Operating voltage | AC 24 V | Power consumption | 2 VA / 2 W | Setpoint setting range | 5…40 °C | Switching differential | Heating: 0.5…6 K
Cooling: 0.5…6 K | Communication | Bus: KNX (S-Mode und LTE-Mode mit Synco 700) | Analog inputs, number | 2 | Analog outputs | Valve, el. heater: 2; Fan: 1 (ECM) | Analog outputs, number | 3 | Analog output, signal | DC 0...10 V | Analog output, current | Max. ±1 mA | Digital inputs, number | 1 | Relay outputs | Valve, compressor or el. heater: 2 outputs, 2-position; Fan: 1- or 3-speed | Relay outputs, number | 3 | Relay output, switching voltage | AC 24...230 V | Relay output, switching current | 5 (4) A | Type of fixing | Wall mounting with screws | Degree of protection | IP30 | Dimensions (W x H x D) | 93 x 128 x 30.8 mm | Data sheet | N3191 |
|
|