Electrical specifications |
Line voltages and power ranges | - 380 ... 480 V 3 AC ±10% (‑15% <1 min) 110 ... 560 kW
- 500 ... 600 V 3 AC ±10% (‑15% <1 min) 110 ... 560 kW
- 660 ... 690 V 3 AC ±10% (‑15% <1 min) 75 ... 800 kW
|
Line system configurations | Grounded TN/TT systems or ungrounded IT systems (a grounded line conductor is not permissible in 690 V line supplies) |
Line frequency | 47 ... 63 Hz |
Output frequency | 0 ... 550 Hz1) |
Line power factor | |
| > 0.96 |
| 0.75 ... 0.93 |
Efficiency | > 98% |
Overvoltage category | III according to EN 61800‑5‑1 |
Rated short-circuit current according to IEC, in conjunction with the specified fuses | |
| 65 kA |
| 84 kA |
| 170 kA |
| 200 kA |
Rated short-circuit current SCCR (Short Circuit Current Rating) according to UL508C (up to 600 V), in conjunction with the specified fuses or circuit breakers | |
| 65 kA |
| 84 kA |
| 170 kA |
| 200 kA |
Control method | Vector control with and without encoder or V/f control |
Fixed speeds | 15 fixed speeds plus 1 minimum speed, parameterizable (in the default setting, 3 fixed setpoints plus 1 minimum speed are selectable using terminal block / PROFIBUS) |
Speed ranges that can be skipped | 4, parameterizable |
Setpoint resolution | 0.001 rpm digital 12-bit analog |
Braking operation | By means of additional Braking Modules and braking resistors |
Mechanical specifications |
Degree of protection | IP00 or IP20 depending on type |
Protection class | I according to EN 61800‑5‑1 |
Touch protection | EN 50274 / BGV A3 when used for the intended purpose |
Cooling method | Forced air cooling AF according to EN 60146 |
Ambient conditions | Storage | Transport | Operation |
Ambient temperature | -25 ... +55 °C | ‑25 ... +70 °C as of ‑40 °C for 24 hours | 0 ... +40 °C up to +55 °C see derating data |
Relative humidity (condensation not permissible) | 5 ... 95% | 5 ... 95% at 40 °C | 5 ... 95% |
| | Class 1K4 according to EN 60721‑3‑1 | Class 2K3 according to EN 60721‑3‑2 | Class 3K3 according to EN 60721‑3‑3 |
Environmental class / harmful chemical substances | Class 1C2 according to EN 60721‑3‑1 | Class 2C2 according to EN 60721‑3‑2 | Class 3C2 according to EN 60721‑3‑3 |
Organic/biological influences | Class 1B1 according to EN 60721‑3‑1 | Class 2B1 according to EN 60721‑3‑2 | Class 3B1 according to EN 60721‑3‑3 |
Degree of pollution | 2 according to EN 61800‑5‑1 |
Installation altitude | Up to 2000 m above sea level without derating; > 2000 m see derating data |
Mechanical stability | Storage | Transport | Operation |
Vibratory load | | | |
| 1.5 mm at 5 ... 9 Hz | 3.1 mm at 5 ... 9 Hz | 0.075 mm at 10 ... 58 Hz |
| 5 m/s2 at > 9 ... 200 Hz | 10 m/s2 at > 9 ... 200 Hz | 10 m/s2 at > 58 … 200 Hz |
| Class 1M2 according to EN 60721‑3‑1 | Class 2M2 according to EN 60721‑3‑2 | – |
Shock load | | | |
| 40 m/s2 for 22 ms | 100 m/s2 for 11 ms | 100 m/s2 for 11 ms |
| Class 1M2 according to EN 60721‑3‑1 | Class 2M2 according to EN 60721‑3‑2 | Class 3M4 according to EN 60721‑3‑3 |
Compliance with standards |
CE marking | According to EMC Directive No. 2004/108/EC and Low Voltage Directive No. 2006/95/EC and Machinery Directive No. 2006/42/EC for functional safety. |
Radio interference suppression | The SINAMICS G130 converter systems are not designed for connection to the public power network ("first environment"). Radio interference suppression is compliant with the EMC product standard for variable-speed drives EN 61800‑3, "Second environment" (industrial networks). EMC disturbances can occur when connected to the public power networks. However, if additional measures are taken (e.g. line filter), it can also be operated in the "first environment". 2) |
Approvals | cULus (only for 380 ... 480 V 3 AC and 500 ... 600 V 3 AC) |