The most important directives and standards are listed below. These are used as basis for the SINAMICSG180 compact units and they must be carefully observed to achieve an EMC-compliant configuration that is safe both functionally and in operation.

Standards for compact units

European directives

2006/95/EC

Low-voltage directive:
Legal guidelines of the EU member states concerning electrical equipment for use within specified voltage limits

2004/108/EC

EMC Directive:
Legal guidelines of the EU member states for electromagnetic compatibility

International and European standards

EN 954-1

Safety of machinery Safety-related parts of control systems;
Part 1: General design principles

ENISO13849‑1

Safety of machinery Safety-related parts of control systems;
Part 1: General design principles (ENISO 13849-1:2006 (replaced EN 954-1)

EN60146‑1‑1

Semiconductor converters General requirements and line-commutated converters
Part 1-1: Specification of basic requirements

EN60204‑1

Electrical equipment of machines
Part1: General definitions

EN 60529

Degrees of protection provided by enclosures (IP code)

EN 61140

Protection against electric shock - Common aspects for installation and equipment

EN61508‑1

Functional safety of electrical/electronic/programmable electronic safety-related systems,
Part1: General requirements

EN61800‑2

Adjustable speed electrical power drive systems,
Part 2: General requirements Rating specifications for low-voltage adjustable frequency AC power drive systems

EN61800‑3

Adjustable speed electrical power drive systems,
Part 3: EMC requirements and specific test methods

EN 61800-5-1

Adjustable speed electrical power drive systems,
Part 5-1: Safety requirements -
Electrical, thermal and energy requirements

EN61800‑5‑2

Adjustable speed electrical power drive systems,
Part 5-2: Safety requirements -
Functional safety (IEC 61800-5-2:2007)

North American standards

UL508C1)

Power conversion equipment

Approvals

TÜV NRTL US1)

Nationally Recognized Testing Laboratory



1) On request

General technical data

Electrical data

Line voltages

Type of supply system

Power ranges

230...400...500V3 AC, -15/+10%

TN/TT system

2.2...160kW(at 400V)

230...500V3 AC, -15/+10%

IT system

2.2...200kW(at 500 V)

230...690V3 AC, -15/+10%

TN/TT or IT system

7.5...200kW(at 690 V)

Line frequency

47...63 Hz

Output frequency

0...250 Hz

Voltage rise in motor

Typ. 500...1000V/μs, but <1500V/μs

Typical line harmonics (I) in % of fundamental mode for the 5/7/11/13/17/19/23/25 harmonics max.

38/18/8/7/5/4/3/2

Typical line harmonics (I) in % of fundamental mode for the 5/7/11/13/17/19/23/25 harmonics max. with LHF filter

1.4/3.6/2.4/1.7/1.0/0.6/0.8/0.4

Pulse number

6

Overvoltage category

III to EN61800‑5‑1

Short Circuit Current Rating (SCCR) according to UL508C (up to 600 V), in conjunction with the specified fuses or circuit breakers

60kA

Control method

  • For motors: Field-oriented control (FOC) with sensor and approval for explosion-proof motors as well as vector control (SVC) with/without sensor (speed, process speed (n), torque, hoist1), line synchronization1))
  • Motor-independent control of current or voltage (current, process current (I), voltage, process voltage (U))

Fixed speeds

3 fixed speeds + 1 minimum speed, parameterizable

Skipped speed ranges

2, parameterizable

Setpoint resolution

13 bits digital with n/f setpoint, 12bits digital with U/I torque setpoint, 9bits + sign analog

Braking operation

The oversaturation control system makes it possible to generate a braking torque of up to 50 % at low to mid-range speeds, and of up to 10 % at high speeds. If a higher braking torque is required, an optionally available braking module with appropriate braking resistor must be installed.

Mechanical data

Degree of protection

IP20, optionally IP21 provided by protective top cover (aluminum, unpainted)

Protection class

I acc. to EN61800‑5‑1

Touch protection

EN 50274 / BGV A3

Type of cooling

Forced air cooling AF to EN 60146

Paint finish

RAL9023 (R-Pearl Dark Grey)

Cable entry

From below

Ambient conditions2)

Storage 3)

Transport 3)

Operation

Ambient temperature

-25...+70C

Class 1K4 acc. to EN 60721-3-1

-25...+70C
down to -40C for 24h
Class 2K3 acc. to EN60721‑3‑2

Air: 0...40C/

Relative humidity
(condensation not permissible)

5...95%
Class 1K3 acc. to EN60721‑3‑1

5...95%
Class 2K3 acc. to EN60721‑3‑2

5...95%
Class 3K3 acc. to EN60721‑3‑3

Environmental class/harmful
chemical substances

Class 1C2 acc. to EN60721‑3‑1

Class 2C2 acc. to EN60721‑3‑2

Class 3C2 acc. to EN60721‑3‑3

Organic/biological influences

Class 1B1 acc. to EN60721‑3‑1

Class 2B1 acc. to EN60721‑3‑2

Class 3B1 acc. to EN60721‑3‑3

Pollution degree

2 acc. to EN61800‑5‑1

Installation altitude

Up to 1000m above sea level without derating, >1000m see derating table (in chapter Configuring instructions)

Mechanical stability2)

Storage 3)

Transport 3)

Operation

Vibratory load

  • Deflection
  • Acceleration

1.5 mm at 5 ... 9 Hz

5m/s2 at >9...200Hz

Class 1M2 acc. to EN60721‑3‑1

3.1mmat5...9Hz

10 m/s2 at >9...200Hz

Class 2M2 acc. to EN60721‑3‑2

0.075mmat10…58Hz

10m/s2 at >58…200Hz

-

Shock load

  • Acceleration

40 m/s2 at 22ms

Class 1M2 acc. to EN60721‑3‑1

100 m/s2 at 11ms

Class 2M2 acc. to EN60721‑3‑2

100 m/s2 at 11ms

Class 3M4 acc. to EN60721‑3‑3

Compliance with standards

CE Label

Acc. to EMC Directive No. 2004/108/EC and Low-Voltage Directive No. 2006/95/EC

Radio interference suppression

Complies with EMC guidelines defined in EN61800‑3 thanks to line filter which is integrated as standard (with grounded supply system):

  • Category C2 for compact units in TN/TT system of the first environment (residential area), category C1 available as an option
  • Category C4 for compact units in IT system of the second environment (industrial area)

Approvals

TÜV NRTL US2)



1) On request

2) Higher standards on request

3) In transport packaging

Deviations from the specified classes are underlined.

400V, 6‑pulse

Line voltage, supply system type

230...500V3AC, TT/TN

SINAMICS G180
compact units

6SE0100‑1AC15‑5❑A7

6SE0100‑1AC17‑0❑A7

6SE0100‑1AC21‑0❑A7

6SE0100‑1AC21‑3❑A7

6SE0100‑1AC21‑8❑A7

Converter type

2T2A‑07400‑002

2T2A‑07400‑003

2T2A‑07400‑004

2T2A‑07400‑005

2T2A‑07400‑007

Electrical data at motor end

Type rating 1)

  • at 50 Hz 400 V

kW

2.2

3

4

5.5

7.5

  • at 60 Hz 460 V

hp

3

5

6

9

12

Output voltage2)

V

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

Output current

  • Continuous current

A

5.5

7

9.5

13

18

  • Short-time current
    (60s every 10minutes) max.

A

6.5

8

11

15

20

Overload capability
(60s every 10minutes) max.

%

18

14

16

15

11

Output power

kVA

3.8

4.8

6.6

9

12.5

Output frequency, max.

Hz

250

250

250

250

250

Rated clock cycle

kHz

4.5

4.5

4.5

4.5

4.5

adjustable from

kHz

3...7.5

3...7.5

3...7.5

3...7.5

3...7.5

Power loss 3)

kW

0.13

0.16

0.2

0.26

0.33

Rated efficiency

%

95.2

95.8

95.9

96

96.2

Electrical data at line end

Connected load

kVA

3.7

4.5

6.2

8.5

12

Rated input voltage

V

400

400

400

400

400

Input current

  • Continuous line current

A

5.3

6.5

8.9

12.2

17.3

  • Short-time line current (60s) max.

A

6.3

7.4

10

14

19

Line fuse (provided by customer)

gL(A)

6…16

10...16

10...16

16

20...32

λline

0.927

0.94

0.918

0.937

0.918

Cosφline

1

1

1

1

1

Radio interference suppression acc. to
EN61800‑3

C2 (class A filter)

C2 (class A filter)

C2 (class A filter)

C2 (class A filter)

C2 (class A filter)

Mechanical data

Coolant requirements

m3/h

45

45

90

90

90

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

60

60

60

60

60

Max. cable length between converter and motor with standard insulation

  • on systems ≤400V (shielded)

m

200/3504)

200/3504)

200/3504)

200/3504)

200/3504)

  • on systems >400V (shielded)

m

150/3004)

150/3004)

150/3004)

150/3004)

150/3004)

Line/load connection

L1, L2, L3/U2, V2, W2

For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"

Dimensions

  • Width

mm

165

165

165

165

165

  • Height
    (without mounting brackets)

mm

410

410

410

410

510

  • Depth

mm

320

320

320

320

320

Weight, approx.

kg

11.5

11.5

11.5

11.5

16.5

Approvals, according to

NRTL5)

NRTL5)

NRTL5)

NRTL5)

NRTL5)

Frame size

K1

K1

K1

K1

K2



1)Rated power of a typical 2- to 6-pole standard motor.

2) Typical output voltage dependent on filter and unit type.

3) Maximum power loss with continuous current.

4) Value is applicable with option L10 (strengthened dv/dt filter; strengthened filter is integrated in unit).

5) On request

Line voltage, supply system type

230...500V3AC, TT/TN

SINAMICS G180
compact units

6SE0100‑1AC22‑5❑A7

6SE0100‑1AC23‑7❑A7

6SE0100‑1AC24‑8❑A7

6SE0100‑1AC25‑8❑A7

6SE0100‑1AC27‑8❑A7

Converter type

2T2A‑07400‑011

2T2A‑07400‑015

2T2A‑07400‑022

2T2A‑07400‑030

2T2A‑07400‑037

Electrical data at motor end

Type rating 1)

  • at 50 Hz 400 V

kW

11

15

22

30

37

  • at 60 Hz 460 V

hp

17

23

34

46

57

Output voltage2)

V

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

Output current

  • Continuous current

A

24.5

37

48

58

78

  • Short-time current
    (60s every 10minutes) max.

A

27

44

54

63

88

Overload capability
(60s every 10minutes) max.

%

10

19

13

9

13

Output power

kVA

17

25.6

33.3

40.2

54

Output frequency, max.

Hz

250

250

250

250

250

Rated clock cycle

kHz

4.5

4.5

4.5

4.5

3

adjustable from

kHz

3...7.5

3...7.5

3...7.5

3...7.5

2...5

Power loss 3)

kW

0.47

0.6

0.84

1.1

1.35

Rated efficiency

%

96.3

96.5

96.6

96.7

96.7

Electrical data at line end

Connected load

kVA

15.7

24.3

31.8

39.1

52.2

Rated input voltage

V

400

400

400

400

400

Input current

  • Continuous line current

A

22.7

35.1

45.9

56.5

75.3

  • Short-time line current (60s) max.

A

25

42

52

61

85

Line fuse (provided by customer)

gL(A)

25...32

40...80

50...80

63…80

80...100

λline

0.932

0.932

0.932

0.924

0.932

Cosφline

1

1

1

1

1

Radio interference suppression acc. to
EN61800‑3

C2 (class A filter)

C2 (class A filter)

C2 (class A filter)

C2 (class A filter)

C2 (class A filter)

Mechanical data

Coolant requirements

m3/h

130

280

280

280

750

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

60

60

60

60

62

Max. cable length between converter and motor with standard insulation

  • on systems ≤400V (shielded)

m

200/3504)

200/3504)

200/3504)

200/3504)

200/3504)

  • on systems >400V (shielded)

m

150/3004)

150/3004)

150/3004)

150/3004)

150/3004)

Line/load connection

L1, L2, L3/U2, V2, W2

For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"

Dimensions

  • Width

mm

165

225

225

225

350

  • Height
    (without mounting brackets)

mm

510

610

610

610

710

  • Depth

mm

320

320

320

320

320

Weight, approx.

kg

16.5

30

31

31

51

Approvals, according to

NRTL5)

NRTL5)

NRTL5)

NRTL5)

NRTL5)

Frame size

K2

K3

K3

K3

K4



1)Rated power of a typical 2- to 6-pole standard motor.

2) Typical output voltage dependent on filter and unit type.

3) Maximum power loss with continuous current.

4) Value is applicable with option L10 (strengthened dv/dt filter; strengthened filter is integrated in unit).

5) On request

Line voltage, supply system type

230...500V3AC, TT/TN

SINAMICS G180
compact units

6SE0100‑1AC28‑8❑A7

6SE0100‑1AC31‑1❑A7

6SE0100‑1AC31‑5❑A7

6SE0100‑1AC31‑8❑A7

6SE0100‑1AC32‑1❑A7

Converter type

2T2A‑07400‑045

2T2A‑07400‑055

2T2A‑07400‑075

2T2A‑07400‑090

2T2A‑07400‑110

Electrical data at motor end

Type rating 1)

  • at 50 Hz 400 V

kW

45

55

75

90

110

  • at 60 Hz 460 V

hp

69

85

116

139

170

Output voltage2)

V

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

Output current

  • Continuous current

A

88

110

145

175

205

  • Short-time current
    (60s every 10minutes) max.

A

110

126

165

204

240

Overload capability
(60s every 10minutes) max.

%

25

15

14

17

17

Output power

kVA

61

76.2

100

121

142

Output frequency, max.

Hz

250

250

250

250

250

Rated clock cycle

kHz

3

3

3

3

3

adjustable from

kHz

2...5

2...5

2...5

2...5

2...5

Power loss 3)

kW

1.59

1.86

2.37

2.83

3.33

Rated efficiency

%

96.8

96.9

97.1

97.1

97.2

Electrical data at line end

Connected load

kVA

57.3

74.8

97.7

119

134

Rated input voltage

V

400

400

400

400

400

Input current

  • Continuous line current

A

82.7

108

141

172

194

  • Short-time line current (60s) max.

A

103

124

160

200

227

Line fuse (provided by customer)

gL(A)

100

125

160

200

200...250

λline

0.924

0.929

0.929

0.924

0.924

Cosφline

1

1

1

1

1

Radio interference suppression acc. to
EN61800‑3

C2 (class A filter)

C2 (class A filter)

C2 (class A filter)

C2 (class A filter)

C2 (class A filter)

Mechanical data

Coolant requirements

m3/h

750

750

1050

1050

1050

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

62

62

64

64

64

Max. cable length between converter and motor with standard insulation

  • on systems ≤400V (shielded)

m

200/3504)

200/3504)

200/3504)

200/3504)

200/3504)

  • on systems >400V (shielded)

m

150/3004)

150/3004)

150/3004)

150/3004)

150/3004)

Line/load connection

L1, L2, L3/U2, V2, W2

For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"

Dimensions

  • Width

mm

350

350

350

350

350

  • Height
    (without mounting brackets)

mm

710

710

1060

1060

1060

  • Depth

mm

320

320

320

320

320

Weight, approx.

kg

53

55

90

94

96

Approvals, according to

NRTL5)

NRTL5)

NRTL5)

NRTL5)

NRTL5)

Frame size

K4

K4

K5

K5

K5



1)Rated power of a typical 2- to 6-pole standard motor.

2) Typical output voltage dependent on filter and unit type.

3) Maximum power loss with continuous current.

4) Value is applicable with option L10 (strengthened dv/dt filter; strengthened filter is integrated in unit).

5) On request

Line voltage, supply system type

230...500V3AC, TT/TN

SINAMICS G180
compact units

6SE0100‑1AC32‑5❑A7

6SE0100‑1AC33‑0❑A7

Converter type

2T2A‑07400‑132

2T2A‑07400‑160

Electrical data at motor end

Type rating 1)

  • at 50 Hz 400 V

kW

132

160

  • at 60 Hz 460 V

hp

204

247

Output voltage2)

V

0...0.98×Vline

0...0.98×Vline

Output current

  • Continuous current

A

245

295

  • Short-time current
    (60s every 10minutes) max.

A

300

360

Overload capability
(60s every 10minutes) max.

%

22

22

Output power

kVA

170

204

Output frequency, max.

Hz

250

250

Rated clock cycle

kHz

3

3

adjustable from

kHz

2...5

2...5

Power loss 3)

kW

3.84

4.65

Rated efficiency

%

97.3

97.3

Electrical data at line end

Connected load

kVA

161

197

Rated input voltage

V

400

400

Input current

  • Continuous line current

A

232

284

  • Short-time line current (60s) max.

A

284

347

Line fuse (provided by customer)

gL(A)

250...315

315...400

λline

0.924

0.924

Cosφline

1

1

Radio interference suppression acc. to
EN61800‑3

C2 (class A filter)

C2 (class A filter)

Mechanical data

Coolant requirements

m3/h

1600

1600

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

66

66

Max. cable length between converter and motor with standard insulation

  • on systems ≤400V (shielded)

m

200/3504)

200/3504)

  • on systems >400V (shielded)

m

150/3004)

150/3004)

Line/load connection

L1, L2, L3/U2, V2, W2

For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"

Dimensions

  • Width

mm

500

500

  • Height
    (without mounting brackets)

mm

1060

1060

  • Depth

mm

320

320

Weight, approx.

kg

160

170

Approvals, according to

NRTL5)

NRTL5)

Frame size

K6

K6



1)Rated power of a typical 2- to 6-pole standard motor.

2) Typical output voltage dependent on filter and unit type.

3) Maximum power loss with continuous current.

4) Value is applicable with option L10 (strengthened dv/dt filter; strengthened filter is integrated in unit).

5) On request

500 V, 6‑pulse

Line voltage, supply system type

230...500V3AC, IT

SINAMICS G180
compact units

6SE0100‑1AD14‑5❑A7

6SE0100‑1AD15‑5❑A7

6SE0100‑1AD17‑0❑A7

6SE0100‑1AD21‑0❑A7

6SE0100‑1AD21‑3❑A7

Converter type

2T2A‑07500‑002

2T2A‑07500‑003

2T2A‑07500‑004

2T2A‑07500‑005

2T2A‑07500‑007

Electrical data at motor end

Type rating 1)

  • at 50 Hz 500 V

kW

2.2

3

4

5.5

7.5

  • at 60 Hz 460 V

hp

3

4

5

7

9

Output voltage2)

V

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

Output current

  • Continuous current

A

4.5

5.5

7

9.5

13

  • Short-time current
    (60s every 10minutes) max.

A

5

6.5

8

11

15

Overload capability
(60s every 10minutes) max.

%

11

18

14

16

15

Output power

kVA

3.9

4.8

6.1

8.2

11.3

Output frequency, max.

Hz

250

250

250

250

250

Rated clock cycle

kHz

4.5

4.5

4.5

4.5

4.5

adjustable from

kHz

3...7.5

3...7.5

3...7.5

3...7.5

3...7.5

Power loss 3)

kW

0.12

0.16

0.2

0.26

0.34

Rated efficiency

%

95.6

95.7

95.9

96.0

96.1

Electrical data at line end

Connected load

kVA

3.7

4.6

6.4

8.6

12.1

Rated input voltage

V

500

500

500

500

500

Input current

  • Continuous line current

A

4.4

5.2

6.5

9.3

12.5

  • Short-time line current (60s) max.

A

4.9

6.1

7.4

11

14

Line fuse (provided by customer)

gL(A)

4...16

6...16

10...16

10...16

16

λline

0.902

0.912

0.932

0.908

0.927

Cosφline

1

1

1

1

1

Radio interference suppression acc. to
EN61800‑3

C4

C4

C4

C4

C4

Mechanical data

Coolant requirements

m3/h

45

45

45

90

90

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

60

60

60

60

60

Max. cable length between converter and motor with standard insulation

  • (shielded)

m

3004)

3004)

3004)

3004)

3004)

Line/load connection

L1, L2, L3/U2, V2, W2

For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"

Dimensions

  • Width

mm

165

165

165

165

165

  • Height
    (without mounting brackets)

mm

410

410

410

410

410

  • Depth

mm

320

320

320

320

320

Weight, approx.

kg

11.5

11.5

11.5

11.5

11.5

Approvals, according to

NRTL5)

NRTL5)

NRTL5)

NRTL5)

NRTL5)

Frame size

K1

K1

K1

K1

K1



1)Rated power of a typical 2- to 6-pole standard motor.

2) Typical output voltage dependent on filter and unit type.

3) Maximum power loss with continuous current.

4) Option L10 included (strengthened dv/dt filter; strengthened filter is integrated in unit).

5) On request

Line voltage, supply system type

230...500V3AC, IT

SINAMICS G180
compact units

6SE0100‑1AD21‑8❑A7

6SE0100‑1AD22‑5❑A7

6SE0100‑1AD23‑7❑A7

6SE0100‑1AD24‑8❑A7

6SE0100‑1AD25‑8❑A7

Converter type

2T2A‑07500‑011

2T2A‑07500‑015

2T2A‑07500‑022

2T2A‑07500‑030

2T2A‑07500‑037

Electrical data at motor end

Type rating 1)

  • at 50 Hz 500 V

kW

11

15

22

30

37

  • at 60 Hz 460 V

hp

17

23

34

46

57

Output voltage2)

V

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

0...0.98× Vline

Output current

  • Continuous current

A

18

24.5

37

48

58

  • Short-time current
    (60s every 10minutes) max.

A

20

27

44

54

63

Overload capability
(60s every 10minutes) max.

%

11

10

19

13

9

Output power

kVA

15.6

21.2

32

41.6

50.2

Output frequency, max.

Hz

250

250

250

250

250

Rated clock cycle

kHz

4.5

4.5

4.5

4.5

4.5

adjustable from

kHz

3...7.5

3...7.5

3...7.5

3...7.5

3...7.5

Power loss 3)

kW

0.48

0.63

0.89

1.17

1.35

Rated efficiency

%

96.2

96.3

96.4

96.5

96.7

Electrical data at line end

Connected load

kVA

16

24.4

32

39.2

52.3

Rated input voltage

V

500

500

500

500

500

Input current

  • Continuous line current

A

17.4

23.4

35.8

46.8

57.1

  • Short-time line current (60s) max.

A

19

26

43

53

62

Line fuse (provided by customer)

gL(A)

20...32

25...32

40...80

50...80

63...80

λline

0.902

0.924

0.918

0.924

0.912

Cosφline

1

1

1

1

1

Radio interference suppression acc. to
EN61800‑3

C4

C4

C4

C4

C4

Mechanical data

Coolant requirements

m3/h

90

130

280

280

280

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

60

60

60

60

62

Max. cable length between converter and motor with standard insulation

  • (shielded)

m

3004)

3004)

3004)

3004)

3004)

Line/load connection

L1, L2, L3/U2, V2, W2

For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"

Dimensions

  • Width

mm

165

165

225

225

225

  • Height
    (without mounting brackets)

mm

510

510

610

610

610

  • Depth

mm

320

320

320

320

320

Weight, approx.

kg

16.5

17.5

30

32

32

Approvals, according to

NRTL5)

NRTL5)

NRTL5)

NRTL5)

NRTL5)

Frame size

K2

K2

K3

K3

K3



1)Rated power of a typical 2- to 6-pole standard motor.

2) Typical output voltage dependent on filter and unit type.

3) Maximum power loss with continuous current.

4) Option L10 included (strengthened dv/dt filter; strengthened filter is integrated in unit).

5) On request

Line voltage, supply system type

230...500V3AC, IT

SINAMICS G180
compact units

6SE0100‑1AD27‑8❑A7

6SE0100‑1AD28‑8❑A7

6SE0100‑1AD31‑1❑A7

6SE0100‑1AD31‑5❑A7

6SE0100‑1AD31‑8❑A7

Converter type

2T2A‑07500‑045

2T2A‑07500‑055

2T2A‑07500‑075

2T2A‑07500‑090

2T2A‑07500‑110

Electrical data at motor end

Type rating 1)

  • at 50 Hz 500 V

kW

45

55

75

90

110

  • at 60 Hz 460 V

hp

56

68

93

111

136

Output voltage2)

V

0...0.98×Vline

0...0.98× Vline

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

Output current

  • Continuous current

A

78

88

110

145

175

  • Short-time current
    (60s every 10minutes) max.

A

88

110

126

165

204

Overload capability
(60s every 10minutes) max.

%

13

25

15

14

17

Output power

kVA

67.5

76.2

95.3

126

152

Output frequency, max.

Hz

250

250

250

250

250

Rated clock cycle

kHz

3

3

3

3

3

adjustable from

kHz

2...5

2...5

2...5

20...5

2...5

Power loss 3)

kW

1.59

1.8

2.37

2.83

3.33

Rated efficiency

%

96.8

97.0

97.1

97.1

97.2

Electrical data at line end

Connected load

kVA

57.5

74.8

98.4

119

136

Rated input voltage

V

500

500

500

500

500

Input current

  • Continuous line current

A

73.7

87.6

109

143

170

  • Short-time line current (60s) max.

A

83

110

125

163

198

Line fuse (provided by customer)

gL(A)

80...100

100

125

160

200

λline

0.918

0.912

0.918

0.918

0.908

Cosφline

1

1

1

1

1

Radio interference suppression acc. to
EN61800‑3

C4

C4

C4

C4

C4

Mechanical data

Coolant requirements

m3/h

750

750

750

1050

1050

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

62

62

64

64

64

Max. cable length between converter and motor with standard insulation

  • (shielded)

m

3004)

3004)

3004)

3004)

3004)

Line/load connection

L1, L2, L3/U2, V2, W2

For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"

Dimensions

  • Width

mm

350

350

350

350

350

  • Height
    (without mounting brackets)

mm

710

710

710

1060

1060

  • Depth

mm

320

320

320

320

320

Weight, approx.

kg

51

53

55

90

94

Approvals, according to

NRTL5)

NRTL5)

NRTL5)

NRTL5)

NRTL5)

Frame size

K4

K4

K4

K5

K5



1)Rated power of a typical 2- to 6-pole standard motor.

2) Typical output voltage dependent on filter and unit type.

3) Maximum power loss with continuous current.

4) Option L10 included (strengthened dv/dt filter; strengthened filter is integrated in unit).

5) On request

Line voltage, supply system type

230...500V3AC, IT

SINAMICS G180
compact units

6SE0100‑1AD32‑1❑A7

6SE0100‑1AD32‑5❑A7

6SE0100‑1AD33‑0❑A7

Converter type

2T2A‑07500‑132

2T2A‑07500‑160

2T2A‑07500‑200

Electrical data at motor end

Type rating 1)

  • at 50 Hz 500 V

kW

132

160

200

  • at 60 Hz 460 V

hp

163

197

247

Output voltage2)

V

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

Output current

  • Continuous current

A

205

245

295

  • Short-time current
    (60s every 10minutes) max.

A

240

300

360

Overload capability
(60s every 10minutes) max.

%

17

22

22

Output power

kVA

178

212

256

Output frequency, max.

Hz

250

250

250

Rated clock cycle

kHz

3

3

3

adjustable from

kHz

2...5

2...5

2...5

Power loss 3)

kW

3.84

4.48

5.6

Rated efficiency

%

97.3

97.4

97.4

Electrical data at line end

Connected load

kVA

161

197

3.8

Rated input voltage

V

500

500

500

Input current

  • Continuous line current

A

196

237

286

  • Short-time line current (60s) max.

A

230

290

349

Line fuse (provided by customer)

gL(A)

200...250

250...315

315...400

λline

0.912

0.912

0.912

Cosφline

1

1

1

Radio interference suppression acc. to
EN61800‑3

C4

C4

C4

Mechanical data

Coolant requirements

m3/h

1050

1600

1600

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

66

66

60

Max. cable length between converter and motor with standard insulation

  • (shielded)

m

3004)

3004)

3004)

Line/load connection

L1, L2, L3/U2, V2, W2

For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"

Dimensions

  • Width

mm

350

500

500

  • Height
    (without mounting brackets)

mm

1060

1060

1060

  • Depth

mm

320

320

320

Weight, approx.

kg

96

170

180

Approvals, according to

NRTL5)

NRTL5)

NRTL5)

Frame size

K5

K6

K6



1)Rated power of a typical 2- to 6-pole standard motor.

2) Typical output voltage dependent on filter and unit type.

3) Maximum power loss with continuous current.

4) Option L10 included (strengthened dv/dt filter; strengthened filter is integrated in unit).

5) On request

690 V, 6‑pulse

Line voltage, supply system type

230...690 V3AC, TT/TN or IT

SINAMICS G180
compact units

6SE0100‑1A❑21‑0❑A7

6SE0100‑1A❑21‑3❑A7

6SE0100‑1A❑21‑8❑A7

6SE0100‑1A❑22‑5❑A7

6SE0100‑1A❑23‑4❑A7

Converter type

2T2A‑07600‑007

2T2A‑07600‑011

2T2A‑07600‑015

2T2A‑07600‑022

2T2A‑07600‑030

Electrical data at motor end

Type rating 1)

  • at 50 Hz 690 V

kW

7.5

11

15

22

30

  • at 60 Hz 575 V

hp

8

12

17

25

34

Output voltage2)

V

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

Output current

  • Continuous current

A

9.5

13

18

27

36

  • Short-time current
    (60s every 10minutes) max.

A

11

16

21

33

45

Overload capability
(60s every 10minutes) max.

%

16

23

17

22

25

Output power

kVA

11.4

15.5

21.5

32.3

43

Output frequency, max.

Hz

250

250

250

250

250

Rated clock cycle

kHz

3

3

3

3

3

adjustable from

kHz

2...5

2...5

2...5

2...5

2...5

Power loss 3)

kW

0.29

0.4

0.55

0.74

1

Rated efficiency

%

96.7

96.8

96.8

97.0

97.0

Electrical data at line end

Connected load

kVA

3.7

4.6

6.4

8.6

12.1

Rated input voltage

V

690

690

690

690

690

Input current

  • Continuous line current

A

8.8

11.8

16.8

25.3

37.3

  • Short-time line current (60s) max.

A

10

14

20

31

47

Line fuse (provided by customer)

gL(A)

10...32

16...32

20...32

32

40...63

λline

0.94

0.948

0.94

0.948

0.867

Cosφline

1

1

1

1

1

Radio interference suppression acc. to
EN61800‑34)

C2 (class A filter)

C2 (class A filter)

C2 (class A filter)

C2 (class A filter)

C2 (class A filter)

Mechanical data

Coolant requirements

m3/h

90

90

130

130

750

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

60

60

60

60

60

Max. cable length between converter and motor with standard insulation

  • (shielded)

m

3005)

3005)

3005)

3005)

3005)

Line/load connection

L1, L2, L3/U2, V2, W2

For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"

Dimensions

  • Width

mm

225

225

225

225

350

  • Height
    (without mounting brackets)

mm

610

610

610

610

710

  • Depth

mm

320

320

320

320

320

Weight, approx.

kg

26

26

28

28

55

Approvals, according to

NRTL6)

NRTL6)

NRTL6)

NRTL6)

NRTL6)

Frame size

K3

K3

K3

K3

K4



1)Rated power of a typical 2- to 6-pole standard motor.

2) Typical output voltage dependent on filter and unit type.

3) Maximum power loss with continuous current.

4)EMC filter not required for IT system, in which case RI suppression category C4.

5) Value is applicable with option L10 (strengthened dv/dt filter; strengthened filter is integrated in unit).

6)On request; the voltage range for NRTL units ends at max. 600V.

Line voltage, supply system type

230...690 V3AC, TT/TN or IT

SINAMICS G180
compact units

6SE0100‑1A❑24‑2❑A7

6SE0100‑1A❑25‑0❑A7

6SE0100‑1A❑25‑8❑A7

6SE0100‑1A❑28‑0❑A7

6SE0100‑1A❑31‑0❑A7

Converter type

2T2A‑07600‑037

2T2A‑07600‑045

2T2A‑07600‑055

2T2A‑07600‑075

2T2A‑07600‑090

Electrical data at motor end

Type rating 1)

  • at 50 Hz 690 V

kW

37

45

55

75

90

  • at 60 Hz 575 V

hp

41

50

62

84

101

Output voltage2)

V

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

Output current

  • Continuous current

A

43

50

60

80

95

  • Short-time current
    (60s every 10minutes) max.

A

55

65

75

90

120

Overload capability
(60s every 10minutes) max.

%

28

30

25

13

26

Output power

kVA

51.4

59.8

71.7

95.6

114

Output frequency, max.

Hz

250

250

250

250

250

Rated clock cycle

kHz

3

3

3

3

3

adjustable from

kHz

2...5

2...5

2...5

2...5

2...5

Power loss 3)

kW

1.19

1.44

1.68

2.28

2.63

Rated efficiency

%

97.1

97.1

97.2

97.2

97.3

Electrical data at line end

Connected load

kVA

16

24.4

32

39.2

52.3

Rated input voltage

V

690

690

690

690

690

Input current

  • Continuous line current

A

42.9

50.1

60.7

80.9

102

  • Short-time line current (60s) max.

A

55

65

76

91

129

Line fuse (provided by customer)

gL(A)

50...63

63

63...80

100

125

λline

0.898

0.863

0.894

0.896

0.845

Cosφline

1

1

1

1

1

Radio interference suppression acc. to
EN61800‑34)

C2 (class A filter)

C2 (class A filter)

C2 (class A filter)

C2 (class A filter)

C2 (class A filter)

Mechanical data

Coolant requirements

m3/h

750

750

750

750

1050

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

60

60

60

60

62

Max. cable length between converter and motor with standard insulation

  • (shielded)

m

3005)

3005)

3005)

3005)

150 (300) 6)

Line/load connection

L1, L2, L3/U2, V2, W2

For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"

Dimensions

  • Width

mm

350

350

350

350

350

  • Height
    (without mounting brackets)

mm

710

710

710

710

1060

  • Depth

mm

320

320

320

320

320

Weight, approx.

kg

55

59

59

59

90

Approvals, according to

NRTL7)

NRTL7)

NRTL7)

NRTL7)

NRTL7)

Frame size

K4

K4

K4

K4

K5



1)Rated power of a typical 2- to 6-pole standard motor.

2) Typical output voltage dependent on filter and unit type.

3) Maximum power loss with continuous current.

4)EMC filter not required for IT system, in which case RI suppression category C4.

5) Value is applicable with option L10 (strengthened dv/dt filter; strengthened filter is integrated in unit).

6) Value is applicable with option L10 (strengthened dv/dt filter; strengthened filter is supplied separately with unit).

7)On request; the voltage range for NRTL units ends at max. 600V.

Line voltage, supply system type

230...690 V3AC, TT/TN or IT

SINAMICS G180
compact units

6SE0100‑1A❑31‑2❑A7

6SE0100‑1A❑31‑4❑A7

6SE0100‑1A❑31‑7❑A7

6SE0100‑1A❑32‑1❑A7

Converter type

2T2A‑07600‑110

2T2A‑07600‑132

2T2A‑07600‑160

2T2A‑07600‑200

Electrical data at motor end

Type rating 1)

  • at 50 Hz 690 V

kW

110

132

160

200

  • at 60 Hz 575 V

hp

122

148

179

224

Output voltage2)

V

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

0...0.98×Vline

Output current

  • Continuous current

A

120

150

175

210

  • Short-time current
    (60s every 10minutes) max.

A

140

175

210

255

Overload capability
(60s every 10minutes) max.

%

17

17

20

21

Output power

kVA

143

179

209

251

Output frequency, max.

Hz

250

250

250

250

Rated clock cycle

kHz

3

3

3

3

adjustable from

kHz

2...5

2...5

2...5

2...5

Power loss 3)

kW

3.21

3.7

4.48

5.38

Rated efficiency

%

97.3

97.4

97.4

97.5

Electrical data at line end

Connected load

kVA

57.5

74.8

98.4

119

Rated input voltage

V

690

690

690

690

Input current

  • Continuous line current

A

119

153

180

222

  • Short-time line current (60s) max.

A

139

178

216

270

Line fuse (provided by customer)

gL(A)

125...160

160...200

200...250

250...315

λline

0.883

0.857

0.862

0.838

Cosφline

1

1

1

1

Radio interference suppression acc. to
EN61800‑3

C2 (class A filter)

C2 (class A filter)

C2 (class A filter)

C2 (class A filter)

Mechanical data

Coolant requirements

m3/h

1050

1050

1600

1600

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

62

62

64

64

Max. cable length between converter and motor with standard insulation

  • (shielded)

m

150/3004)

150/3004)

150/3004)

150/3004)

Line/load connection

L1, L2, L3/U2, V2, W2

For connection cross-sections, see "Cable cross-sections and connections" in section "Configuring instructions"

Dimensions

  • Width

mm

350

350

500

500

  • Height
    (without mounting brackets)

mm

1060

1060

1060

1060

  • Depth

mm

320

320

320

320

Weight, approx.

kg

94

96

170

180

Approvals, according to

NRTL5)

NRTL5)

NRTL5)

NRTL5)

Frame size

K5

K5

K6

K6



1)Rated power of a typical 2- to 6-pole standard motor.

2) Typical output voltage dependent on filter and unit type.

3) Maximum power loss with continuous current.

4) Value is applicable with option L10 (strengthened dv/dt filter; strengthened filter is supplied separately with unit).

5) On request; the voltage range for NRTL units ends at max. 600V.

















skener.ru

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
DENDOR

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FS -

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FK -

  © " " 2007-2022
  (4872) 700-366  skenergo@mail.ru
.