Suitable line-side power components are assigned depending on the power rating of the Basic Line Module. The tables below list recommended components. Additional information about the line-side power components can be found in Catalogs LV 10, IC 10 and IC 10 AO as well as the Industry Mall. Assignment of line-side power components to Basic Line Modules in booksize formatRated power | Suitable for Basic Line Module in booksize format | Line contactor | Output coupling device for line contactor | Main switch |
|---|
kW (hp) | Type 6SL3130... | Type | Article No. | Article No. |
|---|
Line voltage 380 ... 480 V 3 AC | 20 (25) | 1TE22-0AA0 | 3RT1035 | 3TX7004-1LB00 | 3LD2504-0TK51 | 40 (50) | 1TE24-0AA0 | 3RT1045 | 3TX7004-1LB00 | 3LD2704-0TK51 | 100 (125) | 1TE31-0AA0 | 3RT1056 | 3TX7004-1LB00 | 3KA5530-1GE01 |
Rated power | Suitable for Basic Line Module in booksize format | Circuit breaker IEC 60947 | Circuit breaker UL489/CSA C22.2 No. 5-02 | Fuse-switch disconnector |
|---|
kW (hp) | Type 6SL3130... | Article No. | Article No. | Article No. |
|---|
Line voltage 380 ... 480 V 3 AC | 20 (25) | 1TE22-0AA0 | 3RV1041-4JA10 | 3VL2506-2KN30-.... *) | 3NP1123-1CA20 | 40 (50) | 1TE24-0AA0 | 3VL2710-1DC33-.... *) | 3VL2510-2KN30-.... *) | 3NP1123-1CA20 | 100 (125) | 1TE31-0AA0 | 3VL3725-1DC36-.... *) | 3VL3125-2KN30-.... *) | 3NP1143-1DA20 |
Rated power | Suitable for Basic Line Module in booksize format | Switch disconnector with fuse holders | LV HRC fuse (gL/gG) | UL/CSA fuse, Class J 1) Available from: Mersen http://www.ep.mersen.com |
|---|
kW (hp) | Type 6SL3130... | Article No. | Rated current | Size | Article No. | Rated current | Size mm (in) | Reference No. |
|---|
Line voltage 380 ... 480 V 3 AC | 20 (25) | 1TE22-0AA0 | 3KL5230-1GB01 | 63 A | 000 | 3NA3822 | 60 A | 27 Г— 60 (1.06 Г— 2.36) | AJT60 | 40 (50) | 1TE24-0AA0 | 3KL5230-1GB01 | 100 A | 000 | 3NA3830 | 100 A | 29 Г— 117 (1.14 Г— 4.61) | AJT100 | 100 (125) | 1TE31-0AA0 | 3KL5730-1GB01 | 250 A | 1 | 3NA3144 | 250 A | 54 Г— 181 (2.13 Г— 7.13) | AJT250 |
1) Not suitable for 3NP and 3KL switch disconnectors. *) See Catalog LV 10 for Article No. supplements.
|