General technical specifications | PM240M Power Modules |
|---|
System operating voltage | 380 V (-10 %) ... 480 V (+10 %) 3 AC | Line supply requirements Short-circuit power ratio RSC | >100 | Input frequency | 47 ... 63 Hz | Output frequency | | | 0 ... 550 Hz | | 0 ... 200 Hz | Pulse frequency | 4 kHz (standard); 4 ... 16 Hz (in steps of 2 kHz) see derating data | Power factor | 0.95 | Inverter efficiency | 95 ... 97 % | Output voltage, max. in % of the input voltage | 87 % | Overload capability | | | 0.37 ... 3 kW (0.5 ... 4 hp): 2 × rated output current for 3 s, followed by 1.5 × rated output current for 57 s, over a cycle time of 300 s (110 % on average) 4 kW (5 hp): 1.6 × rated output current for 3 s, followed by 1.5 × rated output current for 57 s, over a cycle time of 300 s (110 % on average) | Electromagnetic compatibility | Integrated line filter class A according to EN 55011 | Possible braking methods | Dynamic brake with internal braking resistors (accessories) Dynamic brake with external braking resistors Rmin = 200 Ω (for FSA), Rmin = 60 Ω (for FSB) DC brake Integrated brake control supplies DC power supply for the brake | Line input voltage | 380 V AC | 400 V AC | 440 V AC | 480 V AC | Resulting brake voltage | 171 V DC | 180 V DC | 198 V DC | 216 V DC | Disconnection on the DC side permits "fast" braking (max. output current 1 A) | Degree of protection 1) | IP66 (for Control Unit, screw-type version) IP65 (for Control Units, plug-in version) | Operating temperature | -10 ... +40 °C (14 ... 104 °F) without derating >40 ... 55 ℃ (104 ... 131 °F) see derating characteristics | Storage temperature | -40 ... +70 °C (-40 ... +158 °F) | Permissible mounting positions | All | Relative humidity | <95 % RH, condensation not permissible | Cooling | External cooling with motor fan | Installation altitude | Up to 1000 m (3281 ft) above sea level without derating Over 1000 m (3281 ft) see derating data | Short Circuit Current Rating (SCCR) 2) | 40 kA | Protection functions | - Undervoltage
- Phase failure detection
- Overvoltage
- Overload
- Ground fault
- Short-circuit
- Stall protection
- Motor blocking protection
- Motor overtemperature
- Inverter overtemperature
- Parameter locking
| Compliance with standards | UR, cUR, CE, RCM | CE marking, according to | Low Voltage Directive 2014/35/EU Filtered variants also: EMC Directive 2014/30/EU |
1) Applies to Power Modules and Control Units in the mounted state. 2) Applies to industrial control panel installations to NEC article 409 or UL 508A. Line voltage 380 … 480 V 3 AC | | PM240M Power Modules |
|---|
| | 6SL3517-1BE11-3AM0 | 6SL3517-1BE12-3AM0 | 6SL3517-1BE13-3AM0 | 6SL3517-1BE14-3AM0 |
|---|
Rated output current Irated1) | A | 1.3 | 2.2 | 3.1 | 4.1 | Maximum output current Imax | A | 2.6 | 4.4 | 6.2 | 8.2 | Rated power | kW (hp) | 0.37 (0.5) | 0.75 (1) | 1.1 (1.5) | 1.5 (2) | Rated pulse frequency | kHz | 4 | 4 | 4 | 4 | Efficiency η | % | 96.8 | 98.1 | 98.2 | 97.3 | Power loss 2) At rated output current | kW | 0.025 | 0.032 | 0.041 | 0.052 | Cooling air requirement | m3/s (ft3/s) | 0.0048 (0.17) | 0.0048 (0.17) | 0.0048 (0.17) | 0.0048 (0.17) | Sound pressure level LpA (1 m) | dB | – | – | – | – | Rated input current 3) | A | 1.3 | 2 | 2.8 | 3.6 | Line supply connection U1/L1, V1/L2, W1/L3, PE | | | | | | - Conductor cross-section (recommended)
| mm2 | 1 ... 2.5 18 ... 14 AWG | 1 ... 2.5 18 ... 14 AWG | 1 ... 2.5 18 ... 14 AWG | 1 ... 2.5 18 ... 14 AWG | PE connection (external connection) | | | | | | - Conductor cross-section (recommended)
| mm2 | 10 | 10 | 10 | 10 | Motor connection U2, V2, W2, PE, motor brake, temperature sensor | | | | | | | mm2 | 1 ... 2.5 18 ... 14 AWG | 1 ... 2.5 18 ... 14 AWG | 1 ... 2.5 18 ... 14 AWG | 1 ... 2.5 18 ... 14 AWG | Motor cable length (with wall mounting kit), max. Shielded | m (ft) | 5 (16.41) | 5 (16.41) | 5 (16.41) | 5 (16.41) | Degree of protection | | IP66 | IP66 | IP66 | IP66 | Dimensions | | | | | | | mm (in) | 161 (6.34) | 161 (6.34) | 161 (6.34) | 161 (6.34) | | mm (in) | 135 (5.31) | 135 (5.31) | 135 (5.31) | 135 (5.31) | | mm (in) | 270 (10.63) | 270 (10.63) | 270 (10.63) | 270 (10.63) | Frame size | | FSA | FSA | FSA | FSA | Weight, approx. | kg (lb) | 2.1 (4.63) | 2.1 (4.63) | 2.1 (4.63) | 2.1 (4.63) |
1) The rated output current Irated is based on the duty cycle for high overload (HO). 2) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311. 3) The input current depends on the motor load and line impedance. The input currents apply for loading at rated power with a line impedance corresponding to uK = 1 %. Line voltage 380 … 480 V 3 AC | | PM240M Power Modules |
|---|
| | 6SL3517-1BE16-3AM0 | 6SL3517-1BE17-7AM0 | 6SL3517-1BE21-0AM0 |
|---|
Rated output current Irated1) | A | 5.6 | 7.3 | 8.8 | Maximum output current Imax | A | 11.2 | 14.6 | 14.1 | Rated power | kW (hp) | 2.2 (3) | 3 (4) | 4 (5) | Rated pulse frequency | kHz | 4 | 4 | 4 | Efficiency η | % | 97.6 | 97.6 | 97.7 | Power loss 2) At rated output current | kW | 0.078 | 0.103 | 0.126 | Cooling air requirement | m3/s (ft3/s) | 0.024 (0.85) | 0.024 (0.85) | 0.024 (0.85) | Sound pressure level LpA (1 m) | dB | – | – | – | Rated input current 3) | A | 5.3 | 6.9 | 8 | Line supply connection U1/L1, V1/L2, W1/L3, PE | | | | | - Conductor cross-section (recommended)
| mm2 | 1 ... 2.5 18 ... 14 AWG | 1 ... 2.5 18 ... 14 AWG | 1 ... 2.5 18 ... 14 AWG | PE connection (external connection) | | | | | - Conductor cross-section (recommended)
| mm2 | 10 | 10 | 10 | Motor connection U2, V2, W2, PE, motor brake, temperature sensor | | | | | | mm2 | 1 ... 2.5 18 ... 14 AWG | 1 ... 2.5 18 ... 14 AWG | 1 ... 2.5 18 ... 14 AWG | Motor cable length (with wall mounting kit), max. Shielded | m (ft) | 5 (16.41) | 5 (16.41) | 5 (16.41) | Degree of protection | | IP66 | IP66 | IP66 | Dimensions | | | | | | mm (in) | 181 (7.13) | 181 (7.13) | 181 (7.13) | | mm (in) | 135 (5.31) | 135 (5.31) | 135 (5.31) | | mm (in) | 309 (12.17) | 309 (12.17) | 309 (12.17) | Frame size | | FSB | FSB | FSB | Weight, approx. | kg (lb) | 3.4 (7.50) | 3.4 (7.50) | 3.4 (7.50) |
1) The rated output current Irated is based on the duty cycle for high overload (HO). 2) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311. 3) The input current depends on the motor load and line impedance. The input currents apply for loading at rated power with a line impedance corresponding to uK = 1 %.
|
|