Input characteristic curve in accordance with IEC 61131, type 1
Yes
Yes
Yes; 2-wire sensors connectable
Yes
Number of simultaneously controllable inputs
? Number of simultaneously controllable inputs
8
Input voltage
? Type of input voltage
DC
DC
DC
DC
? Rated value (DC)
24 V
24 V
24 V
24 V
? for signal "0"
-30 to +5V
-30 to +5V
-30 to +5V
-5 to +30V
? for signal "1"
+15 to +30V
+11 to +30V
+15 to +30V
-15 to -30 V
Input current
? for signal "1", typ.
7 mA; at 24 V
8 mA
5 mA
6 mA; at 24 V
Input delay (for rated value of input voltage)
for standard inputs
— parameterizable
No
Yes; 0.1 / 0.5 / 3 / 15 ms
No
No
— at "0" to "1", min.
2 ms; typically 3 ms
0.05 / 0.4 / 2.7 / 14.85
2 ms
2 ms
— at "0" to "1", max.
4.5 ms
0,15 / 0,6 / 3,3 / 15,15
4.5 ms
4.5 ms
— at "1" to "0", min.
2 ms; typically 3 ms
0.05 / 0.4 / 2.7 / 14.85
2 ms
2 ms
— at "1" to "0", max.
4.5 ms
0,15 / 0,6 / 3,3 / 15,15
4.5 ms
4.5 ms
Cable length
? shielded, max.
1 000 m
1 000 m
1 000 m
1 000 m
? unshielded, max.
600 m
600 m
600 m
600 m
Encoder
Connectable encoders
? 2-wire sensor
Yes
Yes
Yes
Yes
— permissible quiescent current (2-wire sensor), max.
1.5 mA
1.5 mA
1.5 mA
1.5 mA
Isochronous mode
Isochronous operation (application synchronized up to terminal)
Yes; TWE = 3000 us
Yes
Interrupts/diagnostics/status information
Diagnostic functions
No
Yes
No
No
Diagnostic messages
? Short-circuit
Yes; Short-circuit of outputs to ground; module by module
Diagnostics indication LED
? Group error SF (red)
No
Yes
No
? Status indicator digital input (green)
Yes; per channel
Yes; per channel
Yes
Yes; per channel
Parameter
Remark
1 byte
3 byte
3-byte parameter (not accessible for the user)
3 byte
Diagnostics short-circuit
Disable / enable
Potential separation
Potential separation digital inputs
? between the channels
No
No
No
No
? between the channels and backplane bus
Yes
Yes
Yes
Yes
Permissible potential difference
between different circuits
75 V DC/60 V AC
75 V DC/60 V AC
75 V DC/60 V AC
75 V DC/60 V AC
Isolation
Isolation tested with
500 V DC
500 V DC
500 V DC
500 V DC
Standards, approvals, certificates
CE mark
Yes
Yes
Yes
Yes
Ambient conditions
Ambient temperature during operation
? min.
-25 °C; = Tmin
-25 °C; = Tmin
-25 °C; = Tmin
-40 °C; = Tmin
? max.
60 °C; = Tmax
70 °C; = Tmax
70 °C; = Tmax
70 °C; = Tmax
Extended ambient conditions
? relative to ambient temperature-atmospheric pressure-installation altitude
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)
Relative humidity
— With condensation, tested in accordance with IEC 60068-2-38, max.
100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions)
100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions)
100 %; incl. condensation / frost permitted (no commissioning under condensation conditions)
100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions)
Resistance
— against biologically active substances / conformity with EN 60721-3-3
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation in corrosive atmospheres!
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
— against chemically active substances / conformity with EN 60721-3-3
Yes; Class 3C4 incl. salt spray. The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
— against mechanically active substances / conformity with EN 60721-3-3
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Dimensions
Width
15 mm
15 mm
15 mm
15 mm
Height
81 mm
81 mm
81 mm
81 mm
Depth
52 mm
52 mm
52 mm
52 mm
Weights
Weight, approx.
35 g
35 g
35 g
35 g
Article number
6AG1132-4BB01-2AB0
6AG1132-4BB31-7AB0
6AG1132-4BD02-7AA0
6AG1132-4BD32-2AA0
SIPLUS DP 2DO HF ET200S
SIPLUS ET200S 2DO high feature
SIPLUS ET200S 4DO (1VE = 5 Stueck)
SIPLUS_ET200S_4DO DC24V/2A
Supply voltage
Reverse voltage protection
Yes; when using the same load voltage as on the power module
Yes; when using the same load voltage as on the power module
Yes; when using the same load voltage as on the power module
Yes; when using the same load voltage as on the power module
Load voltage L+
? Rated value (DC)
24 V; From power module
24 V; From power module
24 V; From power module
24 V; From power module
? Reverse polarity protection
Yes; polarity reversal can lead to the digital outputs being connected through
Yes; polarity reversal can lead to the digital outputs being connected through
Yes; polarity reversal can lead to the digital outputs being connected through
Yes
Input current
from load voltage L+ (without load), max.
5 mA; Per channel
5 mA; Per channel
10 mA; Per channel
10 mA; Per channel
from backplane bus 3.3 V DC, max.
10 mA
10 mA
10 mA
10 mA
Power loss
Power loss, typ.
0.4 W
1.4 W
0.8 W
1.6 W
Address area
Address space per module
? with packing
2 bit
2 bit
4 bit
4 bit
? without packing
1 byte
1 byte
1 byte
1 byte
Digital outputs
Number of digital outputs
2
2
4
4
Short-circuit protection
Yes
Yes
Yes
Yes
? Response threshold, typ.
1.5 A
4 A
1 to 1.5 A
2.8 to 7.2 A
Limitation of inductive shutdown voltage to
-55 to -60 V, typ. L+( )
-55 to -60 V, typ. L+( )
o.k.
Typ. L+ (-55 to -60 V)
Controlling a digital input
Yes
Yes
Yes
Yes
Switching capacity of the outputs
? on lamp load, max.
2.5 W
5 W
5 W
10 W
Load resistance range
? lower limit
48 ?
12 ?
48 ?
12 ?
? upper limit
3 400 ?
3 400 ?
3 400 ?
3 400 ?
Output voltage
? for signal "1", min.
L+ (-1 V)
L+ (-1 V)
L+ (-1 V)
L+ (-1.0 V)
Output current
? for signal "1" rated value
0.5 A
2 A
0.5 A
2 A
? for signal "1" permissible range, min.
7 mA
7 mA
7 mA
7 mA
? for signal "1" permissible range, max.
600 mA
2.4 A
600 mA
2.4 A
? for signal "0" residual current, max.
0.3 mA
0.5 mA
0.3 mA
0.5 mA
Output delay with resistive load
? "0" to "1", max.
100 µs
100 µs
45 µs; Typical value
50 µs; Typ. 45 µs
? "1" to "0", max.
400 µs
400 µs
90 µs; Typical value
120 µs; Typ. 90 µs
Parallel switching of two outputs
? for uprating
No
No
No
No
? for redundant control of a load
Yes; per module
Yes; per module
Yes; per module
Yes; per module
Switching frequency
? with resistive load, max.
100 Hz
100 Hz
800 Hz
1 000 Hz
? with inductive load, max.
2 Hz
2 Hz; 0,5 H
2 Hz
2 Hz; At 0.5 H
? on lamp load, max.
10 Hz
10 Hz
10 Hz
10 Hz
Total current of the outputs
? Current per module, max.
1 A
4 A
2 A
4 A
Cable length
? shielded, max.
1 000 m
1 000 m
1 000 m
1 000 m
? unshielded, max.
600 m
600 m
600 m
600 m
Isochronous mode
Isochronous operation (application synchronized up to terminal)
Yes
Yes
Yes
Yes
Interrupts/diagnostics/status information
Diagnostic functions
Yes; Can be read out
Yes; Can be read out
No
No
Substitute values connectable
Yes; 0/1
Yes; 0/1
Diagnostic messages
? Wire-break
Yes; channel by channel
Yes; channel by channel
? Short-circuit
Yes; channel by channel
Yes; channel by channel
Diagnostics indication LED
? Group error SF (red)
Yes
Yes
? Status indicator digital output (green)
Yes
Yes
Yes
Yes
Parameter
Remark
3 byte
3 byte
1 byte
1 byte
Diagnostics wire break
Disable / enable
Disable / enable
Diagnostics short-circuit
Disable / enable
Disable / enable
Response to CPU/master STOP
Substitute a value/keep last value
Substitute a value/keep last value
Potential separation
Potential separation digital outputs
? between the channels
No
No
No
No
? between the channels and backplane bus
Yes
Yes
Yes
Yes
Isolation
Isolation tested with
500 V DC
500 V DC
500 V DC
500 V DC
Ambient conditions
Ambient temperature during operation
? min.
-25 °C; = Tmin
-25 °C; = Tmin
-25 °C; = Tmin
-25 °C; = Tmin
? max.
60 °C; = Tmax
70 °C; = Tmax
70 °C; = Tmax
60 °C; = Tmax
Extended ambient conditions
? relative to ambient temperature-atmospheric pressure-installation altitude
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)
Relative humidity
— With condensation, tested in accordance with IEC 60068-2-38, max.
100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
— against biologically active substances / conformity with EN 60721-3-3
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
— against chemically active substances / conformity with EN 60721-3-3
Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
— against mechanically active substances / conformity with EN 60721-3-3
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Dimensions
Width
15 mm
15 mm
15 mm
15 mm
Height
81 mm
81 mm
81 mm
81 mm
Depth
52 mm
52 mm
52 mm
52 mm
Weights
Weight, approx.
40 g
40 g
40 g
40 g
Article number
6AG1132-4BF00-7AA0
6AG1132-4BF50-7AA0
6AG1132-4HB12-2AB0
SIPLUS ET200S EM 8 DO
SIPLUS ET200S EM 8 DO DC24V/0.5A
SIPLUS ET200S 2DORLY 24-48VDC 230VAC/5A
Supply voltage
Reverse voltage protection
Yes
Yes; when using the same correctly polarized load voltage as on the power module
Load voltage L+
? Rated value (DC)
24 V
24 V; From power module
24 V; From power module
? Reverse polarity protection
Yes
Yes
Yes
Input current
from load voltage L+ (without load), max.
5 mA; Per channel
5 mA
30 mA
from backplane bus 3.3 V DC, max.
10 mA
10 mA
10 mA
Power loss
Power loss, typ.
1.5 W
1.5 W
0.6 W
Address area
Address space per module
? with packing
2 bit
? without packing
1 byte
1 byte
1 byte
Digital outputs
Number of digital outputs
8
8
2
Short-circuit protection
Yes
Yes
No
? Response threshold, typ.
1.5 A
1.5 A
Limitation of inductive shutdown voltage to
Typ. L+ (-55 to -60 V)
Typ. 47 V
No
Controlling a digital input
Yes
Yes
Yes
Switching capacity of the outputs
? on lamp load, max.
5 W
5 W
Load resistance range
? lower limit
48 ?
48 ?
? upper limit
3 400 ?
3 400 ?
Output voltage
? for signal "1", min.
L+ (-1.0 V)
Max. 1 V
Output current
? for signal "1" rated value
0.5 A
0.5 A
5 A
? for signal "1" permissible range, min.
7 mA
5 mA
? for signal "1" permissible range, max.
600 mA
600 mA
? for signal "1" minimum load current
8 mA
? for signal "0" residual current, max.
0.3 mA
5 µA
Output delay with resistive load
? "0" to "1", max.
300 µs
300 µs
? "1" to "0", max.
600 µs
600 µs
Parallel switching of two outputs
? for uprating
No
No
? for redundant control of a load
Yes
Yes; per module
Switching frequency
? with resistive load, max.
100 Hz
100 Hz
2 Hz
? with inductive load, max.
2 Hz
0.5 Hz
0.5 Hz
? on lamp load, max.
10 Hz
10 Hz
2 Hz
Total current of the outputs
? Current per module, max.
4 A
4 A
Relay outputs
Switching capacity of contacts
— Thermal continuous current, max.
5 A
Cable length
? shielded, max.
1 000 m
1 000 m
1 000 m
? unshielded, max.
600 m
600 m
600 m
Isochronous mode
Isochronous operation (application synchronized up to terminal)
Yes; jitter incumbered < 100us
Yes
No
Interrupts/diagnostics/status information
Diagnostic functions
No
No
No
Substitute values connectable
Yes; 0/1
Diagnostics indication LED
? Status indicator digital output (green)
Yes
Yes
Yes
Parameter
Remark
3-byte parameter (not accessible for the user)
3 byte
Response to CPU/master STOP
Substitute a value/keep last value
Potential separation
Potential separation digital outputs
? between the channels
No
No
Yes
? between the channels and backplane bus
Yes
Yes
Yes
? Between the channels and load voltage L+
Yes
Isolation
Isolation tested with
500 V DC
500 V DC
tested with
? Channels against backplane bus and load voltage L+
1500 V AC
? Load voltage L+ against backplane bus
500 V DC
Ambient conditions
Ambient temperature during operation
? min.
-40 °C; = Tmin
-25 °C; = Tmin
-25 °C; = Tmin
? max.
70 °C; = Tmax
70 °C; = Tmax
60 °C; = Tmax
Extended ambient conditions
? relative to ambient temperature-atmospheric pressure-installation altitude
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m)
Relative humidity
— With condensation, tested in accordance with IEC 60068-2-38, max.
100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
— against biologically active substances / conformity with EN 60721-3-3
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
— against chemically active substances / conformity with EN 60721-3-3
Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
— against mechanically active substances / conformity with EN 60721-3-3
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Dimensions
Width
15 mm
15 mm
15 mm
Height
81 mm
81 mm
81 mm
Depth
52 mm
52 mm
52 mm
Weights
Weight, approx.
40 g
40 g
50 g
skener.ru
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Àðìàòóðà DENDOR
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Äàò÷èêè è èçìåðèòåëè
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ðåãóëÿòîðû è ðåãèñòðàòîðû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ïíåâìàòè÷åñêîå îáîðóäîâàíèå
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Êðàíû è Êëàïàíû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Èçìåðèòåëüíûå ïðèáîðû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ñèñòåìû áåñïðîâîäíîãî óïðàâëåíèÿ «óìíûé äîì»
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Áåñêîíòàêòíûå âûêëþ÷àòåëè Êîíå÷íûå âûêëþ÷àòåëè Îïòè÷åñêèå äàò÷èêè Ýíêîäåðû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FS - Óñòàíîâêà óìÿã÷åíèÿ
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FK - Óñòàíîâêà îáåçæåëåçèâàíèÿ