General technical specifications | SICROWBAR AC |
|---|
Degree of protection | IP00 acc. to EN 60529 | Protection class | I according to EN 50178 | Overvoltage category | III, corresponding to EN 60664 | Dimensioning creepages and clearances | Pollution degree 2 acc. to EN 50178 | Rated insulation voltage (for installation altitudes up to 2000 m above sea level) 1) | 725 V AC for rated supply voltages of 400 ... 725 V 1200 V AC for rated supply voltages of 850 ... 1150 V | Installation altitude | ≤ 2000 m above sea level | Permissible ambient temperature | | | +5 ... +55 °C | | -40 ... +70 °C | Climate class | 3K3 acc. to EN 60721-3-3 | Fuse monitoring (microswitch at the fused disconnector, 1 changeover contact) | Flat connector 6.3 mm Г— 0.8 mm | - Disconnector closed, all fuse links OK
| 1/2 closed, 1/4 opened | - Disconnector closed, one or several fuse links defective
| 1/4 closed, 1/2 opened | | 1/4 closed, 1/2 opened | - Maximum switching capacity
| 50 Hz 250 V AC, 3 A 30 V DC, 3 A |
1) Installation altitudes above 2000 m on request. | | SICROWBAR AC |
|---|
| | 7VV3002‑3CD20 | 7VV3002‑3AD20 | 7VV3002‑3BD20 | 7VV3002‑3GD20 |
|---|
Max. permissible rated supply voltage VN | V | 460 | | 550 | | Nominal response voltage of BOD element VAN | V | 1000 | 1200 | 1400 | 1600 | Min. limit voltage of BOD element at 5 °C VRRM_05 | V | 864 | 1056 | 1248 | 1440 | Max. limit voltage of BOD element at 55 °C VRRM_55 | V | 1166 | 1378 | 1590 | 1802 | Max. permissible peak current, Imax | A | 200 | 1000 | | 2000 | Rated insulation voltage (the insulation voltage is determined by the highest rated supply voltage of the relevant construction type) VISO | V | 550 | | | | Varistor voltage (breakdown voltage) at TA = 25 °C, 1 mA (data sheet value Г— 2 for 2 series-connected varistors) VV | V | 720 | | 860 | | Max. energy (for 2 ms) at TA = 85 °C (data sheet value Г— 2 for 2 series-connected varistors) W0 | Ws | 600 | | 720 | | Energy that can be absorbed 100 times (determined from the derating data) W2 | Ws | 350 | | 419 | | Energy that can be absorbed 10000 times (determined from the derating data) W4 | Ws | 42 | | 50 | | Version | | A | | | | Dimensions | | | | | | | mm | 265 | | | | | mm | 385 | | | | | mm | 237 | | | | Weight, approx. | kg | 7 | | | |
| | SICROWBAR AC |
|---|
| | 7VV3002‑3DD20 | 7VV3002‑3ED20 | 7VV3002‑3JD20 | 7VV3002‑3KD20 | 7VV3002‑3LD20 |
|---|
Max. permissible rated supply voltage VN | V | 770 | 920 | | 1100 | | Nominal response voltage of BOD element VAN | V | 1900 | 2400 | 2600 | 2800 | 3000 | Min. limit voltage of BOD element at 5 °C VRRM_05 | V | 1728 | 2208 | 2400 | 2592 | 2784 | Max. limit voltage of BOD element at 55 °C VRRM_55 | V | 2120 | 2650 | 2862 | 3074 | 3286 | Max. permissible peak current, Imax | A | 300 | 800 | 1000 | 400 | 1000 | Rated insulation voltage (the insulation voltage is determined by the highest rated supply voltage of the relevant construction type) VISO | V | 770 | 1100 | | | | Varistor voltage (breakdown voltage) at TA = 25 °C, 1 mA (data sheet value Г— 2 for 2 series-connected varistors) VV | V | 1240 | 1500 | | 1820 | | Max. energy (for 2 ms) at TA = 85 °C (data sheet value Г— 2 for 2 series-connected varistors) W0 | Ws | 2400 | 3300 | | 3000 | | Energy that can be absorbed 100 times (determined from the derating data) W2 | Ws | 986 | 1196 | | 1027 | | Energy that can be absorbed 10000 times (determined from the derating data) W4 | Ws | 145 | 176 | | 214 | | Version | | B | C | | | | Dimensions | | | | | | | | mm | 580 | | | | | | mm | 305 | | | | | | mm | 205 | 245 | | | | Weight, approx. | kg | 11 | 12 | | | |
|
|