Article number

6ES7671-1RC08-0YA0

SIMATIC WINAC RTX F 2010

General information

Product type designation

RTX F 2010

Firmware version

V4.6

Engineering with

  • Programming package

STEP 7 V5.5 or higher + S7 Distributed Safety V5.4 SP5 or higher + S7 F Configuration Pack V5.5 SP6 HF1 / iMap V3.0 SP1; STEP 7 in TIA Portal V13 or higher + STEP 7 Safety Advanced V13

Memory

Type of memory

RAM

Work memory

  • integrated (for program)

4Mbyte; Adjustable; depends on Non Paged Memory Pool

  • integrated (for data)

4Mbyte; Adjustable; depends on Non Paged Memory Pool

Load memory

  • integrated RAM, max.

Adjustable; depends on Non Paged Memory Pool

CPU processing times

for bit operations, typ.

0.004s; Typical

for fixed point arithmetic, typ.

0.003s; Typical

for floating point arithmetic, typ.

0.004s; Typical

Reference platform

Pentium 4, 2.4 GHz

CPU-blocks

DB

  • Number, max.

65535; Limited only by RAM set for data

  • Size, max.

64kbyte

FB

  • Number, max.

65536; Limited only by RAM set for code

  • Size, max.

64kbyte

FC

  • Number, max.

65536; Limited only by RAM set for code

  • Size, max.

64kbyte

OB

  • Number, max.

Limited only by RAM set for code

  • Size, max.

64kbyte

  • Number of free cycle OBs

1; OB 1

  • Number of time alarm OBs

1; OB 10

  • Number of delay alarm OBs

1; OB 20

  • Number of cyclic interrupt OBs

9; OB 30-38

  • Number of process alarm OBs

1; OB 40

  • Number of ODK OBs

3; OB 52-54

  • Number of DPV1 alarm OBs

3; OB 55-57

  • Number of isochronous mode OBs

2; OB 61-62

  • Number of startup OBs

2; OB 100, 102

  • Number of asynchronous error OBs

7; OB 80, 82-85, 86, 88

  • Number of synchronous error OBs

2; OB 121, 122

Nesting depth

  • per priority class

24

  • additional within an error OB

24

Counters, timers and their retentivity

S7 counter

  • Number

2048

Retentivity

  • adjustable

Yes

  • lower limit

0

  • upper limit

2047

  • preset

8

Counting range

  • can be set

Yes

  • lower limit

0

  • upper limit

999

IEC counter

  • Number

Unlimited (limited only by RAM capacity)

S7 times

  • Number

2048

Retentivity

  • adjustable

Yes

  • lower limit

0

  • upper limit

2047

  • preset

0

Time range

  • lower limit

10ms

  • upper limit

9990s

IEC timer

  • present

Yes

  • Type

SFB

  • Number

Unlimited (limited only by RAM capacity)

Data areas and their retentivity

Retentivity without UPS and PS Extension Board

128 kbyte with SIMATIC IPC427C and HMI IPC477C; further SIMATIC PCs on request

Retentivity with UPS

all data

Flag

  • Number, max.

16kbyte

  • of which retentive

MB 0 to MB 16383

  • Retentivity preset

MB 0 to MB 15

  • Number of clock memories

8

Data blocks

  • Retentivity adjustable

Yes; via non-retain property on DB

  • Retentivity preset

Yes

Local data

  • adjustable, max.

64kbyte

  • preset

32kbyte

  • per priority class, max.

61440byte

Address area

I/O address area

  • Inputs

16kbyte

  • Outputs

16kbyte

of which distributed

  • DP interface, inputs

16kbyte

  • DP interface, outputs

16kbyte

  • PROFINET interface, inputs

16kbyte

  • PROFINET interface, outputs

16kbyte

Process image

  • Inputs, adjustable

8kbyte

  • Outputs, adjustable

8kbyte

  • Inputs, default

512byte

  • Outputs, default

512byte

Subprocess images

  • Number of subprocess images, max.

15

Digital channels

  • Inputs

128000

  • Outputs

128000

Analog channels

  • Inputs

8000

  • Outputs

8000

Number of operable FMs and CPs (recommended)

  • FM

4; FM distributed: FM 350-1, FM 350-2, FM 351, FM 352 / FM 352-5, FM 353, FM 354, FM 355, FM 355-2

  • CP, PtP

2; CP 340, CP 341 distributed

  • CP, LAN

Over PC CP

Submodules

  • Number of submodules, max

4

  • of which PROFIBUS, max.

4; Supported interfaces: see 1st and 2nd interface

  • of which Industrial Ethernet, max.

1; Supported interfaces: see 3rd and 4th interface

Time of day

Clock

  • Hardware clock (real-time)

Yes

  • retentive and synchronizable

Yes

Operating hours counter

  • Number

8

Clock synchronization

  • supported

Yes

  • to PC-CP, slave

Yes

  • on Ethernet via NTP

Yes

1. Interface

Interface type

CP 5611-A2, CP 5621, integrated PROFIBUS interface of the SIMATIC PC

Physics

RS 485 / PROFIBUS

Isolated

Yes

Number of simultaneously operable CPs, max.

1

Power supply to interface (15 to 30 V DC), max.

does not exist

Functionality

  • MPI

No

  • PROFIBUS DP master

Yes

  • PROFIBUS DP slave

No

DP master

  • Number of connections, max.

8

  • Transmission rate, max.

12Mbit/s

  • Number of DP slaves, max.

64

Services

  • PG/OP communication

Yes

  • Routing

Yes

  • Global data communication

No

  • S7 basic communication

No

  • S7 communication

Yes

  • S7 communication, as client

Yes

  • S7 communication, as server

Yes

  • Equidistance

Yes; Only in conjunction with isochronous mode

  • Isochronous mode

Yes

  • SYNC/FREEZE

Yes

  • Activation/deactivation of DP slaves

Yes

  • Direct data exchange (slave-to-slave communication)

Yes

  • DPV0

Yes

  • DPV1

Yes

Address area

  • Inputs, max.

16kbyte

  • Outputs, max.

16kbyte

User data per DP slave

  • Inputs, max.

244byte

  • Outputs, max.

244byte

2. Interface

Interface type

CP 5613, CP 5613-A2, CP 5603, CP 5623

Physics

RS 485 / PROFIBUS

Isolated

Yes

Number of simultaneously operable CPs, max.

4

Functionality

  • MPI

No

  • PROFIBUS DP master

Yes

  • PROFIBUS DP slave

No

DP master

  • Number of connections, max.

50

  • Transmission rate, max.

12Mbit/s

  • Number of DP slaves, max.

125

Services

  • PG/OP communication

Yes

  • Routing

Yes

  • Global data communication

No

  • S7 basic communication

No

  • S7 communication

Yes

  • S7 communication, as client

Yes

  • S7 communication, as server

Yes

  • Equidistance

Yes; Only in conjunction with isochronous mode

  • Isochronous mode

Yes

  • SYNC/FREEZE

Yes

  • Activation/deactivation of DP slaves

Yes

  • Direct data exchange (slave-to-slave communication)

Yes

  • DPV0

Yes

  • DPV1

Yes

Address area

  • Inputs, max.

16kbyte

  • Outputs, max.

16kbyte

User data per DP slave

  • Inputs, max.

244byte

  • Outputs, max.

244byte

3. Interface

Interface type

PROFINET

Physics

Ethernet

Isolated

Yes

Number of simultaneously operable CPs, max.

1; Intel Pro/1000 (Intel 82571EB, 82573L, 82574L, 82541PI; non-shared IRQ required); integrated IE interface SIMATIC PC 4x7B, 6x7B, 8x7B, IPC4x7C, IPC6x7C, IPC8x7C

automatic detection of transmission rate

Yes; 10/100 Mbit/s

Autonegotiation

Yes

Autocrossing

Yes

Interface types

  • Number of ports

1

  • integrated switch

No

Media redundancy

  • supported

No

Functionality

  • PROFINET IO Controller

Yes

  • PROFINET IO Device

No

  • PROFINET CBA

Yes

  • Open IE communication

Yes

PROFINET IO Controller

  • Transmission rate, max.

100Mbit/s

Services

  • PG/OP communication

Yes

  • S7 routing

Yes

  • S7 communication

Yes

  • Isochronous mode

No

  • Open IE communication

Yes

  • IRT

No

  • Prioritized startup

Yes

  • Number of IO devices with prioritized startup, max.

32

  • Number of connectable IO Devices, max.

128

  • Number of connectable IO Devices for RT, max.

128

  • of which in line, max.

128

  • Activation/deactivation of IO Devices

Yes

  • Number of IO Devices that can be simultaneously activated/deactivated, max.

8

  • IO Devices changing during operation (partner ports), supported

Yes

  • Device replacement without swap medium

Yes

  • Send cycles

1 ms

  • Updating time

1 to 512 ms (minimum value depends on communication share set for PROFINET I/O, on the number of I/O devices, and on the volume of configured user data)

Address area

  • Inputs, max.

16kbyte

  • Outputs, max.

16kbyte

  • User data per address area, max.

2kbyte

  • User data consistency, max.

254byte

PROFINET CBA

  • acyclic transmission

Yes

  • cyclic transmission

Yes

Open IE communication

  • Number of connections, max.

32

  • Local port numbers used at the system end

0, 20, 21, 23, 25, 80, 102, 135, 161, 8080, 34962, 34963, 34964, 65532, 65533, 65534, 65535

  • Keep-alive function, supported

Yes

SIMATIC communication

  • Number of connections, max.

16

4. Interface

Interface type

PROFINET

Physics

Ethernet

Isolated

Yes

Number of simultaneously operable CPs, max.

1; CP 1616 (HW release 8 or above), CP 1604 (HW release 7 or higher), integrated PROFINET interface of SIMATIC PC and S7-mEC

automatic detection of transmission rate

Yes; 10/100 Mbit/s

Autonegotiation

Yes

Autocrossing

Yes

Change of IP address at runtime, supported

Yes

Interface types

  • Number of ports

3

  • integrated switch

Yes

Media redundancy

  • supported

Yes

  • Switchover time on line break, typ.

200ms

  • Number of stations in the ring, max.

50

Functionality

  • PROFINET IO Controller

Yes

  • PROFINET IO Device

No

  • PROFINET CBA

Yes

  • Open IE communication

Yes

  • Web server

Yes

PROFINET IO Controller

  • Transmission rate, max.

100Mbit/s

Services

  • PG/OP communication

Yes

  • S7 routing

Yes

  • S7 communication

Yes

  • Isochronous mode

Yes

  • Open IE communication

Yes

  • IRT

Yes

  • Prioritized startup

Yes

  • Number of IO devices with prioritized startup, max.

32

  • Number of connectable IO Devices, max.

256

  • Of which IO devices with IRT, max.

64

  • of which in line, max.

64

  • Number of IO Devices with IRT and the option "high flexibility"

64

  • of which in line, max.

32

  • Number of connectable IO Devices for RT, max.

256

  • of which in line, max.

256

  • Activation/deactivation of IO Devices

Yes

  • Number of IO Devices that can be simultaneously activated/deactivated, max.

8

  • IO Devices changing during operation (partner ports), supported

Yes

  • Device replacement without swap medium

Yes

  • Send cycles

250 s, 500 s, 1 ms

Address area

  • User data per address area, max.

2kbyte

Open IE communication

  • Local port numbers used at the system end

0, 20, 21, 25, 80, 102, 135, 161, 34962, 34963, 34964, 65532, 65533, 65534, 65535

SIMATIC communication

  • Number of connections, max.

32

Protocols

Open IE communication

  • TCP/IP

Yes

  • Data length for connection type 01H, max.

Not supported

  • Data length for connection type 11H, max.

65534byte

  • Data length, max.

65534byte

  • ISO-on-TCP (RFC1006)

Yes

  • Data length, max.

65534byte

  • UDP

Yes

  • Data length, max.

1472byte

Web server

  • User-defined websites

No

  • Number of HTTP clients

2

Isochronous mode

Isochronous operation (application synchronized up to terminal)

Yes

Equidistance

Yes

Number of DP masters with isochronous mode

2

User data per isochronous slave, max.

128byte

shortest clock pulse

2.2ms; 2.2 ms without partial process image; 2.2 ms with partial process image

Communication functions

PG/OP communication

Yes

Data record routing

Yes; only with CP 5611 or integrated PROFIBUS interface of the SIMATIC PC

Global data communication

  • supported

No

S7 basic communication

  • supported

No

S7 communication

  • supported

Yes

  • as server

Yes

  • as client

Yes

  • User data per job, max.

64kbyte; Depends on which block is used: BSEND/USEND or PUT/GET

Web server

  • supported

Yes

PROFINET CBA (at set setpoint communication load)

  • Setpoint for the CPU communication load

20%

  • Number of remote interconnection partners

64

  • Number of functions, master/slave

30

  • Total of all master/slave connections

1000

  • Data length of all incoming connections master/slave, max.

6800byte

  • Data length of all outgoing connections master/slave, max.

6800byte

  • Number of device-internal and PROFIBUS interconnections

500

  • Data length of device-internal und PROFIBUS interconnections, max.

4000byte

  • Data length per connection, max.

1400byte

Remote interconnections with acyclic transmission

  • Sampling frequency: Sampling time, min.

500ms

  • Number of incoming interconnections

100

  • Number of outgoing interconnections

100

  • Data length of all incoming interconnections, max.

2000byte

  • Data length of all outgoing interconnections, max.

2000byte

  • Data length per connection, max.

1400byte

Remote interconnections with cyclic transmission

  • Transmission frequency: Transmission interval, min.

10ms

  • Number of incoming interconnections

200

  • Number of outgoing interconnections

200

  • Data length of all incoming interconnections, max.

4800byte

  • Data length of all outgoing interconnections, max.

4800byte

  • Data length per connection, max.

250byte

HMI variables via PROFINET (acyclic)

  • Number of stations that can log on for HMI variables (PN OPC/iMap)

3

  • HMI variable updating

500ms

  • Number of HMI variables

200

  • Data length of all HMI variables, max.

2000byte

PROFIBUS proxy functionality

  • supported

Yes

  • Number of linked PROFIBUS devices

16

  • Data length per connection, max.

240byte; Slave-dependent

Number of connections

  • overall

96

  • usable for PG communication

  • reserved for PG communication

1

  • usable for OP communication

  • reserved for OP communication

1

S7 message functions

Number of login stations for message functions, max.

62

SCAN procedure

No

Process diagnostic messages

Yes; ALARM_S, ALARM_SQ, ALARM_D, ALARM_DQ

simultaneously active Alarm-S blocks, max.

20; of a total of 20 for all SFCs

Alarm 8-blocks

Yes

  • Number of instances for alarm 8 and S7 communication blocks, max.

4000

Process control messages

No

Test commissioning functions

Status block

Yes

Single step

Yes

Number of breakpoints

20

Status/control

  • Status/control variable

Yes

Forcing

  • Forcing

No

Diagnostic buffer

  • present

Yes

  • Number of entries, max.

  • adjustable

Yes

  • preset

120

Hardware requirement

Hardware required

PC with color monitor, keyboard, mouse or pointing device for Windows

Processor

  • Processor

Intel Celeron M 900 MHz or compatible (older PC systems with Programmable Interrupt Controllers (PIC) are not suitable for WinAC RTX F 2010.)

  • Multi-processor system

No

  • Hyper-threading

Yes

Lifetime of module

  • Main memory, min.

1Gbyte

  • Required memory on hard disk

100Mbyte

Operating systems

pre-installed operating system

  • Windows NT 4.0

No

  • Windows 2000

No

  • Windows Vista

No

  • Windows XP

Yes; Professional, SP2 and SP3

  • Windows XP Embedded

Yes; With the delivery image of the SIMATIC PC

  • supported HAL types under Windows XP

ACPI uniprocessor PC, ACPI multiprocessor PC, MPS multiprocessor PC

  • Windows 7

Yes; Professional, Enterprise, Ultimate (only 32 bits)

  • Windows Embedded Standard 7

No

Configuration

Configuration software

  • STEP 7

Yes; As of V5.5 + HW update/S7 F Configuration Pack V5.5 + SP6 + HF1/option package S7 Distributed Safety V5.4 + SP5 or later

Programming

  • Nesting levels

8

Programming language

  • LAD

Yes

  • FBD

Yes

  • STL

Yes

  • SCL

Yes

  • CFC

Yes

  • GRAPH

Yes

  • HiGraph

Yes

Software libraries

  • Easy Motion Control

Yes

  • Software redundancy

Yes; As of V1.2, only for operation of WinAC RTX (F) with WinAC RTX (F)

Number of simultaneously active SFCs

  • DPSYC_FR

20; of a total of 20 for all SFCs

  • D_ACT_DP

20; of a total of 20 for all SFCs

  • RD_REC

20; of a total of 20 for all SFCs

  • WR_REC

20; of a total of 20 for all SFCs

  • WR_PARM

20; of a total of 20 for all SFCs

  • PARM_MOD

20; of a total of 20 for all SFCs

  • WR_DPARM

20; of a total of 20 for all SFCs

  • DPNRM_DG

20; of a total of 20 for all SFCs

  • RDSYSST

20; of a total of 20 for all SFCs

Number of simultaneously active SFBs

  • RDREC

20; of a total of 20 for all SFBs

  • WRREC

20; of a total of 20 for all SFBs

Know-how protection

  • User program protection/password protection

Yes

  • Block encryption

No

Open Development interfaces

  • CCX (Custom Code Extension)

Yes; WinAC ODK V4.2 or higher

  • CMI (Controller Management Interface)

Yes; WinAC ODK V4.2 or higher

  • SMX (Shared Memory Extension)

Yes; WinAC ODK V4.2 or higher

  • Inputs

4kbyte

  • Outputs

4kbyte

Weights

Weight, approx.

100g; With packaging


















skener.ru

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
DENDOR

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FS -

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FK -

  © " " 2007-2022
  (4872) 700-366  skenergo@mail.ru
.