Unless explicitly specified otherwise, the following technical specifications are valid for all PM240?2 Power Modules in the blocksize format, FSA to FSF.
Note:
When engineering the complete SINAMICS S120 drive, the system data of the associated Control Units, supplementary system components, DC link components and Sensor Modules must be taken into consideration.
Electrical specifications
Line voltage
Blocksize format FSA ... FSC
200 to 240 V 1 AC ±10% 200 to 240 V 3 AC ±10% 380 to 480 V 3 AC ±10%
Blocksize format FSD to FSF
200 … 240 V 3 AC ±10 % (in operation -20 % <1 min) 380 ... 480 V 3 AC ±10 % (in operation -20 % <1 min) 500 … 690 V 3 AC ±10 % (in operation -20 % <1 min)
Line system configurations
Grounded TN/TT systems and non-grounded IT systems
Line frequency
47 ... 63 Hz
Line power factor
for a 3 AC line supply voltage and output power
Blocksize format FSA ... FSC
Fundamental power factor (cos ?1)
>0.96
Total (?)
> 0.7 - 0.85
Blocksize format FSD to FSF
Fundamental power factor (cos ?1)
> 0.98 - 0.99
Total (?)
> 0.9 - 0.92
Electromagnetic compatibility1)
Interference immunity
All PM240-2 Power Modules are suitable for use in both the first and second environments.
Interference emission acc. to EN 61800?3 Second environment
For devices with integrated radio suppression interference filter
Category C2
For devices with integrated radio suppression interference filter, format FSF with a line supply voltage of 690 V
Category C3
For devices without integrated radio interference suppression filter with optional external radio interference filter for grounded line supplies
Category C2 (recommended for operation in conjunction with a residual current protective device RCD)
For devices without integrated radio interference suppression filter for operation on IT line supplies
Category C4
Interference emission acc. to EN 61800?3 First environment
Can be used in the first environment when taking into consideration the additional secondary conditions listed in Section, EMC notes
Overvoltage category
acc. to IEC/EN 61800?5?1
III
Electronics power supply
implemented as PELV circuit according to IEC/EN 61800?5?1
24 V DC, -15 % +20 % Ground = negative pole grounded via the electronics
Short-circuit current rating (SCCR)
(Short Circuit Current Rating) Applies to industrial control cabinet installations according to NEC Article 409 or UL 508A
100 kA See the recommended line-side components – the value depends on the fuses and circuit breakers used
Rated pulse frequency
For devices with a rated voltage of 200 V 1/3 AC, 400 V 3 AC and a type rating ? 90 kW based on Irated
4 kHz
For devices with a rated voltage of 690 V 3 AC and a type rating ? 110 kW based on Irated
2 kHz
Output voltage, max.
Approximately 0.95 ? line voltage (at 200 V 1 AC, approximately 0.74 ? line voltage)
Output frequency
0 ... 550 Hz (dependencies on the control mode and pulse frequency must be taken into account)
Mechanical specifications
Type of cooling
Internal air cooling, power units with forced air cooling using integrated fans External air cooling (push-through cooling) for push-through device versions
Degree of protection
acc. to EN 60529
IP20
Protection class
Line circuits with protective conductor connection according to IEC/EN 61800?5?1
I
Electronic circuits
Safety extra low-voltage PELV/SELV
Touch protection
according to EN 50274/DGUV regulation 3 when used as intended
Internal air cooling
Forced air cooling AF to EN 60146
External air cooling
Push-through cooling for push-through device versions
Ambient conditions
Storage
Transport
Operation
In the product packaging
In transport packaging
Ambient temperature
Class 1K4 acc. to EN 60721?3?1 -25 ... +55 °C (-13 ... +131 °F)
Class 2K4 acc. to EN 60721?3?2 -40 ... +70 °C (-40 ... +158 °F)
Class 3K3 2) acc. to EN 60721?3?3 For operation without derating3): -10 ... +40 °C (14 ... 104 °F) (for operation with low overload) -10 ... +50 °C (14 ... 122 °F) (for operation with high overload) For operation with derating: >40 ... +60 °C (104 ... 140 °F)
Relative humidity
(oil mist, salt mist, ice, condensation, dripping water, spraying water and water jets are not permitted)
Class 1K4 acc. to EN 60721?3?1 5 ... 95 %
Class 2K3 acc. to EN 60721?3?2 5 ... 95 % at 40 °C
Class 3K3 2) acc. to EN 60721?3?3 5 ... 95 %
Environmental class/harmful chemical substances
Class 1C2 acc. to EN 60721?3?1
Class 2C2 acc. to EN 60721?3?2
Class 3C2 acc. to EN 60721?3?3
Organic/biological influences
Class 1B1 acc. to EN 60721?3?1
Class 2B1 acc. to EN 60721?3?2
Class 3B1 acc. to EN 60721?3?3
Degree of pollution
acc. to IEC/EN 61800?5?1 (condensation not permissible)
2
Installation altitude
For operation with low overload
Up to 1000m (3281 ft) above sea level without derating
For operation with high overload
Up to 2000 m (6562 ft) above sea level without derating
From 2000 m up to 4000 m (6562 ft to 13124 ft) above sea level observe the derating characteristics
See characteristic for current derating as a function of the installation altitude and/or reduction of the ambient temperature by 3.5 K per 500 m (1640 ft)
Mechanical strength
Storage
Transport
Operation
In the product packaging
In transport packaging
Vibratory load
Class 1M2 acc. to EN 60721?3?1
Class 2M3 acc. to EN 60721?3?2
Class 3M1 acc. to EN 60721?3?3 Test values acc. to EN 60068?2?6
Shock load
Class 1M2 acc. to EN 60721?3?1
Class 2M3 acc. to EN 60721?3?2
Class 3M1 acc. to EN 60721?3?3 Test values acc. to EN 60068?2?27
Certificates
Declarations of conformity
CE (Low Voltage, EMC and M?achinery Directives)
Certificates of suitability
Blocksize format FSA ... FSC
cULus according to UL 61800?5?1; CSA only with external surge voltage protection device; RCM; SEMI F47
Blocksize format FSD to FSF
cULus acc. to UL 61800?5?1; CSA only with external surge voltage protection device; RCM; SEMI F47 KCC only with internal or external line filters, Category C2; RoHS; EAC WEEE (Waste Electrical & Electronic Equipment)
1) Observe the EMC notes in Section, Tools and configuring.
2) Better than 3K3 through increased ruggedness regarding the temperature range and humidity.
3) Also carefully observe the permissible temperatures for the Control Unit and where relevant, the operator panel (IOP or BOP?2)
PM240?2 Power Modules standard variant
Line voltage 200 ... 240 V 1 AC/3 AC
PM240?2 Power Modules standard variant
Without integrated line filter
6SL3210-1PB13-0UL0
6SL3210-1PB13-8UL0
6SL3210-1PB15-5UL0
6SL3210-1PB17-4UL0
6SL3210-1PB21-0UL0
With integrated line filter class A
6SL3210-1PB13-0AL0
6SL3210-1PB13-8AL0
6SL3210-1PB15-5AL0
6SL3210-1PB17-4AL0
6SL3210-1PB21-0AL0
Output current
at 50 Hz 230 V 1 AC
Rated current Irated 1)
A
3
3.9
5.5
7.4
10.4
For S6 duty (40 %) IS6
A
3.3
4.3
6.1
8.2
11.5
Base-load current IH2)
A
2.3
3
3.9
5.5
7.4
Maximum current Imax
A
4.6
6
8.3
11.1
15.6
Type rating
Based on Irated
kW (hp)
0.55 (0.75)
0.75 (1)
1.1 (1.5)
1.5 (2)
2.2 (3)
Based on IH
kW (hp)
0.37 (0.5)
0.55 (0.75)
0.75 (1)
1.1 (1.5)
1.5 (2)
Rated pulse frequency
kHz
4
4
4
4
4
Efficiency ?
%
>96
>96
>96
>96
>96
Power loss 3)
at rated current
kW
0.04
0.04
0.05
0.07
0.12
Cooling air requirement
m3/s (ft3/s)
0.005 (0.18)
0.005 (0.18)
0.0092 (0.325)
0.0092 (0.325)
0.0092 (0.325)
Sound pressure level
LpA (1 m)
dB
<50
<50
<62
<62
<62
24 V DC power supply
for Control Unit
A
1
1
1
1
1
Input current 4)
Rated current 1 AC/3 AC
A
7.5/4.3
9.6/5.5
13.5/7.8
18.1/10.5
24/13.9
Based on IH 1 AC/3 AC
A
6.6/3.8
8.4/4.8
11.8/6.8
15.8/9.1
20.9/12.1
Line supply connection
U1/L1, V1/L2, W1/L3
Terminal connector
Terminal connector
Terminal connector
Terminal connector
Terminal connector
Conductor cross-section
mm2
1.5 ... 2.5
1.5 ... 2.5
1.5 ... 6
1.5 ... 6
1.5 ... 6
Motor connection
U2, V2, W2
Terminal connector
Terminal connector
Terminal connector
Terminal connector
Terminal connector
Conductor cross-section
mm2
1.5 ... 2.5
1.5 ... 2.5
1.5 ... 6
1.5 ... 6
1.5 ... 6
PE connection
Included in terminal connector
Included in terminal connector
Included in terminal connector
Included in terminal connector
Included in terminal connector
Motor cable length, max.
Shielded
m (ft)
50 (164)
50 (164)
50 (164)
50 (164)
50 (164)
Unshielded
m (ft)
100 (328)
100 (328)
100 (328)
100 (328)
100 (328)
Degree of protection
IP20
IP20
IP20
IP20
IP20
Dimensions
Width
mm (in)
73 (2.87)
73 (2.87)
100 (3.94)
100 (3.94)
100 (3.94)
Height
mm (in)
196 (7.72)
196 (7.72)
291 (11.46)
291 (11.46)
291 (11.46)
Depth without operator panel
mm (in)
165 (6.50)
165 (6.50)
165 (6.50)
165 (6.50)
165 (6.50)
Frame size
FSA
FSA
FSB
FSB
FSB
Weight, approx.
Without integrated line filter
kg (lb)
1.4 (3.09)
1.4 (3.09)
2.9 (6.39)
2.9 (6.39)
2.9 (6.39)
With integrated line filter
kg (lb)
1.6 (3.53)
1.6 (3.53)
3.1 (6.84)
3.1 (6.84)
3.1 (6.84)
1) The rated output current Irated is based on the duty cycle for low overload (LO).
2) The base-load current IH is based on the duty cycle for high overload (HO).
4) The input current depends on the motor load and line impedance. The input currents apply for a load with the type rating (based on Irated) for a line impedance corresponding to uk = 1%. The current values are specified on the rating plate of the Power Module.
Line voltage 200 ... 240 V 1 AC/3 AC
PM240?2 Power Modules standard variant
Without integrated line filter
6SL3210-1PB21-4UL0
6SL3210-1PB21-8UL0
With integrated line filter class A
6SL3210-1PB21-4AL0
6SL3210-1PB21-8AL0
Output current
at 50 Hz 230 V 1 AC
Rated current Irated 1)
A
13.6
17.5
For S6 duty (40 %) IS6
A
15
19.3
Base-load current IH2)
A
10.4
13.6
Maximum current Imax
A
20.8
27.2
Type rating
Based on Irated
kW (hp)
3 (4)
4 (5)
Based on IH
kW (hp)
2.2 (3)
3 (4)
Rated pulse frequency
kHz
4
4
Efficiency ?
%
>96
>96
Power loss 3)
at rated current
kW
0.14
0.18
Cooling air requirement
m3/s (ft3/s)
0.0185 (0.65)
0.0185 (0.65)
Sound pressure level
LpA (1 m)
dB
<65
<65
24 V DC power supply
for Control Unit
A
1
1
Input current 4)
Rated current 1 AC/3 AC
A
35.9/20.7
43/24.8
Based on IH 1 AC/3 AC
A
31.3/18.1
37.5/21.7
Line supply connection
U1/L1, V1/L2, W1/L3
Terminal connector
Terminal connector
Conductor cross-section
mm2
6 ... 16
6 ... 16
Motor connection
U2, V2, W2
Terminal connector
Terminal connector
Conductor cross-section
mm2
6 ... 16
6 ... 16
PE connection
Included in terminal connector
Included in terminal connector
Motor cable length, max.
Shielded
m (ft)
50 (164)
50 (164)
Unshielded
m (ft)
100 (328)
100 (328)
Degree of protection
IP20
IP20
Dimensions
Width
mm (in)
140 (5.51)
140 (5.51)
Height
mm (in)
355 (13.98)
355 (13.98)
Depth without operator panel
mm (in)
165 (6.50)
165 (6.50)
Frame size
FSC
FSC
Weight, approx.
Without integrated line filter
kg (lb)
5 (11)
5 (11)
With integrated line filter
kg (lb)
5.2 (11.5)
5.2 (11.5)
1) The rated output current Irated is based on the duty cycle for low overload (LO).
2) The base-load current IH is based on the duty cycle for high overload (HO).
4) The input current depends on the motor load and line impedance. The input currents apply for a load with the type rating (based on Irated) for a line impedance corresponding to uk = 1%. The current values are specified on the rating plate of the Power Module.
Line voltage 200 ... 240 V 3 AC
PM240?2 Power Modules standard variant
Without integrated line filter
6SL3210-1PC22-2UL0
6SL3210-1PC22-8UL0
6SL3210-1PC24-2UL0
6SL3210-1PC25-4UL0
6SL3210-1PC26-8UL0
With integrated line filter class A
6SL3210-1PC22-2AL0
6SL3210-1PC22-8AL0
–
–
–
Output current
at 50 Hz 230 V 3 AC
Rated current Irated 1)
A
22
28
42
54
68
For S6 duty (40 %) IS6
A
24.2
30.8
50
64
81
Base-load current IH2)
A
17.5
22
35
42
54
Maximum current Imax
A
35
44
70
84
108
Type rating
Based on Irated
kW (hp)
5.5 (7.5)
7.5 (10)
11 (15)
15 (20)
18.5 (25)
Based on IH
kW (hp)
4 (5)
5.5 (7.5)
7.5 (10)
11 (15)
15 (20)
Rated pulse frequency
kHz
4
4
4
4
4
Efficiency ?
%
>97
>97
>97
>97
>97
Power loss 3)
at rated current
kW
0.2
0.26
0.42
0.57
0.76
Cooling air requirement
m3/s (ft3/s)
0.0185 (0.65)
0.0185 (0.65)
0.055 (1.9)
0.055 (1.9)
0.055 (1.9)
Sound pressure level
LpA (1 m)
dB
<65
<65
45 ... 65 4)
45 ... 65 4)
45 ... 65 4)
24 V DC power supply
for Control Unit
A
1
1
1
1
1
Input current 5)
Rated current
A
28.6
36.4
44
56
70
Based on IH
A
26.2
33
36
43
56
Line supply connection
U1/L1, V1/L2, W1/L3
Terminal connector
Terminal connector
Screw terminals
Screw terminals
Screw terminals
Conductor cross-section
mm2
6 ... 16
6 ... 16
10 ... 35
10 ... 35
10 ... 35
Motor connection
U2, V2, W2
Terminal connector
Terminal connector
Screw terminals
Screw terminals
Screw terminals
Conductor cross-section
mm2
6 ... 16
6 ... 16
10 ... 35
10 ... 35
10 ... 35
PE connection
Included in terminal connector
Included in terminal connector
Screw terminals
Screw terminals
Screw terminals
Motor cable length, max.
Shielded
m (ft)
50 (164)
50 (164)
200 (656)
200 (656)
200 (656)
Unshielded
m (ft)
100 (328)
100 (328)
300 (984)
300 (984)
300 (984)
Degree of protection
IP20
IP20
IP20
IP20
IP20
Dimensions
Width
mm (in)
140 (5.51)
140 (5.51)
200 (7.87)
200 (7.87)
200 (7.87)
Height
mm (in)
355 (13.98)
355 (13.98)
472 (18.58)
472 (18.58)
472 (18.58)
Depth without operator panel
mm (in)
165 (6.50)
165 (6.50)
237 (9.33)
237 (9.33)
237 (9.33)
Frame size
FSC
FSC
FSD
FSD
FSD
Weight, approx.
Without integrated line filter
kg (lb)
5 (11)
5 (11)
17 (37.5)
17 (37.5)
17 (37.5)
With integrated line filter
kg (lb)
5.2 (11.5)
5.2 (11.5)
–
–
–
1) The rated output current Irated is based on the duty cycle for low overload (LO).
2) The base-load current IH is based on the duty cycle for high overload (HO).
4) Values dependent on ambient temperature and utilization.
5) The input current depends on the motor load and line impedance. The input currents apply for a load with the type rating (based on Irated) for a line impedance corresponding to uk = 1%. The current values are specified on the rating plate of the Power Module.
Line voltage 200 ... 240 V 3 AC
PM240?2 Power Modules standard variant
Without integrated line filter
6SL3210-1PC28-0UL0
6SL3210-1PC31-1UL0
6SL3210-1PC31-3UL0
6SL3210-1PC31-6UL0
6SL3210-1PC31-8UL0
With integrated line filter class A
–
–
–
–
–
Output current
at 50 Hz 230 V 3 AC
Rated current Irated 1)
A
80
104
130
154
178
For S6 duty (40 %) IS6
A
96
124
156
184
213
Base-load current IH2)
A
68
80
104
130
154
Maximum current Imax
A
136
160
208
260
308
Type rating
Based on Irated
kW (hp)
22 (30)
30 (40)
37 (50)
45 (60)
55 (75)
Based on IH
kW (hp)
18.5 (25)
22 (30)
30 (40)
37 (50)
45 (60)
Rated pulse frequency
kHz
4
4
4
4
4
Efficiency ?
%
>97
>97
>97
>97
>97
Power loss 3)
at rated current
kW
0.85
1.2
1.44 (3.53)
1.79
2.18 (3.53)
Cooling air requirement
m3/s (ft3/s)
0.083 (2.9)
0.083 (2.9)
0.153 (5.4)
0.153 (5.4)
0.153 (5.4)
Sound pressure level
LpA (1 m)
dB
44 ... 62 4)
44 ... 62 4)
56 ... 68 4)
56 ... 68 4)
56 ... 68 4)
24 V DC power supply
for Control Unit
A
1
1
1
1
1
Input current 5)
Rated current
A
83
107
134
158
183
Based on IH
A
71
83
110
138
164
Line supply connection
U1/L1, V1/L2, W1/L3
Screw terminals
Screw terminals
M10 screw stud
M10 screw stud
M10 screw stud
Conductor cross-section
mm2
25 ... 70
25 ... 70
35 ... 2 ? 120
35 ... 2 ? 120
35 ... 2 ? 120
Motor connection
U2, V2, W2
Screw terminals
Screw terminals
M10 screw stud
M10 screw stud
M10 screw stud
Conductor cross-section
mm2
25 ... 70
25 ... 70
35 ... 2 ? 120
35 ... 2 ? 120
35 ... 2 ? 120
PE connection
Screw terminals
Screw terminals
M10 screw stud
M10 screw stud
M10 screw stud
Motor cable length, max.
Shielded
m (ft)
200 (656)
200 (656)
300 (984)
300 (984)
300 (984)
Unshielded
m (ft)
300 (984)
300 (984)
450 (1476)
450 (1476)
450 (1476)
Degree of protection
IP20
IP20
IP20
IP20
IP20
Dimensions
Width
mm (in)
275 (10.83)
275 (10.83)
305 (12.01)
305 (12.01)
305 (12.01)
Height
mm (in)
551 (21.69)
551 (21.69)
708 (27.87)
708 (27.87)
708 (27.87)
Depth without operator panel
mm (in)
237 (9.33)
237 (9.33)
357 (14.06)
357 (14.06)
357 (14.06)
Frame size
FSE
FSE
FSF
FSF
FSF
Weight, approx.
Without integrated line filter
kg (lb)
26 (57.3)
26 (57.3)
57 (126)
57 (126)
57 (126)
With integrated line filter
kg (lb)
–
–
–
–
–
1) The rated output current Irated is based on the duty cycle for low overload (LO).
2) The base-load current IH is based on the duty cycle for high overload (HO).
4) Values dependent on ambient temperature and utilization.
5) The input current depends on the motor load and line impedance. The input currents apply for a load with the type rating (based on Irated) for a line impedance corresponding to uk = 1%. The current values are specified on the rating plate of the Power Module.
Line voltage 380 ... 480 V 3 AC
PM240?2 Power Modules standard variant
Without integrated line filter
6SL3210-1PE11-8UL1
6SL3210-1PE12-3UL1
6SL3210-1PE13-2UL1
6SL3210-1PE14-3UL1
6SL3210-1PE16-1UL1
6SL3210-1PE18-0UL1
With integrated line filter class A
6SL3210-1PE11-8AL1
6SL3210-1PE12-3AL1
6SL3210-1PE13-2AL1
6SL3210-1PE14-3AL1
6SL3210-1PE16-1AL1
6SL3210-1PE18-0AL1
Output current
at 50 Hz 400 V 3 AC
Rated current Irated1)
A
1.7
2.2
3.1
4.1
5.9
7.7
For S6 duty (40 %) IS6
A
2
2.5
3.5
4.5
6.5
8.5
Base-load current IH2)
A
1.3
1.7
2.2
3.1
4.1
5.9
Maximum current Imax
A
2.6
3.4
4.7
6.2
8.9
11.8
Type rating
Based on Irated
kW (hp)
0.55 (0.75)
0.75 (1)
1.1 (1.5)
1.5 (2)
2.2 (3)
3 (4)
Based on IH
kW (hp)
0.37 (0.5)
0.55 (0.75)
0.75 (1)
1.1 (1.5)
1.5 (2)
2.2 (3)
Rated pulse frequency
kHz
4
4
4
4
4
4
Efficiency ?
%
>96
>96
>96
>96
>96
>96
Power loss 3)
at rated current
kW
0.04
0.04
0.04
0.07
0.1
0.12
Cooling air requirement
m3/s (ft3/s)
0.005 (0.18)
0.005 (0.18)
0.005 (0.18)
0.005 (0.18)
0.005 (0.18)
0.005 (0.18)
Sound pressure level
LpA (1 m)
dB
<50
<50
<50
<50
< 56.3
< 56.3
24 V DC power supply
for Control Unit
A
1
1
1
1
1
1
Input current 4)
Rated current
A
2.3
2.9
4.1
5.5
7.7
10.1
Based on IH
A
2
2.6
3.3
4.7
6.1
8.8
Line supply connection
U1/L1, V1/L2, W1/L3
Terminal connector
Terminal connector
Terminal connector
Terminal connector
Terminal connector
Terminal connector
Conductor cross-section
mm2
1 ... 2.5
1 ... 2.5
1 ... 2.5
1 ... 2.5
1 ... 2.5
1 ... 2.5
Motor connection
U2, V2, W2
Terminal connector
Terminal connector
Terminal connector
Terminal connector
Terminal connector
Terminal connector
Conductor cross-section
mm2
1 ... 2.5
1 ... 2.5
1 ... 2.5
1 ... 2.5
1 ... 2.5
1 ... 2.5
PE connection
Included in terminal connector
Included in terminal connector
Included in terminal connector
Included in terminal connector
Included in terminal connector
Included in terminal connector
Motor cable length, max.
Without filter, shielded/unshielded
m (ft)
150/150 (492/492)
150/150 (492/492)
150/150 (492/492)
150/150 (492/492)
150/150 (492/492)
150/150 (492/492)
With integrated filter class A, shielded/unshielded
m (ft)
50/100 (164/328)
50/100 (164/328)
50/100 (164/328)
50/100 (164/328)
50/100 (164/328)
50/100 (164/328)
Degree of protection
IP20
IP20
IP20
IP20
IP20
IP20
Dimensions
Width
mm (in)
73 (2.87)
73 (2.87)
73 (2.87)
73 (2.87)
73 (2.87)
73 (2.87)
Height
mm (in)
196 (7.72)
196 (7.72)
196 (7.72)
196 (7.72)
196 (7.72)
196 (7.72)
Depth without operator panel
mm (in)
165 (6.50)
165 (6.50)
165 (6.50)
165 (6.50)
165 (6.50)
165 (6.50)
Frame size
FSA
FSA
FSA
FSA
FSA
FSA
Weight, approx.
Without integrated line filter
kg (lb)
1.4 (3.09)
1.4 (3.09)
1.4 (3.09)
1.4 (3.09)
1.4 (3.09)
1.4 (3.09)
With integrated line filter
kg (lb)
1.5 (3.31)
1.5 (3.31)
1.5 (3.31)
1.5 (3.31)
1.5 (3.31)
1.5 (3.31)
1) The rated output current Irated is based on the duty cycle for low overload (LO).
2) The base-load current IH is based on the duty cycle for high overload (HO).
4) The input current depends on the motor load and line impedance. The input currents apply for a load with the type rating (based on Irated) for a line impedance corresponding to uk = 1%. The current values are specified on the rating plate of the Power Module.
Line voltage 380 ... 480 V 3 AC
PM240?2 Power Modules standard variant
Without integrated line filter
6SL3210-1PE21-1UL0
6SL3210-1PE21-4UL0
6SL3210-1PE21-8UL0
6SL3210-1PE22-7UL0
6SL3210-1PE23-3UL0
With integrated line filter class A
6SL3210-1PE21-1AL0
6SL3210-1PE21-4AL0
6SL3210-1PE21-8AL0
6SL3210-1PE22-7AL0
6SL3210-1PE23-3AL0
Output current
at 50 Hz 400 V 3 AC
Rated current Irated1)
A
10.2
13.2
18
26
32
For S6 duty (40 %) IS6
A
11.2
14.5
19.8
28.6
37.1
Base-load current IH2)
A
7.7
10.2
13.2
18
26
Maximum current Imax
A
15.4
20.4
27
39
52
Type rating
Based on Irated
kW (hp)
4 (5)
5.5 (7.5)
7.5 (10)
11 (15)
15 (20)
Based on IH
kW (hp)
3 (4)
4 (5)
5.5 (7.5)
7.5 (10)
11 (15)
Rated pulse frequency
kHz
4
4
4
4
4
Efficiency ?
%
>97
>97
>97
>97
>97
Power loss 3)
at rated current
kW
0.11
0.15
0.2
0.3
0.37
Cooling air requirement
m3/s (ft3/s)
0.0092 (0.32)
0.0092 (0.32)
0.0092 (0.32)
0.0185 (0.65)
0.0185 (0.65)
Sound pressure level
LpA (1 m)
dB
<62
<62
<62
<65
<65
24 V DC power supply
for Control Unit
A
1
1
1
1
1
Input current 4)
Rated current
A
13.3
17.2
22.2
32.6
39.9
Based on IH
A
11.6
15.3
19.8
27
36
Line supply connection
U1/L1, V1/L2, W1/L3
Terminal connector
Terminal connector
Terminal connector
Terminal connector
Terminal connector
Conductor cross-section
mm2
1.5 ... 6
1.5 ... 6
1.5 ... 6
6 ... 16
6 ... 16
Motor connection
U2, V2, W2
Terminal connector
Terminal connector
Terminal connector
Terminal connector
Terminal connector
Conductor cross-section
mm2
1.5 ... 6
1.5 ... 6
1.5 ... 6
6 ... 16
6 ... 16
PE connection
Included in terminal connector
Included in terminal connector
Included in terminal connector
Included in terminal connector
Included in terminal connector
Motor cable length, max.
Without filter, shielded/unshielded
m (ft)
150/150 (492/492)
150/150 (492/492)
150/150 (492/492)
150/150 (492/492)
150/150 (492/492)
With integrated filter class A, shielded/unshielded
m (ft)
100/100 (328/328) 5)
100/100 (328/328) 5)
100/100 (328/328) 5)
150/150 (492/492) 5)
150/150 (492/492) 5)
Degree of protection
IP20
IP20
IP20
IP20
IP20
Dimensions
Width
mm (in)
100 (3.94)
100 (3.94)
100 (3.94)
140 (5.51)
140 (5.51)
Height
mm (in)
291 (11.46)
291 (11.46)
291 (11.46)
355 (13.98)
355 (13.98)
Depth without operator panel
mm (in)
165 (6.50)
165 (6.50)
165 (6.50)
165 (6.50)
165 (6.50)
Frame size
FSB
FSB
FSB
FSC
FSC
Weight, approx.
Without integrated line filter
kg (lb)
2.9 (6.39)
2.9 (6.39)
3 (6.62)
4.7 (10.4)
4.8 (10.6)
With integrated line filter
kg (lb)
3.1 (6.84)
3.1 (6.84)
3.2 (7.06)
5.3 (11.7)
5.4 (11.9)
1) The rated output current Irated is based on the duty cycle for low overload (LO).
2) The base-load current IH is based on the duty cycle for high overload (HO).
4) The input current depends on the motor load and line impedance. The input currents apply for a load with the type rating (based on Irated) for a line impedance corresponding to uk = 1%. The current values are specified on the rating plate of the Power Module.
5) The values are applicable for low capacitance cables, e.g. MOTION?CONNECT. For standard CY cables the max. permissible motor cable length is 50 m (164 ft) (shielded).
Line voltage 380 ... 480 V 3 AC
PM240?2 Power Modules standard variant
Without integrated line filter
6SL3210-1PE23-8UL0
6SL3210-1PE24-5UL0
6SL3210-1PE26-0UL0
6SL3210-1PE27-5UL0
6SL3210-1PE28-8UL0
6SL3210-1PE31-1UL0
With integrated line filter class A
6SL3210-1PE23-8AL0
6SL3210-1PE24-5AL0
6SL3210-1PE26-0AL0
6SL3210-1PE27-5AL0
6SL3210-1PE28-8AL0
6SL3210-1PE31-1AL0
Output current
at 50 Hz 400 V 3 AC
Rated current Irated1)
A
38
45
60
75
90
110
For S6 duty (40 %) IS6
A
45
54
72
90
108
132
Base-load current IH2)
A
32
38
45
60
75
90
Maximum current Imax
A
64
76
90
120
150
180
Type rating
Based on Irated
kW (hp)
18.5 (25)
22 (30)
30 (40)
37 (50)
45 (60)
55 (75)
Based on IH
kW (hp)
15 (20)
18.5 (25)
22 (30)
30 (40)
37 (50)
45 (60)
Rated pulse frequency
kHz
4
4
4
4
4
4
Efficiency ?
%
>97
>97
>97
>97
>97
>97
Power loss 3)
at rated current
kW
0.55 (0.74)
0.68
0.77
1.02
1.2
1.55
Cooling air requirement
m3/s (ft3/s)
0.055 (1.9)
0.055 (1.9)
0.055 (1.9)
0.055 (1.9)
0.083 (2.9)
0.083 (2.9)
Sound pressure level
LpA (1 m)
dB
45 ... 65 4)
45 ... 65 4)
45 ... 65 4)
45 ... 65 4)
44 ... 62 4)
44 ... 62 4)
24 V DC power supply
for Control Unit
A
1
1
1
1
1
1
Input current 5)
Rated current
A
39
47
62 (
77
93
113
Based on IH
A
33
38
47
62
78
94
Line supply connection
U1/L1, V1/L2, W1/L3
Screw terminals
Screw terminals
Screw terminals
Screw terminals
Screw terminals
Screw terminals
Conductor cross-section
mm2
10 ... 35
10 ... 35
10 ... 35
10 ... 35
25 ... 70
25 ... 70
Motor connection
U2, V2, W2
Screw terminals
Screw terminals
Screw terminals
Screw terminals
Screw terminals
Screw terminals
Conductor cross-section
mm2
10 ... 35
10 ... 35
10 ... 35
10 ... 35
25 ... 70
25 ... 70
PE connection
Screw terminals
Screw terminals
Screw terminals
Screw terminals
Screw terminals
Screw terminals
Motor cable length, max.
Shielded
m (ft)
200 (656)
200 (656)
200 (656)
200 (656)
200 (656)
200 (656)
Unshielded
m (ft)
300 (984)
300 (984)
300 (984)
300 (984)
300 (984)
300 (984)
Degree of protection
IP20
IP20
IP20
IP20
IP20
IP20
Dimensions
Width
mm (in)
200 (7.87)
200 (7.87)
200 (7.87)
200 (7.87)
275 (10.83)
275 (10.83)
Height
mm (in)
472 (18.58)
472 (18.58)
472 (18.58)
472 (18.58)
551 (21.69)
551 (21.69)
Depth without operator panel
mm (in)
237 (9.33)
237 (9.33)
237 (9.33)
237 (9.33)
237 (9.33)
237 (9.33)
Frame size
FSD
FSD
FSD
FSD
FSE
FSE
Weight, approx.
Without integrated line filter
kg (lb)
16 (35.3)
16 (35.3)
17 (37.5)
17 (37.5)
26 (57.3)
26 (57.3)
With integrated line filter
kg (lb)
17.5 (38.6)
17.5 (38.6)
18.5 (40.8)
18.5 (40.8)
28 (61.7)
28 (61.7)
1) The rated output current Irated is based on the duty cycle for low overload (LO).
2) The base-load current IH is based on the duty cycle for high overload (HO).
4) Values dependent on ambient temperature and utilization.
5) The input current depends on the motor load and line impedance. The input currents apply for a load with the type rating (based on Irated) for a line impedance corresponding to uk = 1%. The current values are specified on the rating plate of the Power Module.
Line voltage 380 ... 480 V 3 AC
PM240?2 Power Modules standard variant
Without integrated line filter
6SL3210-1PE31-5UL0
6SL3210-1PE31-8UL0
6SL3210-1PE32-1UL0
6SL3210-1PE32-5UL0
With integrated line filter class A
6SL3210-1PE31-5AL0
6SL3210-1PE31-8AL0
6SL3210-1PE32-1AL0
6SL3210-1PE32-5AL0
Output current
at 50 Hz 400 V 3 AC
Rated current Irated1)
A
145
178
205
250
For S6 duty (40 %) IS6
A
174
213
246
300
Base-load current IH2)
A
110
145
178
205
Maximum current Imax
A
220
290
356
410
Type rating
Based on Irated
kW (hp)
75 (100)
90 (125)
110 (150)
132 (200)
Based on IH
kW (hp)
55 (75)
75 (100)
90 (125)
110 (150)
Rated pulse frequency
kHz
4
4
2
2
Efficiency ?
%
>97
>97
>97
>97
Power loss 3)
at rated current
kW
1.79
2.33
2.17
2.84
Cooling air requirement
m3/s (ft3/s)
0.2 (7.1)
0.2 (7.1)
0.2 (7.1)
0.2 (7.1)
Sound pressure level
LpA (1 m)
dB
56 ... 68 4)
56 ... 68 4)
56 ... 68 4)
56 ... 68 4)
24 V DC power supply
for Control Unit
A
1
1
1
1
Input current 5)
Rated current
A
149
183
211
257
Based on IH
A
117
154
189
218
Line supply connection
U1/L1, V1/L2, W1/L3
M10 screw stud
M10 screw stud
M10 screw stud
M10 screw stud
Conductor cross-section
mm2
35 ... 2 ? 120
35 ... 2 ? 120
35 ... 2 ? 120
35 ... 2 ? 120
Motor connection
U2, V2, W2
M10 screw stud
M10 screw stud
M10 screw stud
M10 screw stud
Conductor cross-section
mm2
35 ... 2 ? 120
35 ... 2 ? 120
35 ... 2 ? 120
35 ... 2 ? 120
PE connection
M10 screw stud
M10 screw stud
M10 screw stud
M10 screw stud
Motor cable length, max.
Shielded
m (ft)
300 (984)
300 (984)
300 (984)
300 (984)
Unshielded
m (ft)
450 (1476)
450 (1476)
450 (1476)
450 (1476)
Degree of protection
IP20
IP20
IP20
IP20
Dimensions
Width
mm (in)
305 (12.01)
305 (12.01)
305 (12.01)
305 (12.01)
Height
mm (in)
708 (27.87)
708 (27.87)
708 (27.87)
708 (27.87)
Depth without operator panel
mm (in)
357 (14.06)
357 (14.06)
357 (14.06)
357 (14.06)
Frame size
FSF
FSF
FSF
FSF
Weight, approx.
Without integrated line filter
kg (lb)
57 (126)
57 (126)
61 (135)
61 (135)
With integrated line filter
kg (lb)
63 (139)
63 (139)
65 (143)
65 (143)
1) The rated output current Irated is based on the duty cycle for low overload (LO).
2) The base-load current IH is based on the duty cycle for high overload (HO).
4) Values dependent on ambient temperature and utilization.
5) The input current depends on the motor load and line impedance. The input currents apply for a load with the type rating (based on Irated) for a line impedance corresponding to uk = 1%. The current values are specified on the rating plate of the Power Module.
Line voltage 500 ... 690 V 3 AC
PM240?2 Power Modules standard variant
Without integrated line filter
6SL3210-1PH21-4UL0
6SL3210-1PH22-0UL0
6SL3210-1PH22-3UL0
6SL3210-1PH22-7UL0
6SL3210-1PH23-5UL0
6SL3210-1PH24-2UL0
With integrated line filter class A
6SL3210-1PH21-4AL0
6SL3210-1PH22-0AL0
6SL3210-1PH22-3AL0
6SL3210-1PH22-7AL0
6SL3210-1PH23-5AL0
6SL3210-1PH24-2AL0
Output current
at 50 Hz 690 V 3 AC
Rated current Irated 1)
A
14
19
23
27
35
42
For S6 duty (40 %) IS6
A
16
22
27
32
42
50
Base-load current IH2)
A
11
14
19
23
27
35
Maximum current Imax
A
22
29
38
46
54
70
Type rating
Based on Irated
kW (hp)
11 (10)
15 (15)
18.5 (20)
22 (25)
30 (30)
37 (40)
Based on IH
kW (hp)
7.5 (7.5)
11 (10)
15 (15)
18.5 (20)
22 (25)
30 (30)
Rated pulse frequency
kHz
2
2
2
2
2
2
Efficiency ?
%
>98
>98
>98
>98
>98
>98
Power loss 3)
at rated current
kW
0.32
0.41
0.48
0.56
0.73
0.88
Cooling air requirement
m3/s (ft3/s)
0.055 (1.9)
0.055 (1.9)
0.055 (1.9)
0.055 (1.9)
0.055 (1.9)
0.055 (1.9)
Sound pressure level
LpA (1 m)
dB
45 ... 65 4)
45 ... 65 4)
45 ... 65 4)
45 ... 65 4)
45 ... 65 4)
45 ... 65 4)
24 V DC power supply
for Control Unit
A
1
1
1
1
1
1
Input current 5)
Rated current
A
15
20
24
28
36
44
Based on IH
A
11
14
20
24
28
36
Line supply connection
U1/L1, V1/L2, W1/L3
Screw terminals
Screw terminals
Screw terminals
Screw terminals
Screw terminals
Screw terminals
Conductor cross-section
mm2
10 ... 35
10 ... 35
10 ... 35
10 ... 35
10 ... 35
10 ... 35
Motor connection
U2, V2, W2
Screw terminals
Screw terminals
Screw terminals
Screw terminals
Screw terminals
Screw terminals
Conductor cross-section
mm2
10 ... 35
10 ... 35
10 ... 35
10 ... 35
10 ... 35
10 ... 35
PE connection
Screw terminals
Screw terminals
Screw terminals
Screw terminals
Screw terminals
Screw terminals
Motor cable length, max.
Shielded
m (ft)
200 (656)
200 (656)
200 (656)
200 (656)
200 (656)
200 (656)
Unshielded
m (ft)
300 (984)
300 (984)
300 (984)
300 (984)
300 (984)
300 (984)
Degree of protection
IP20
IP20
IP20
IP20
IP20
IP20
Dimensions
Width
mm (in)
200 (7.87)
200 (7.87)
200 (7.87)
200 (7.87)
200 (7.87)
200 (7.87)
Height
mm (in)
472 (18.58)
472 (18.58)
472 (18.58)
472 (18.58)
472 (18.58)
472 (18.58)
Depth without operator panel
mm (in)
237 (9.33)
237 (9.33)
237 (9.33)
237 (9.33)
237 (9.33)
237 (9.33)
Frame size
FSD
FSD
FSD
FSD
FSD
FSD
Weight, approx.
Without integrated line filter
kg (lb)
17 (37.5)
17 (37.5)
17 (37.5)
17 (37.5)
17 (37.5)
17 (37.5)
With integrated line filter
kg (lb)
18.5 (40.8)
18.5 (40.8)
18.5 (40.8)
18.5 (40.8)
18.5 (40.8)
18.5 (40.8)
1) The rated output current Irated is based on the duty cycle for low overload (LO).
2) The base-load current IH is based on the duty cycle for high overload (HO).
4) Values dependent on ambient temperature and utilization.
5) The input current depends on the motor load and line impedance. The input currents apply for a load with the type rating (based on Irated) for a line impedance corresponding to uk = 1%. The current values are specified on the rating plate of the Power Module.
Line voltage 500 ... 690 V 3 AC
PM240?2 Power Modules standard variant
Without integrated line filter
6SL3210-1PH25-2UL0
6SL3210-1PH26-2UL0
6SL3210-1PH28-0UL0
6SL3210-1PH31-0UL0
6SL3210-1PH31-2UL0
6SL3210-1PH31-4UL0
With integrated line filter class A
6SL3210-1PH25-2AL0
6SL3210-1PH26-2AL0
6SL3210-1PH28-0AL0
6SL3210-1PH31-0AL0
6SL3210-1PH31-2AL0
6SL3210-1PH31-4AL0
Output current
at 50 Hz 690 V 3 AC
Rated current Irated 1)
A
52
62
80
100
115
142
For S6 duty (40 %) IS6
A
62
74
96
120
138
170
Base-load current IH2)
A
42
52
62
80
100
115
Maximum current Imax
A
84
104
124
160
200
230
Type rating
Based on Irated
kW (hp)
45 (50)
55 (60)
75 (75)
90 (100)
110 (100)
132 (125)
Based on IH
kW (hp)
37 (40)
45 (50)
55 (60)
75 (75)
90 (100)
110 (100)
Rated pulse frequency
kHz
2
2
2
2
2
2
Efficiency ?
%
>98
>98
>98
>98
>98
>98
Power loss 3)
at rated current
kW
1
1.21
1.23
1.57
1.83
2.35
Cooling air requirement
m3/s (ft3/s)
0.083 (2.9)
0.083 (2.9)
0.083 (2.9)
0.083 (2.9)
0.2 (7.1)
0.2 (7.1)
Sound pressure level
LpA (1 m)
dB
44 ... 62 4)
44 ... 62 4)
56 ... 68 4)
56 ... 68 4)
56 ... 68 4)
56 ... 68 4)
24 V DC power supply
for Control Unit
A
1
1
1
1
1
1
Input current 5)
Rated current
A
50
59
78
97
111
137
Based on IH
A
44
54
66
85
106
122
Line supply connection
U1/L1, V1/L2, W1/L3
Screw terminals
Screw terminals
M10 screw stud
M10 screw stud
M10 screw stud
M10 screw stud
Conductor cross-section
mm2
25 ... 70
25 ... 70
35 ... 2 ? 120
35 ... 2 ? 120
35 ... 2 ? 120
35 ... 2 ? 120
Motor connection
U2, V2, W2
Screw terminals
Screw terminals
M10 screw stud
M10 screw stud
M10 screw stud
M10 screw stud
Conductor cross-section
mm2
25 ... 70
25 ... 70
35 ... 2 ? 120
35 ... 2 ? 120
35 ... 2 ? 120
35 ... 2 ? 120
PE connection
Screw terminals
Screw terminals
M10 screw stud
M10 screw stud
M10 screw stud
M10 screw stud
Motor cable length, max.
Shielded
m (ft)
200 (656)
200 (656)
300 (984)
300 (984)
300 (984)
300 (984)
Unshielded
m (ft)
300 (984)
300 (984)
450 (1476)
450 (1476)
450 (1476)
450 (1476)
Degree of protection
IP20
IP20
IP20
IP20
IP20
IP20
Dimensions
Width
mm (in)
275 (10.83)
275 (10.83)
305 (12.01)
305 (12.01)
305 (12.01)
305 (12.01)
Height
mm (in)
551 (21.69)
551 (21.69)
708 (27.87)
708 (27.87)
708 (27.87)
708 (27.87)
Depth without operator panel
mm (in)
237 (9.33)
237 (9.33)
357 (14.06)
357 (14.06)
357 (14.06)
357 (14.06)
Frame size
FSE
FSE
FSF
FSF
FSF
FSF
Weight, approx.
Without integrated line filter
kg (lb)
26 (57.3)
26 (57.3)
60 (132.3)
60 (132.3)
60 (132.3)
60 (132.3)
With integrated line filter
kg (lb)
28 (61.7)
28 (61.7)
64 (141)
64 (141)
64 (141)
64 (141)
1) The rated output current Irated is based on the duty cycle for low overload (LO).
2) The base-load current IH is based on the duty cycle for high overload (HO).
4) Values dependent on ambient temperature and utilization.
5) The input current depends on the motor load and line impedance. The input currents apply for a load with the type rating (based on Irated) for a line impedance corresponding to uk = 1%. The current values are specified on the rating plate of the Power Module.
PM240?2 Power Modules push-through variant
Line voltage 200 ... 240 V 1 AC/3 AC
PM240?2 Power Modules push-through variant
Without integrated line filter
6SL3211-1PB13-8UL0
6SL3211-1PB21-0UL0
6SL3211-1PB21-8UL0
With integrated line filter class A
6SL3211-1PB13-8AL0
6SL3211-1PB21-0AL0
6SL3211-1PB21-8AL0
Output current
At 50 Hz 230 V 1 AC/3 AC
Rated current Irated 1)
A
3.9
10.4
17.5
For S6 duty (40 %) IS6
A
3.3
11.5
19.3
Base-load current IH2)
A
3
7.4
13.6
Maximum current Imax
A
6 (0.24)
15.6
27.2
Type rating
Based on Irated
kW (hp)
0.75 (1)
2.2 (3)
4 (5)
Based on IH
kW (hp)
0.55 (0.75)
1.5 (2)
3 (4)
Rated pulse frequency
kHz
4
4
4
Efficiency ?
%
>96
>96
>96
Power loss 3)
at rated current
kW
0.04
0.12
0.18
Cooling air requirement
m3/s (ft3/s)
0.005 (0.18)
0.0092 (0.3)
0.0185 (0.7)
Sound pressure level
LpA (1 m)
dB
<56
<62
<65
24 V DC power supply
for Control Unit
A
1
1
1
Input current 4)
Rated current 1 AC/3 AC
A
9.6/5.5
24/13.9
43/24.8
Based on IH 1 AC/3 AC
A
8.4/4.8
20.9/12.1
37.5/21.7
Line supply connection
U1/L1, V1/L2, W1/L3
Screw terminals, plug-in
Screw terminals, plug-in
Screw terminals, plug-in
Conductor cross-section
mm2
1.5 ... 2.5
1.5 ... 6
6 ... 16
Motor connection
U2, V2, W2
Screw terminals, plug-in
Screw terminals, plug-in
Screw terminals, plug-in
Conductor cross-section
mm2
1.5 ... 2.5
1.5 ... 6
6 ... 16
Motor cable length, max.
Shielded
m (ft)
150 (492)
150 (492)
150 (492)
Unshielded
m (ft)
150 (492)
150 (492)
150 (492)
Degree of protection
IP20
IP20
IP20
Dimensions
Width
mm (in)
126 (4.96)
154 (6.06)
200 (7.87)
Height
mm (in)
238 (9.37)
345 (13.58)
411 (16.18)
Depth without operator panel
mm (in)
171 (6.73)
171 (6.73)
171 (6.73)
Frame size
FSA
FSB
FSC
Weight, approx.
With integrated line filter
Without integrated line filter
kg (lb)
1.8 (3.97)
3.4 (7.50)
5.8 (12.8)
With integrated line filter
kg (lb)
2 (4.41)
3.7 (8.16)
6.3 (13.9)
1) The rated output current Irated is based on the duty cycle for low overload (LO).
2) The base-load current IH is based on the duty cycle for high overload (HO).
4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1 %. The rated input currents apply for a load with the type rating (based on Irated) – these current values are specified on the rating plate.
Line voltage 380 ... 480 V 3 AC
PM240?2 Power Modules push-through variant
Without integrated line filter
6SL3211-1PE18-0UL1
6SL3211-1PE21-8UL0
6SL3211-1PE23-3UL0
With integrated line filter class A
6SL3211-1PE18-0AL1
6SL3211-1PE21-8AL0
6SL3211-1PE23-3AL0
Output current
at 50 Hz 400 V 3 AC
Rated current Irated1)
A
7.7
18
32
For S6 duty (40 %) IS6
A
8.5
19.8
37.1
Base-load current IH2)
A
5.9
13.2
26
Maximum current Imax
A
11.8
27
52
Type rating
Based on Irated
kW (hp)
3 (4)
7.5 (10)
15 (20)
Based on IH
kW (hp)
2.2 (7.5)
5.5 (7.5)
11 (15)
Rated pulse frequency
kHz
4
4
4
Efficiency ?
%
>96
>97
>97
Power loss 3)
at rated current
kW
0.113
0.239
0.385
Cooling air requirement
m3/s (ft3/s)
0.007 (0.2)
0.0092 (0.3)
0.0185 (0.7)
Sound pressure level
LpA (1 m)
dB
<56
<62
<65
24 V DC power supply
for Control Unit
A
1
1
1
Input current 4)
Rated current
A
10.1
22.2
39.9
Based on IH
A
8.8
19.8
36
Line supply connection
U1/L1, V1/L2, W1/L3
Screw terminals, plug-in
Screw terminals, plug-in
Screw terminals, plug-in
Conductor cross-section
mm2
1.5 ... 2.5
1.5 ... 6
6 ... 16
Motor connection
U2, V2, W2
Screw terminals, plug-in
Screw terminals, plug-in
Screw terminals, plug-in
Conductor cross-section
mm2
1.5 ... 2.5
1.5 ... 6
6 ... 16
Motor cable length, max.
Without filter, shielded/unshielded
m (ft)
150/150 (492/492)
150/150 (492/492)
150/150 (492/492)
With integrated filter class A, shielded/unshielded
m (ft)
50/100 (164/328)
100/100 (328/328) 5)
150/150 (492/492) 5)
Degree of protection
IP20
IP20
IP20
Dimensions
Width
mm (in)
126 (4.96)
154 (6.06)
200 (7.87)
Height
mm (in)
238 (9.37)
345 (13.58)
411 (16.18)
Depth without operator panel
mm (in)
171 (6.73)
171 (6.73)
171 (6.73)
Frame size
FSA
FSB
FSC
Weight, approx.
With integrated line filter
Without integrated line filter
kg (lb)
1.7 (3.75)
3.6 (7.94)
5.8 (12.8)
With integrated line filter
kg (lb)
1.8 (3.97)
3.9 (8.60)
6.3 (13.9)
1) The rated output current Irated is based on the duty cycle for low overload (LO).
2) The base-load current IH is based on the duty cycle for high overload (HO).
4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1 %. The rated input currents apply for a load with the type rating (based on Irated) – these current values are specified on the rating plate.
5) The values are applicable for low capacitance cables, e.g. MOTION?CONNECT. For standard CY cables the max. permissible motor cable length is 50 m (164 ft) (shielded).
skener.ru
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Àðìàòóðà DENDOR
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Äàò÷èêè è èçìåðèòåëè
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ðåãóëÿòîðû è ðåãèñòðàòîðû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ïíåâìàòè÷åñêîå îáîðóäîâàíèå
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Êðàíû è Êëàïàíû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Èçìåðèòåëüíûå ïðèáîðû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ñèñòåìû áåñïðîâîäíîãî óïðàâëåíèÿ «óìíûé äîì»
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Áåñêîíòàêòíûå âûêëþ÷àòåëè Êîíå÷íûå âûêëþ÷àòåëè Îïòè÷åñêèå äàò÷èêè Ýíêîäåðû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FS - Óñòàíîâêà óìÿã÷åíèÿ
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FK - Óñòàíîâêà îáåçæåëåçèâàíèÿ