Siemens
ÑÐÅÄÑÒÂÀ ÏÐÎÌÛØËÅÍÍÎÉ ÀÂÒÎÌÀÒÈÇÀÖÈÈ
îôèöèàëüíûé ïàðòíåð Ñèìåíñ
Êàòàëîã ÑÀ01 2018
(4872) 700-366
skenergo@mail.ru

Line voltage 380 ... 480 V 3 AC

DC link voltage 510 ... 720 V DC

Motor Modules in chassis format

 

6SL3720-1TE32-1AA3

6SL3720-1TE32-6AA3

6SL3720-1TE33-1AA3

6SL3720-1TE33-8AA3

6SL3720-1TE35-0AA3

6SL3720-1TE36-1AA3

Type rating

 

 

 

 

 

 

 

  • At IL (50 Hz 400 V) 1)

kW

110

132

160

200

250

315

  • At IH (50 Hz 400 V) 1)

kW

90

110

132

160

200

250

  • At IL (60 Hz 460 V) 2)

hp

150

200

250

300

400

500

  • At IH (60 Hz 460 V) 2)

hp

150

200

200

250

350

350

Output current

 

 

 

 

 

 

 

  • Rated current Irated O

A

210

260

310

380

490

605

  • Base-load current IL3)

A

205

250

302

370

477

590

  • Base-load current IH4)

A

178

233

277

340

438

460

  • Maximum current Imax O

A

307

375

453

555

715

885

DC link current

 

 

 

 

 

 

 

  • Rated current Irated DC
    when supplied via

 

 

 

 

 

 

 

  • Basic/Smart Line Module

A

252

312

372

456

588

726

  • Active Line Module

A

227

281

335

411

529

653

  • Base-load current IL DC 3)
    when supplied via

 

 

 

 

 

 

 

  • Basic/Smart Line Module

A

245

304

362

444

573

707

  • Active Line Module

A

221

273

326

400

515

636

  • Base-load current IH DC 4)
    when supplied via

 

 

 

 

 

 

 

  • Basic/Smart Line Module

A

224

277

331

405

523

646

  • Active Line Module

A

202

250

298

365

470

581

Current demand

 

 

 

 

 

 

 

  • 24 V DC auxiliary power supply

A

0.8

0.8

0.9

0.9

0.9

1.0

  • 400 V AC

A

0.63

1.13

1.8

1.8

1.8

3.6

DC link capacitance

μF

4200

5200

6300

7800

9600

12600

Pulse frequency 5)

 

 

 

 

 

 

 

  • Rated frequency

kHz

2

2

2

2

2

1.25

  • Pulse frequency, max.
       
  • Without current derating

kHz

2

2

2

2

2

1.25

  • With current derating

kHz

8

8

8

8

8

7.5

Power loss, max. 6)

 

 

 

 

 

 

 

  • At 50 Hz 400 V

kW

1.86

2.5

2.96

3.67

4.28

5.84

  • At 60 Hz 460 V

kW

1.94

2.6

3.1

3.8

4.5

6.3

Cooling air requirement

m3/s

0.17

0.23

0.36

0.36

0.36

0.78

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

67

69

69

69

69

72

Motor connection

U2, V2, W2

 

M12 screws

M12 screws

M12 screws

M12 screws

M12 screws

M12 screws

  • Conductor cross section, max. (IEC)

mm2

2 Ã— 185

2 Ã— 185

2 Ã— 240

2 Ã— 240

2 Ã— 240

4 Ã— 240

Cable length, max. 7)

 

 

 

 

 

 

 

  • Shielded

m

300

300

300

300

300

300

  • Unshielded

m

450

450

450

450

450

450

PE/GND connection

 

PE bar

PE bar

PE bar

PE bar

PE bar

PE bar

  • Busbar cross-section

mm2

600

600

600

600

600

600

  • Conductor cross section, max. (IEC)

mm2

240

240

240

240

240

240

Degree of protection

 

IP20

IP20

IP20

IP20

IP20

IP20

Dimensions

 

 

 

 

 

 

 

  • Width 8)

mm

400

400

400

400

400

600

  • Height 9)

mm

2200

2200

2200

2200

2200

2200

  • Depth

mm

600

600

600

600

600

600

Weight, approx.

kg

145

145

286

286

286

490

Frame size

 

FX

FX

GX

GX

GX

HX

Short-circuit current rating according to IEC

kA

65

65

65

65

65

65



1) Rated output of a typical 6-pole standard induction motor based on IL or IH for 400 V 3 AC 50 Hz.

2) Rated output of a typical 6-pole standard induction motor based on IL or IH for 460 V 3 AC 60 Hz.

3) The base-load current IL is based on a load cycle of 110 % for 60 s or 150 % for 10 s with a load cycle duration of 300 s.

4) The base-load current IH is based on a duty cycle of 150 % for 60 s or 160 % for 10 s with a duty cycle duration of 300 s.

5)Information regarding the correlation between the pulse frequency and max. output current/output frequency is provided in the SINAMICS Low Voltage Engineering Manual.

6) The specified power loss represents the maximum value at 100% utilization. The value is lower under normal operating conditions.

7) Total of all motor cables. Longer cable lengths for specific configurations are available on request. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.

8) With option L10 (dv/dt filter plus VPL):- Frame sizes FX/GX/HX/JX: Additional cabinet 600 mm wide

With option L34 (circuit breaker on the output side):- Frame size FX/GX: Additional cabinet 400 mm wide

- Frame size HX/JX: Additional cabinet 600 mm wide.

9) The cabinet height increases by 250 mm with degree of protection IP21, and by 400 mm with degrees of protection IP23, IP43 and IP54.

 

Line voltage 380 ... 480 V 3 AC

DC link voltage 510 ... 720 V DC

Motor Modules in chassis format

 

6SL3720-1TE37-5AA3

6SL3720-1TE38-4AA3

6SL3720-1TE41-0AA3

6SL3720-1TE41-2AA3

6SL3720-1TE41-4AA3

Type rating

 

 

 

 

 

 

  • At IL (50 Hz 400 V) 1)

kW

400

450

560

710

800

  • At IH (50 Hz 400 V) 1)

kW

315

400

450

560

710

  • At IL (60 Hz 460 V) 2)

hp

600

700

800

1000

1150

  • At IH (60 Hz 460 V) 2)

hp

450

600

700

900

1000

Output current

 

 

 

 

 

 

  • Rated current Irated O

A

745

840

985

1260

1405

  • Base-load current IL3)

A

725

820

960

1230

1370

  • Base-load current IH4)

A

570

700

860

1127

1257

  • Maximum current Imax O

A

1087

1230

1440

1845

2055

DC link current

 

 

 

 

 

 

  • Rated current Irated DC
    when supplied via

 

 

 

 

 

 

  • Basic/Smart Line Module

A

894

1008

1182

1512

1686

  • Active Line Module

A

805

907

1064

1361

1517

  • Base-load current IL DC 3)
    when supplied via

 

 

 

 

 

 

  • Basic/Smart Line Module

A

871

982

1152

1474

1643

  • Active Line Module

A

784

884

1037

1326

1479

  • Base-load current IH DC 4)
    when supplied via

 

 

 

 

 

 

  • Basic/Smart Line Module

A

795

897

1051

1345

1500

  • Active Line Module

A

716

807

946

1211

1350

Current demand

 

 

 

 

 

 

  • 24 V DC auxiliary power supply

A

1.0

1.0

1.25

1.4

1.4

  • 400 V AC

A

3.6

3.6

5.4

5.4

5.4

DC link capacitance

μF

15600

16800

18900

26100

28800

Pulse frequency 5)

 

 

 

 

 

 

  • Rated frequency

kHz

1.25

1.25

1.25

1.25

1.25

  • Pulse frequency, max.

 

 

 

 

 

 

  • Without current derating

kHz

1.25

1.25

1.25

1.25

1.25

  • With current derating

kHz

7.5

7.5

7.5

7.5

7.5

Power loss, max. 6)

 

 

 

 

 

 

  • At 50 Hz 400 V

kW

6.68

7.15

9.5

11.1

12.0

  • At 60 Hz 460 V

kW

7.3

7.8

10.2

12.0

13.0

Cooling air requirement

m3/s

0.78

0.78

1.08

1.08

1.08

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

72

72

72

72

72

Motor connection

U2, V2, W2

 

M12 screws

M12 screws

M12 screws

M12 screws

M12 screws

  • Conductor cross section, max. (IEC)

mm2

4 Ã— 240

4 Ã— 240

6 Ã— 240

6 Ã— 240

6 Ã— 240

Cable length, max. 7)

 

 

 

 

 

 

  • Shielded

m

300

300

300

300

300

  • Unshielded

m

450

450

450

450

450

PE/GND connection

 

PE bar

PE bar

PE bar

PE bar

PE bar

  • Busbar cross-section

mm2

600

600

600

600

600

  • Conductor cross section, max. (IEC)

mm2

240

240

240

240

240

Degree of protection

 

IP20

IP20

IP20

IP20

IP20

Dimensions

 

 

 

 

 

 

  • Width 8)

mm

600

600

800

800

800

  • Height 9)

mm

2200

2200

2200

2200

2200

  • Depth

mm

600

600

600

600

600

Weight, approx.

kg

490

490

700

700

700

Frame size

 

HX

HX

JX

JX

JX

Short-circuit current rating according to IEC

kA

65

84

84

100

100



1) Rated output of a typical 6-pole standard induction motor based on IL or IH for 400 V 3 AC 50 Hz.

2) Rated output of a typical 6-pole standard induction motor based on IL or IH for 460 V 3 AC 60 Hz.

3) The base-load current IL is based on a load cycle of 110 % for 60 s or 150 % for 10 s with a load cycle duration of 300 s.

4) The base-load current IH is based on a duty cycle of 150 % for 60 s or 160 % for 10 s with a duty cycle duration of 300 s.

5)Information regarding the correlation between the pulse frequency and max. output current/output frequency is provided in the SINAMICS Low Voltage Engineering Manual.

6) The specified power loss represents the maximum value at 100% utilization. The value is lower under normal operating conditions.

7) Total of all motor cables. Longer cable lengths for specific configurations are available on request. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.

8) With option L10 (dv/dt filter plus VPL):- Frame sizes FX/GX/HX/JX: Additional cabinet 600 mm wide

With option L34 (circuit breaker on the output side):- Frame size FX/GX: Additional cabinet 400 mm wide

- Frame size HX/JX: Additional cabinet 600 mm wide.

9) The cabinet height increases by 250 mm with degree of protection IP21, and by 400 mm with degrees of protection IP23, IP43 and IP54.

 

Line voltage 500 ... 690 V 3 AC

DC link voltage 675 â€¦ 1035 V DC

Motor Modules in chassis format

 

6SL3720-1TG28-5AA3

6SL3720-1TG31-0AA3

6SL3720-1TG31-2AA3

6SL3720-1TG31-5AA3

6SL3720-1TG31-8AA3

6SL3720-1TG32-2AA3

Type rating

 

 

 

 

 

 

 

  • At IL (50 Hz 690 V) 1)

kW

75

90

110

132

160

200

  • At IH (50 Hz 690 V) 1)

kW

55

75

90

110

132

160

  • At IL (50 Hz 500 V) 1)

kW

55

55

75

90

110

132

  • At IH (50 Hz 500 V) 1)

kW

45

55

75

90

90

110

  • At IL (60 Hz 575 V) 2)

hp

75

75

100

150

150

200

  • At IH (60 Hz 575 V) 2)

hp

75

75

100

125

150

200

Output current

 

 

 

 

 

 

 

  • Rated current Irated O

A

85

100

120

150

175

215

  • Base-load current IL3)

A

80

95

115

142

170

208

  • Base-load current IH4)

A

76

89

107

134

157

192

  • Maximum current Imax O

A

120

142

172

213

255

312

DC link current

 

 

 

 

 

 

 

  • Rated current Irated DC
    when supplied via

 

 

 

 

 

 

 

  • Basic/Smart Line Module

A

102

120

144

180

210

258

  • Active Line Module

A

92

108

130

162

189

232

  • Base-load current IL DC 3)
    when supplied via

 

      
  • Basic/Smart Line Module

A

99

117

140

175

204

251

  • Active Line Module

A

89

105

126

157

184

226

  • Base-load current IH DC 4)
    when supplied via

 

 

 

 

 

 

 

  • Basic/Smart Line Module

A

90

106

128

160

186

229

  • Active Line Module

A

81

96

115

144

168

206

Current demand

 

 

 

 

 

 

 

  • 24 V DC auxiliary power supply

A

0.8

0.8

0.8

0.8

0.9

0.9

  • 690 V AC

A

0.4

0.4

0.4

0.4

1.0

1.0

DC link capacitance

μF

1200

1200

1600

2800

2800

2800

Pulse frequency 5)

 

 

 

 

 

 

 

  • Rated frequency

kHz

1.25

1.25

1.25

1.25

1.25

1.25

  • Pulse frequency, max.

 

 

 

 

 

 

 

  • Without current derating

kHz

1.25

1.25

1.25

1.25

1.25

1.25

  • With current derating

kHz

7.5

7.5

7.5

7.5

7.5

7.5

Power loss, max. 6)

 

 

 

 

 

 

 

  • At 50 Hz 690 V

kW

1.17

1.43

1.89

1.8

2.67

3.09

  • At 60 Hz 575 V

kW

1.1

1.3

1.77

1.62

2.5

2.91

Cooling air requirement

m3/s

0.17

0.17

0.17

0.17

0.36

0.36

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

67

67

67

67

69

69

Motor connection

U2, V2, W2

 

M12 screws

M12 screws

M12 screws

M12 screws

M12 screws

M12 screws

  • Conductor cross section, max. (IEC)

mm2

2 Ã— 185

2 Ã— 185

2 Ã— 185

2 Ã— 185

2 Ã— 240

2 Ã— 240

Cable length, max. 7)

 

 

 

 

 

 

 

  • Shielded

m

300

300

300

300

300

300

  • Unshielded

m

450

450

450

450

450

450

PE/GND connection

 

PE bar

PE bar

PE bar

PE bar

PE bar

PE bar

  • Busbar cross-section

mm2

600

600

600

600

600

600

  • Conductor cross section, max. (IEC)

mm2

240

240

240

240

240

240

Degree of protection

 

IP20

IP20

IP20

IP20

IP20

IP20

Dimensions

 

 

 

 

 

 

 

  • Width 8)

mm

400

400

400

400

400

400

  • Height 9)

mm

2200

2200

2200

2200

2200

2200

  • Depth

mm

600

600

600

600

600

600

Weight, approx.

kg

145

145

145

145

286

286

Frame size

 

FX

FX

FX

FX

GX

GX

Short-circuit current rating according to IEC

kA

65

65

65

65

65

65



1) Rated output of a typical 6-pole standard induction motor based on IL or IH for 500 V or 690 V 3 AC 50 Hz. 

2) Rated output of a typical 6-pole standard induction motor based on IL or IH for 575 V 3 AC 60 Hz.

3) The base-load current IL is based on a load cycle of 110 % for 60 s or 150 % for 10 s with a load cycle duration of 300 s.

4) The base-load current IH is based on a duty cycle of 150 % for 60 s or 160 % for 10 s with a duty cycle duration of 300 s.

5)Information regarding the correlation between the pulse frequency and max. output current/output frequency is provided in the SINAMICS Low Voltage Engineering Manual.

6) The specified power loss represents the maximum value at 100% utilization. The value is lower under normal operating conditions.

7) Total of all motor cables. Longer cable lengths for specific configurations are available on request. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.

8) With option L10 (dv/dt filter plus VPL):- Frame sizes FX/GX/HX/JX: Additional cabinet 600 mm wide

With option L34 (circuit breaker on the output side):- Frame size FX/GX: Additional cabinet 400 mm wide

- Frame size HX/JX: Additional cabinet 600 mm wide.

9) The cabinet height increases by 250 mm with degree of protection IP21, and by 400 mm with degrees of protection IP23, IP43 and IP54.

 

Line voltage 500 ... 690 V 3 AC

DC link voltage 675 â€¦ 1035 V DC

Motor Modules in chassis format

 

6SL3720-1TG32-6AA3

6SL3720-1TG33-3AA3

6SL3720-1TG34-1AA3

6SL3720-1TG34-7AA3

6SL3720-1TG35-8AA3

6SL3720-1TG37-4AA3

Type rating

 

 

 

 

 

 

 

  • At IL (50 Hz 690 V) 1)

kW

250

315

400

450

560

710

  • At IH (50 Hz 690 V) 1)

kW

200

250

315

400

450

630

  • At IL (50 Hz 500 V) 1)

kW

160

200

250

315

400

500

  • At IH (50 Hz 500 V) 1)

kW

132

160

200

250

315

450

  • At IL (60 Hz 575 V) 2)

hp

250

300

400

450

600

700

  • At IH (60 Hz 575 V) 2)

hp

200

250

350

450

500

700

Output current

 

 

 

 

 

 

 

  • Rated current Irated O

A

260

330

410

465

575

735

  • Base-load current IL3)

A

250

320

400

452

560

710

  • Base-load current IH4)

A

233

280

367

416

514

657

  • Maximum current Imax O

A

375

480

600

678

840

1065

DC link current

 

 

 

 

 

 

 

  • Rated current Irated DC
    when supplied via

 

 

 

 

 

 

 

  • Basic/Smart Line Module

A

312

396

492

558

690

882

  • Active Line Module

A

281

356

443

502

621

794

  • Base-load current IL DC 3)
    when supplied via

 

 

 

 

 

 

 

  • Basic/Smart Line Module

A

304

386

479

544

672

859

  • Active Line Module

A

273

347

431

489

605

774

  • Base-load current IH DC 4)
    when supplied via

 

 

 

 

 

 

 

  • Basic/Smart Line Module

A

277

352

437

496

614

784

  • Active Line Module

A

250

316

394

446

552

706

Current demand

 

 

 

 

 

 

 

  • 24 V DC auxiliary power supply

A

0.9

0.9

1.0

1.0

1.0

1.25

  • 690 V AC

A

1.0

1.0

2.1

2.1

2.1

3.1

DC link capacitance

μF

3900

4200

7400

7400

7400

11100

Pulse frequency 5)

 

 

 

 

 

 

 

  • Rated frequency

kHz

1.25

1.25

1.25

1.25

1.25

1.25

  • Pulse frequency, max.

 

 

 

 

 

 

 

  • Without current derating

kHz

1.25

1.25

1.25

1.25

1.25

1.25

  • With current derating

kHz

7.5

7.5

7.5

7.5

7.5

7.5

Power loss, max. 6)

 

 

 

 

 

 

 

  • At 50 Hz 690 V

kW

3.62

4.34

6.13

6.8

10.3

10.9

  • At 60 Hz 575 V

kW

3.38

3.98

5.71

6.32

9.7

10.0

Cooling air requirement

m3/s

0.36

0.36

0.78

0.78

0.78

1.08

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

69

69

72

72

72

72

Motor connection

U2, V2, W2

 

M12 screws

M12 screws

M12 screws

M12 screws

M12 screws

M12 screws

  • Conductor cross section, max. (IEC)

mm2

2 Ã— 240

2 Ã— 240

4 Ã— 240

4 Ã— 240

4 Ã— 240

6 Ã— 240

Cable length, max. 7)

 

 

 

 

 

 

 

  • Shielded

m

300

300

300

300

300

300

  • Unshielded

m

450

450

450

450

450

450

PE/GND connection

 

PE bar

PE bar

PE bar

PE bar

PE bar

PE bar

  • Busbar cross-section

mm2

600

600

600

600

600

600

  • Conductor cross section, max. (IEC)

mm2

240

240

240

240

240

240

Degree of protection

 

IP20

IP20

IP20

IP20

IP20

IP20

Dimensions

 

 

 

 

 

 

 

  • Width 8)

mm

400

400

600

600

600

800

  • Height 9)

mm

2200

2200

2200

2200

2200

2200

  • Depth

mm

600

600

600

600

600

600

Weight, approx.

kg

286

286

490

490

490

700

Frame size

 

GX

GX

HX

HX

HX

JX

Short-circuit current rating according to IEC

kA

65

65

65

84

84

100



1) Rated output of a typical 6-pole standard induction motor based on IL or IH for 500 V or 690 V 3 AC 50 Hz.

2) Rated output of a typical 6-pole standard induction motor based on IL or IH for 575 V 3 AC 60 Hz.

3) The base-load current IL is based on a load cycle of 110 % for 60 s or 150 % for 10 s with a load cycle duration of 300 s.

4) The base-load current IH is based on a duty cycle of 150 % for 60 s or 160 % for 10 s with a duty cycle duration of 300 s.

5)Information regarding the correlation between the pulse frequency and max. output current/output frequency is provided in the SINAMICS Low Voltage Engineering Manual.

6) The specified power loss represents the maximum value at 100% utilization. The value is lower under normal operating conditions.

7) Total of all motor cables. Longer cable lengths for specific configurations are available on request. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.

8) With option L10 (dv/dt filter plus VPL):- Frame sizes FX/GX/HX/JX: Additional cabinet 600 mm wide

With option L34 (circuit breaker on the output side):- Frame size FX/GX: Additional cabinet 400 mm wide

- Frame size HX/JX: Additional cabinet 600 mm wide.

9) The cabinet height increases by 250 mm with degree of protection IP21, and by 400 mm with degrees of protection IP23, IP43 and IP54.

 

Line voltage 500 ... 690 V 3 AC

DC link voltage 675 â€¦ 1035 V DC

Motor Modules in chassis format

 

6SL3720-1TG38-1AA3

6SL3720-1TG38-8AA3

6SL3720-1TG41-0AA3

6SL3720-1TG41-3AA3

Type rating

 

 

 

 

 

  • At IL (50 Hz 690 V) 1)

kW

800

900

1000

1200

  • At IH (50 Hz 690 V) 1)

kW

710

800

900

1000

  • At IL (50 Hz 500 V) 1)

kW

560

630

710

900

  • At IH (50 Hz 500 V) 1)

kW

500

560

630

800

  • At IL (60 Hz 575 V) 2)

hp

800

900

1000

1250

  • At IH (60 Hz 575 V) 2)

hp

700

800

900

1000

Output current

 

 

 

 

 

  • Rated current Irated O

A

810

910

1025

1270

  • Base-load current IL3)

A

790

880

1000

1230

  • Base-load current IH4)

A

724

814

917

1136

  • Maximum current Imax O

A

1185

1320

1500

1845

DC link current

 

 

 

 

 

  • Rated current Irated DC
    when supplied via

 

 

 

 

 

  • Basic/Smart Line Module

A

972

1092

1230

1524

  • Active Line Module

A

875

983

1107

1372

  • Base-load current IL DC 3)
    when supplied via

 

 

 

 

 

  • Basic/Smart Line Module

A

947

1064

1199

1485

  • Active Line Module

A

853

958

1079

1337

  • Base-load current IH DC 4)
    when supplied via

 

 

 

 

 

  • Basic/Smart Line Module

A

865

971

1094

1356

  • Active Line Module

A

778

874

985

1221

Current demand

 

 

 

 

 

  • 24 V DC auxiliary power supply

A

1.25

1.4

1.4

1.4

  • 690 V AC

A

3.1

3.1

3.1

3.1

DC link capacitance

μF

11100

14400

14400

19200

Pulse frequency 5)

 

 

 

 

 

  • Rated frequency

kHz

1.25

1.25

1.25

1.25

  • Pulse frequency, max.

 

 

 

 

 

  • Without current derating

kHz

1.25

1.25

1.25

1.25

  • With current derating

kHz

7.5

7.5

7.5

7.5

Power loss, max. 6)

 

 

 

 

 

  • At 50 Hz 690 V

kW

11.5

11.7

13.2

16.0

  • At 60 Hz 575 V

kW

10.5

10.6

12.0

14.2

Cooling air requirement

m3/s

1.08

1.08

1.08

1.08

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

72

72

72

72

Motor connection

U2, V2, W2

 

M12 screws

M12 screws

M12 screws

M12 screws

  • Conductor cross section, max. (IEC)

mm2

6 x 240

6 x 240

6 x 240

6 x 240

Cable length, max. 7)

 

 

 

 

 

  • Shielded

m

300

300

300

300

  • Unshielded

m

450

450

450

450

PE/GND connection

 

PE bar

PE bar

PE bar

PE bar

  • Busbar cross-section

mm2

600

600

600

600

  • Conductor cross section, max. (IEC)

mm2

240

240

240

240

Degree of protection

 

IP20

IP20

IP20

IP20

Dimensions

 

 

 

 

 

  • Width 8)

mm

800

800

800

800

  • Height 9)

mm

2200

2200

2200

2200

  • Depth

mm

600

600

600

600

Weight, approx.

kg

700

700

700

700

Frame size

 

JX

JX

JX

JX

Short-circuit current rating according to IEC

kA

100

100

100

100



1) Rated output of a typical 6-pole standard induction motor based on IL or IH for 500 V or 690 V 3 AC 50 Hz.

2) Rated output of a typical 6-pole standard induction motor based on IL or IH for 575 V 3 AC 60 Hz.

3) The base-load current IL is based on a load cycle of 110 % for 60 s or 150 % for 10 s with a load cycle duration of 300 s.

4) The base-load current IH is based on a duty cycle of 150 % for 60 s or 160 % for 10 s with a duty cycle duration of 300 s.

5)Information regarding the correlation between the pulse frequency and max. output current/output frequency is provided in the SINAMICS Low Voltage Engineering Manual.

6) The specified power loss represents the maximum value at 100% utilization. The value is lower under normal operating conditions.

7) Total of all motor cables. Longer cable lengths for specific configurations are available on request. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.

8) With option L10 (dv/dt filter plus VPL):- Frame sizes FX/GX/HX/JX: Additional cabinet 600 mm wide

With option L34 (circuit breaker on the output side):- Frame size FX/GX: Additional cabinet 400 mm wide

- Frame size HX/JX: Additional cabinet 600 mm wide.

9) The cabinet height increases by 250 mm with degree of protection IP21, and by 400 mm with degrees of protection IP23, IP43 and IP54.

















skener.ru

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Àðìàòóðà DENDOR

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Äàò÷èêè è èçìåðèòåëè

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ðåãóëÿòîðû è ðåãèñòðàòîðû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ïíåâìàòè÷åñêîå îáîðóäîâàíèå

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Êðàíû è Êëàïàíû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Èçìåðèòåëüíûå ïðèáîðû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ñèñòåìû áåñïðîâîäíîãî óïðàâëåíèÿ «óìíûé äîì»

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Áåñêîíòàêòíûå âûêëþ÷àòåëè Êîíå÷íûå âûêëþ÷àòåëè Îïòè÷åñêèå äàò÷èêè Ýíêîäåðû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FS - Óñòàíîâêà óìÿã÷åíèÿ

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FK - Óñòàíîâêà îáåçæåëåçèâàíèÿ

  © ÎÎÎ "ÑÊ ÝÍÅÐÃÎ" 2007-2022
  (4872) 700-366  skenergo@mail.ru
ßíäåêñ.Ìåòðèêà