RDG165KN - Room thermostat with KNX communications and built-in humidity sensor and humidity control, AC 24 V, for fan coil units and universal applications, heat pump, fan (1-/ 3-speed, DC), valves (2-point, DC)
Operating voltage
AC 24 V
Power consumption
2 VA / 2 W
Setpoint setting range
5…40 °C
Switching differential
Heating: 0.5…6 K
Cooling: 0.5…6 K
Communication
Bus: KNX (S-Mode und LTE-Mode mit Synco 700)
Analog inputs, number
2
Analog outputs
Valve, el. heater: 2; Fan: 1 (ECM)
Analog outputs, number
3
Analog output, signal
DC 0...10 V
Analog output, current
Max. ±1 mA
Digital inputs, number
1
Relay outputs
Valve, compressor or el. heater: 2 outputs, 2-position; Fan: 1- or 3-speed