Line reactorsLine voltage 380 ... 480 V 3 AC | Line reactor |
|---|
| 6SL3000-0CE32-3AA0 | 6SL3000-0CE32-8AA0 | 6SL3000-0CE33-3AA0 | 6SL3000-0CE35-1AA0 | 6SL3000-0CE36-3AA0 | 6SL3000-0CE37-7AA0 | Rated current | A | 224 | 278 | 331 | 508 | 628 | 773 | Nominal inductance LN | ?H | 76 | 62 | 52 | 42 | 27 | 22 | Power loss 1) at 50/60 Hz | kW | 0.274 | 0.247 | 0.267 | 0.365 | 0.368 | 0.351 | Line supply/load connection | | 1 ? hole for M10 Provided for busbar connection | 1 ? hole for M10 Provided for busbar connection | 1 ? hole for M10 Provided for busbar connection | 1 ? hole for M12 Provided for busbar connection | 1 ? hole for M12 Provided for busbar connection | 1 ? hole for M12 Provided for busbar connection | PE connection | | M6 screw | M6 screw | M6 screw | M6 screw | M6 screw | M6 screw | Degree of protection | | IP00 | IP00 | IP00 | IP00 | IP00 | IP00 | Dimensions | | | | | | | | | mm | 270 | 270 | 270 | 300 | 300 | 300 | | mm | 248 | 248 | 248 | 269 | 269 | 269 | | mm | 200 | 200 | 200 | 212 | 212 | 212 | Weight, approx. | kg | 24.5 | 26 | 27.8 | 38.0 | 41.4 | 51.3 | Conformity | | CE | CE | CE | CE | CE | CE | Approvals, according to | | cURus | cURus | cURus | cURus | cURus | cURus | Suitable for Power Module, chassis format | | | 6SL3310-1TE32-1AA3 (110 kW) | 6SL3310-1TE32-6AA3 (132 kW) | 6SL3310-1TE33-1AA3 (160 kW) | 6SL3310-1TE33-8AA3 (200 kW) 6SL3310-1TE35-0AA3 (250 kW) | – | – | - Liquid-cooled
(type rating)
| | 6SL3315-1TE32-1AA3 (110 kW) | 6SL3315-1TE32-6AA3 (132 kW) | 6SL3315-1TE33-1AA3 (160 kW) | 6SL3315-1TE35-0AA3 (250 kW) | – | – | Suitable for Basic Line Module, chassis format | | | – | – | – | 6SL3330-1TE34-2AA3 (200 kW) 6SL3330-1TE35-3AA3 (250 kW) | – | 6SL3330-1TE38-2AA3 (400 kW) | - Liquid-cooled
(rated power)
| | – | – | – | – | 6SL3335-1TE37-4AA3 (360 kW) | – |
1) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions. Line voltage 380 ... 480 V 3 AC | Line reactor |
|---|
| 6SL3000-0CE41-0AA0 | 6SL3000-0CE41-5AA0 | 6SL3000-0EE36-2AA0 | 6SL3000-0EE38-8AA0 | 6SL3000-0EE41-4AA0 | Rated current | A | 1022 | 1485 | 615 | 885 | 1430 | Nominal inductance LN | ?H | 16 | 13 | 55 | 35 | 25 | Power loss 1) at 50/60 Hz | kW | 0,498 | 0,776 | 0,56 | 0,81 | 1,08 | Line supply/load connection | | 1 ? hole for M12 Provided for busbar connection | 1 ? hole for M12 Provided for busbar connection | 1 ? hole for M10 Provided for busbar connection | 1 ? hole for M10 Provided for busbar connection | 2 ? hole for M10 Provided for busbar connection | PE connection | | M6 screw | M6 screw | M6 thread | M6 thread | M6 thread | Degree of protection | | IP00 | IP00 | IP00 | IP00 | IP00 | Dimensions | | | | | | | | mm | 350 | 460 | 300 | 442 | 544 | | mm | 321 | 435 | 264 | 376 | 386 | | mm | 211 | 235 | 203 | 263 | 232 | Weight, approx. | kg | 69.6 | 118 | 57 | 85.5 | 220 | Conformity | | CE | CE | CE | CE | CE | Approvals, according to | | cURus | cURus | cURus | cURus | cURus | Suitable for Basic Line Module, chassis format | | | 6SL3330-1TE41-2AA3 (560 kW) | 6SL3330-1TE41-5AA3 (710 kW) | – | – | – | - Liquid-cooled
(rated power)
| | 6SL3335-1TE41-2AA3 (600 kW) | 6SL3335-1TE41-7AA3 (830 kW) | – | – | – | Suitable for Smart Line Module, chassis format | | | – | – | 6SL3330-6TE35-5AA3 (250 kW) 6SL3330-6TE37-3AA3 (355 kW) | 6SL3330-6TE41-1AA3 (500 kW) | 6SL3330-6TE41-3AA3 (630 kW) 6SL3330-6TE41-7AA3 (800 kW) |
1) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions. Line voltage 500 ... 690 V 3 AC | Line reactor |
|---|
| 6SL3000-0CH32-7AA0 | 6SL3000-0CH33-4AA0 | 6SL3000-0CH34-8AA0 | 6SL3000-0CH36-0AA0 | 6SL3000-0CH41-2AA0 | 6SL3000-0EH41-6AA0 | Rated current | A | 270 | 342 | 482 | 597 | 1167 | 1600 | Nominal inductance LN | ?H | 100 | 81 | 65 | 46 | 30 | 17 | Power loss 1) at 50/60 Hz | kW | 0.277 | 0.27 | 0.48 | 0.485 | 0.783 | 0.977 | Line supply/load connection | | 1 ? hole for M10 Provided for busbar connection | 1 ? hole for M10 Provided for busbar connection | 1 ? hole for M12 Provided for busbar connection | 1 ? hole for M12 Provided for busbar connection | 2 ? hole for M12 Provided for busbar connection | 2 ? hole for M12 Provided for busbar connection | PE connection | | M6 screw | M6 screw | M6 screw | M6 screw | M6 screw | M6 screw | Degree of protection | | IP00 | IP00 | IP00 | IP00 | IP00 | IP00 | Dimensions | | | | | | | | | mm | 270 | 270 | 350 | 350 | 460 | 416 | | mm | 248 | 248 | 321 | 321 | 435 | 435 | | mm | 200 | 200 | 232 | 232 | 235 | 250 | Weight, approx. | kg | 27.9 | 38.9 | 55.6 | 63.8 | 147 | 134 | Conformity | | CE | CE | CE | CE | CE | CE | Approvals 2), according to | | cURus | cURus | cURus | cURus | cURus | cURus | Suitable for Basic Line Module, chassis format | | | 6SL3330-1TG33-0AA3 (250 kW) | – | 6SL3330-1TG34-3AA3 (355 kW) | 6SL3330-1TG36-8AA3 (560 kW) | 6SL3330-1TG41-1AA3 (900 kW) 6SL3330-1TG41-4AA3 (1100 kW) | – | - Liquid-cooled
(rated power)
| | – | 6SL3335-1TG34-2AA3 (355 kW) | – | 6SL3335-1TG37-3AA3 (630 kW) | 6SL3335-1TG41-3AA3 (1100 kW) | 6SL3335-1TG41-7AA3 (1370 kW) |
1) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions. 2) Only for line voltages 500 ... 600 V 3 AC. Line voltage 500 ... 690 V 3 AC | Line reactor |
|---|
| 6SL3000-0EH34-7AA0 | 6SL3000-0EH37-6AA0 | 6SL3000-0EH41-4AA0 | Rated current | A | 465 | 760 | 1430 | Nominal inductance LN | ?H | 115 | 70 | 40 | Power loss 1) at 50/60 Hz | kW | 0,82 | 0,95 | 1,85 | Line supply/load connection | | 1 ? hole for M10 Provided for busbar connection | 1 ? hole for M10 Provided for busbar connection | 2 ? hole for M10 Provided for busbar connection | PE connection | | M6 nut | M6 nut | M6 nut | Degree of protection | | IP00 | IP00 | IP00 | Dimensions | | | | | | mm | 360 | 442 | 655 | | mm | 325 | 370 | 383 | | mm | 229 | 303 | 288 | Weight, approx. | kg | 58 | 145 | 239 | Conformity | | CE | CE | CE | Approvals 2), according to | | cURus | cURus | cURus | Suitable for Smart Line Module, chassis format | | | 6SL3330-6TG35-5AA3 (450 kW) | 6SL3330-6TG38-8AA3 (710 kW) | 6SL3330-6TG41-2AA3 (1000 kW) 6SL3330-6TG41-7AA3 (1400 kW) |
1) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions. 2) Only for line voltages 500 ... 600 V 3 AC.
|
|