Siemens
СРЕДСТВА ПРОМЫШЛЕННОЙ АВТОМАТИЗАЦИИ
официальный партнер Сименс
Каталог СА01 2018
(4872) 700-366
skenergo@mail.ru

Derating data

Pulse frequency

Rated power at 400 V 3 AC

Rated output current in A

for a pulse frequency of

kW

hp

4 kHz

6 kHz

8 kHz

10 kHz

12 kHz

14 kHz

16 kHz

0.75

1

2.2

1.9

1.5

1.3

1.1

1

0.9

1.5

1.5 1)

4.1

3.5

2.9

2.5

2.1

1.8

1.6

3

4

7.7

6.5

5.4

4.6

3.9

3.5

3.1

4

5

10.2

8.7

7.1

6.1

5.1

4.6

4.1

5.5

7.5

13.2

11.2

9.2

7.9

6.6

5.9

5.3

7.5

10

19

16.2

13.3

11.4

9.5

8.6

7.6



1) It is not possible to make any assignment to a particular standard.

Ambient temperature

Permissible output current as a function of ambient temperature for PM250D Power Modules, frame sizes FSA to FSC

Note:

The operating temperature ranges of the Control Units should be taken into account. The temperature ranges are specified in the technical specifications under Control Units.

Installation altitude

Permissible output current as a function of installation altitude for PM250D Power Modules, frame sizes FSA to FSC

Permissible input voltage as a function of installation altitude for PM250D Power Modules, frame sizes FSA to FSC


















  © ООО "СК ЭНЕРГО" 2007-2022
  (4872) 700-366  skenergo@mail.ru
Яндекс.Метрика