25) | 30 (30) | Rated pulse frequency | kHz | 2 | 2 | 2 | 2 | 2 | 2 | Efficiency η | % | >98 | >98 | >98 | >98 | >98 | >98 | Power loss 3) at rated current | kW | 0.32 | 0.41 | 0.48 | 0.56 | 0.73 | 0.88 | Cooling air requirement | m3/s (ft3/s) | 0.055 (1.9) | 0.055 (1.9) | 0.055 (1.9) | 0.055 (1.9) | 0.055 (1.9) | 0.055 (1.9) | Sound pressure level LpA (1 m) | dB | 45 ... 65 4) | 45 ... 65 4) | 45 ... 65 4) | 45 ... 65 4) | 45 ... 65 4) | 45 ... 65 4) | 24 V DC power supply for Control Unit | A | 1 | 1 | 1 | 1 | 1 | 1 | Input current 5) | | | | | | | | | A | 15 | 20 | 24 | 28 | 36 | 44 | | A | 11 | 14 | 20 | 24 | 28 | 36 | Line supply connection U1/L1, V1/L2, W1/L3 | | Screw terminals | Screw terminals | Screw terminals | Screw terminals | Screw terminals | Screw terminals | | mm2 | 10 ... 35 | 10 ... 35 | 10 ... 35 | 10 ... 35 | 10 ... 35 | 10 ... 35 | Motor connection U2, V2, W2 | | Screw terminals | Screw terminals | Screw terminals | Screw terminals | Screw terminals | Screw terminals | | mm2 | 10 ... 35 | 10 ... 35 | 10 ... 35 | 10 ... 35 | 10 ... 35 | 10 ... 35 | PE connection | | Screw terminals | Screw terminals | Screw terminals | Screw terminals | Screw terminals | Screw terminals | Motor cable length, max. | | | | | | | | | m (ft) | 200 (656) | 200 (656) | 200 (656) | 200 (656) | 200 (656) | 200 (656) | | m (ft) | 300 (984) | 300 (984) | 300 (984) | 300 (984) | 300 (984) | 300 (984) | Degree of protection | | IP20 | IP20 | IP20 | IP20 | IP20 | IP20 | Dimensions | | | | | | | | | mm (in) | 200 (7.87) | 200 (7.87) | 200 (7.87) | 200 (7.87) | 200 (7.87) | 200 (7.87) | | mm (in) | 472 (18.58) | 472 (18.58) | 472 (18.58) | 472 (18.58) | 472 (18.58) | 472 (18.58) | - Depth without operator panel
| mm (in) | 237 (9.33) | 237 (9.33) | 237 (9.33) | 237 (9.33) | 237 (9.33) | 237 (9.33) | Frame size | | FSD | FSD | FSD | FSD | FSD | FSD | Weight, approx. | | | | | | | | - Without integrated line filter
| kg (lb) | 17 (37.5) | 17 (37.5) | 17 (37.5) | 17 (37.5) | 17 (37.5) | 17 (37.5) | - With integrated line filter
| kg (lb) | 18.5 (40.8) | 18.5 (40.8) | 18.5 (40.8) | 18.5 (40.8) | 18.5 (40.8) | 18.5 (40.8) |
1) The rated output current Irated is based on the duty cycle for low overload (LO). 2) The base-load current IH is based on the duty cycle for high overload (HO). 3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311 4) Values dependent on ambient temperature and utilization. 5) The input current depends on the motor load and line impedance. The input currents apply for a load with the type rating (based on Irated) for a line impedance corresponding to uk = 1%. The current values are specified on the rating plate of the Power Module. Line voltage 500 ... 690 V 3 AC | PM240‑2 Power Modules standard variant |
---|
Without integrated line filter | 6SL3210-1PH25-2UL0 | 6SL3210-1PH26-2UL0 | 6SL3210-1PH28-0UL0 | 6SL3210-1PH31-0UL0 | 6SL3210-1PH31-2UL0 | 6SL3210-1PH31-4UL0 |
---|
With integrated line filter class A | 6SL3210-1PH25-2AL0 | 6SL3210-1PH26-2AL0 | 6SL3210-1PH28-0AL0 | 6SL3210-1PH31-0AL0 | 6SL3210-1PH31-2AL0 | 6SL3210-1PH31-4AL0 |
---|
Output current at 50 Hz 690 V 3 AC | | | | | | | | | A | 52 | 62 | 80 | 100 | 115 | 142 | | A | 62 | 74 | 96 | 120 | 138 | 170 | | A | 42 | 52 | 62 | 80 | 100 | 115 | | A | 84 | 104 | 124 | 160 | 200 | 230 | Type rating | | | | | | | | | kW (hp) | 45 (50) | 55 (60) | 75 (75) | 90 (100) | 110 (100) | 132 (125) | | kW (hp) | 37 (40) | 45 (50) | 55 (60) | 75 (75) | 90 (100) | 110 (100) | Rated pulse frequency | kHz | 2 | 2 | 2 | 2 | 2 | 2 | Efficiency η | % | >98 | >98 | >98 | >98 | >98 | >98 | Power loss 3) at rated current | kW | 1 | 1.21 | 1.23 | 1.57 | 1.83 | 2.35 | Cooling air requirement | m3/s (ft3/s) | 0.083 (2.9) | 0.083 (2.9) | 0.083 (2.9) | 0.083 (2.9) | 0.2 (7.1) | 0.2 (7.1) | Sound pressure level LpA (1 m) | dB | 44 ... 62 4) | 44 ... 62 4) | 56 ... 68 4) | 56 ... 68 4) | 56 ... 68 4) | 56 ... 68 4) | 24 V DC power supply for Control Unit | A | 1 | 1 | 1 | 1 | 1 | 1 | Input current 5) | | | | | | | | | A | 50 | 59 | 78 | 97 | 111 | 137 | | A | 44 | 54 | 66 | 85 | 106 | 122 | Line supply connection U1/L1, V1/L2, W1/L3 | | Screw terminals | Screw terminals | M10 screw stud | M10 screw stud | M10 screw stud | M10 screw stud | | mm2 | 25 ... 70 | 25 ... 70 | 35 ... 2 × 120 | 35 ... 2 × 120 | 35 ... 2 × 120 | 35 ... 2 × 120 | Motor connection U2, V2, W2 | | Screw terminals | Screw terminals | M10 screw stud | M10 screw stud | M10 screw stud | M10 screw stud | | mm2 | 25 ... 70 | 25 ... 70 | 35 ... 2 × 120 | 35 ... 2 × 120 | 35 ... 2 × 120 | 35 ... 2 × 120 | PE connection | | Screw terminals | Screw terminals | M10 screw stud | M10 screw stud | M10 screw stud | M10 screw stud | Motor cable length, max. | | | | | | | | | m (ft) | 200 (656) | 200 (656) | 300 (984) | 300 (984) | 300 (984) | 300 (984) | | m (ft) | 300 (984) | 300 (984) | 450 (1476) | 450 (1476) | 450 (1476) | 450 (1476) | Degree of protection | | IP20 | IP20 | IP20 | IP20 | IP20 | IP20 | Dimensions | | | | | | | | | mm (in) | 275 (10.83) | 275 (10.83) | 305 (12.01) | 305 (12.01) | 305 (12.01) | 305 (12.01) | | mm (in) | 551 (21.69) | 551 (21.69) | 708 (27.87) | 708 (27.87) | 708 (27.87) | 708 (27.87) | - Depth without operator panel
| mm (in) | 237 (9.33) | 237 (9.33) | 357 (14.06) | 357 (14.06) | 357 (14.06) | 357 (14.06) | Frame size | | FSE | FSE | FSF | FSF | FSF | FSF | Weight, approx. | | | | | | | | - Without integrated line filter
| kg (lb) | 26 (57.3) | 26 (57.3) | 60 (132.3) | 60 (132.3) | 60 (132.3) | 60 (132.3) | - With integrated line filter
| kg (lb) | 28 (61.7) | 28 (61.7) | 64 (141) | 64 (141) | 64 (141) | 64 (141) |
1) The rated output current Irated is based on the duty cycle for low overload (LO). 2) The base-load current IH is based on the duty cycle for high overload (HO). 3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311 4) Values dependent on ambient temperature and utilization. 5) The input current depends on the motor load and line impedance. The input currents apply for a load with the type rating (based on Irated) for a line impedance corresponding to uk = 1%. The current values are specified on the rating plate of the Power Module. PM240‑2 Power Modules push-through variantLine voltage 200 ... 240 V 1 AC/3 AC | PM240‑2 Power Modules push-through variant |
---|
Without integrated line filter | 6SL3211-1PB13-8UL0 | 6SL3211-1PB21-0UL0 | 6SL3211-1PB21-8UL0 |
---|
With integrated line filter class A | 6SL3211-1PB13-8AL0 | 6SL3211-1PB21-0AL0 | 6SL3211-1PB21-8AL0 |
---|
Output current At 50 Hz 230 V 1 AC/3 AC | | | | | | A | 3.9 | 10.4 | 17.5 | | A | 3.3 | 11.5 | 19.3 | | A | 3 | 7.4 | 13.6 | | A | 6 (0.24) | 15.6 | 27.2 | Type rating | | | | | | kW (hp) | 0.75 (1) | 2.2 (3) | 4 (5) | | kW (hp) | 0.55 (0.75) | 1.5 (2) | 3 (4) | Rated pulse frequency | kHz | 4 | 4 | 4 | Efficiency η | % | >96 | >96 | >96 | Power loss 3) at rated current | kW | 0.04 | 0.12 | 0.18 | Cooling air requirement | m3/s (ft3/s) | 0.005 (0.18) | 0.0092 (0.3) | 0.0185 (0.7) | Sound pressure level LpA (1 m) | dB | <56 | <62 | <65 | 24 V DC power supply for Control Unit | A | 1 | 1 | 1 | Input current 4) | | | | | | A | 9.6/5.5 | 24/13.9 | 43/24.8 | | A | 8.4/4.8 | 20.9/12.1 | 37.5/21.7 | Line supply connection U1/L1, V1/L2, W1/L3 | | Screw terminals, plug-in | Screw terminals, plug-in | Screw terminals, plug-in | | mm2 | 1.5 ... 2.5 | 1.5 ... 6 | 6 ... 16 | Motor connection U2, V2, W2 | | Screw terminals, plug-in | Screw terminals, plug-in | Screw terminals, plug-in | | mm2 | 1.5 ... 2.5 | 1.5 ... 6 | 6 ... 16 | Motor cable length, max. | | | | | | m (ft) | 150 (492) | 150 (492) | 150 (492) | | m (ft) | 150 (492) | 150 (492) | 150 (492) | Degree of protection | | IP20 | IP20 | IP20 | Dimensions | | | | | | mm (in) | 126 (4.96) | 154 (6.06) | 200 (7.87) | | mm (in) | 238 (9.37) | 345 (13.58) | 411 (16.18) | - Depth without operator panel
| mm (in) | 171 (6.73) | 171 (6.73) | 171 (6.73) | Frame size | | FSA | FSB | FSC | Weight, approx. With integrated line filter | | | | | - Without integrated line filter
| kg (lb) | 1.8 (3.97) | 3.4 (7.50) | 5.8 (12.8) | - With integrated line filter
| kg (lb) | 2 (4.41) | 3.7 (8.16) | 6.3 (13.9) |
1) The rated output current Irated is based on the duty cycle for low overload (LO). 2) The base-load current IH is based on the duty cycle for high overload (HO). 3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311 4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1 %. The rated input currents apply for a load with the type rating (based on Irated) – these current values are specified on the rating plate. Line voltage 380 ... 480 V 3 AC | PM240‑2 Power Modules push-through variant |
---|
Without integrated line filter | 6SL3211-1PE18-0UL1 | 6SL3211-1PE21-8UL0 | 6SL3211-1PE23-3UL0 |
---|
With integrated line filter class A | 6SL3211-1PE18-0AL1 | 6SL3211-1PE21-8AL0 | 6SL3211-1PE23-3AL0 |
---|
Output current at 50 Hz 400 V 3 AC | | | | | | A | 7.7 | 18 | 32 | | A | 8.5 | 19.8 | 37.1 | | A | 5.9 | 13.2 | 26 | | A | 11.8 | 27 | 52 | Type rating | | | | | | kW (hp) | 3 (4) | 7.5 (10) | 15 (20) | | kW (hp) | 2.2 (7.5) | 5.5 (7.5) | 11 (15) | Rated pulse frequency | kHz | 4 | 4 | 4 | Efficiency η | % | >96 | >97 | >97 | Power loss 3) at rated current | kW | 0.113 | 0.239 | 0.385 | Cooling air requirement | m3/s (ft3/s) | 0.007 (0.2) | 0.0092 (0.3) | 0.0185 (0.7) | Sound pressure level LpA (1 m) | dB | <56 | <62 | <65 | 24 V DC power supply for Control Unit | A | 1 | 1 | 1 | Input current 4) | | | | | | A | 10.1 | 22.2 | 39.9 | | A | 8.8 | 19.8 | 36 | Line supply connection U1/L1, V1/L2, W1/L3 | | Screw terminals, plug-in | Screw terminals, plug-in | Screw terminals, plug-in | | mm2 | 1.5 ... 2.5 | 1.5 ... 6 | 6 ... 16 | Motor connection U2, V2, W2 | | Screw terminals, plug-in | Screw terminals, plug-in | Screw terminals, plug-in | | mm2 | 1.5 ... 2.5 | 1.5 ... 6 | 6 ... 16 | Motor cable length, max. | | | | | - Without filter, shielded/unshielded
| m (ft) | 150/150 (492/492) | 150/150 (492/492) | 150/150 (492/492) | - With integrated filter class A, shielded/unshielded
| m (ft) | 50/100 (164/328) | 100/100 (328/328) 5) | 150/150 (492/492) 5) | Degree of protection | | IP20 | IP20 | IP20 | Dimensions | | | | | | mm (in) | 126 (4.96) | 154 (6.06) | 200 (7.87) | | mm (in) | 238 (9.37) | 345 (13.58) | 411 (16.18) | - Depth without operator panel
| mm (in) | 171 (6.73) | 171 (6.73) | 171 (6.73) | Frame size | | FSA | FSB | FSC | Weight, approx. With integrated line filter | | | | | - Without integrated line filter
| kg (lb) | 1.7 (3.75) | 3.6 (7.94) | 5.8 (12.8) | - With integrated line filter
| kg (lb) | 1.8 (3.97) | 3.9 (8.60) | 6.3 (13.9) |
1) The rated output current Irated is based on the duty cycle for low overload (LO). 2) The base-load current IH is based on the duty cycle for high overload (HO). 3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311 4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1 %. The rated input currents apply for a load with the type rating (based on Irated) – these current values are specified on the rating plate. 5) The values are applicable for low capacitance cables, e.g. MOTION‑CONNECT. For standard CY cables the max. permissible motor cable length is 50 m (164 ft) (shielded).
|
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Àðìàòóðà DENDOR
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Äàò÷èêè è èçìåðèòåëè
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ðåãóëÿòîðû è ðåãèñòðàòîðû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ïíåâìàòè÷åñêîå îáîðóäîâàíèå
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Êðàíû è Êëàïàíû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Èçìåðèòåëüíûå ïðèáîðû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ñèñòåìû áåñïðîâîäíîãî óïðàâëåíèÿ «óìíûé äîì»
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Áåñêîíòàêòíûå âûêëþ÷àòåëè Êîíå÷íûå âûêëþ÷àòåëè Îïòè÷åñêèå äàò÷èêè Ýíêîäåðû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FS - Óñòàíîâêà óìÿã÷åíèÿ
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FK - Óñòàíîâêà îáåçæåëåçèâàíèÿ
|