3) The input current depends on the motor load and line impedance. The input currents apply for loading at rated power with a line impedance corresponding to uK = 1 %.
Line voltage 380 … 480 V 3 AC
PM240M Power Modules
6SL3517-1BE16-3AM0
6SL3517-1BE17-7AM0
6SL3517-1BE21-0AM0
Rated output current Irated1)
A
5.6
7.3
8.8
Maximum output current Imax
A
11.2
14.6
14.1
Rated power
kW (hp)
2.2 (3)
3 (4)
4 (5)
Rated pulse frequency
kHz
4
4
4
Efficiency ?
%
97.6
97.6
97.7
Power loss 2)
At rated output current
kW
0.078
0.103
0.126
Cooling air requirement
m3/s (ft3/s)
0.024 (0.85)
0.024 (0.85)
0.024 (0.85)
Sound pressure level LpA (1 m)
dB
–
–
–
Rated input current 3)
A
5.3
6.9
8
Line supply connection U1/L1, V1/L2, W1/L3, PE
Conductor cross-section (recommended)
mm2
1 ... 2.5 18 ... 14 AWG
1 ... 2.5 18 ... 14 AWG
1 ... 2.5 18 ... 14 AWG
PE connection
(external connection)
Conductor cross-section (recommended)
mm2
10
10
10
Motor connection U2, V2, W2, PE, motor brake, temperature sensor
Conductor cross-section
mm2
1 ... 2.5 18 ... 14 AWG
1 ... 2.5 18 ... 14 AWG
1 ... 2.5 18 ... 14 AWG
Motor cable length, max.
Shielded
m (ft)
5 (16.41)
5 (16.41)
5 (16.41)
Degree of protection
IP66
IP66
IP66
Dimensions
Width
mm (in)
181 (7.13)
181 (7.13)
181 (7.13)
Height
mm (in)
135 (5.31)
135 (5.31)
135 (5.31)
Depth
mm (in)
309 (12.17)
309 (12.17)
309 (12.17)
Frame size
FSB
FSB
FSB
Weight, approx.
kg (lb)
3.4 (7.50)
3.4 (7.50)
3.4 (7.50)
1) The rated output current Irated is based on the duty cycle for high overload (HO).
3) The input current depends on the motor load and line impedance. The input currents apply for loading at rated power with a line impedance corresponding to uK = 1 %.