Overload capabilitySINAMICS S120 Liquid Cooled units have an overload reserve, e.g. to handle breakaway torques. If larger surge loads occur, this must be taken into account when configuring. In drives with overload requirements, the appropriate base load current must, therefore, be used as a basis for the required load. The permissible overload levels are valid under the prerequisite that the drive units are operated with their base load current before and after the overload condition based on a duty cycle duration of 300 s. For short, repeating load cycles with significant load fluctuations within the load cycle, the appropriate sections in the SINAMICS Low Voltage Engineering Manual must be observed (as PDF file on the CD-ROM provided with the catalog). Power Modules and Motor Modules The base load current for a low overload IL is the basis for a duty cycle of 110 % for 60 s or 150 % for 10 s. Low overload The base load current for a high overload IH is the basis for a duty cycle of 150 % for 60 s or 160 % for 10 s. High overload Line Modules The base load current for a high overload IH DC is the basis for a duty cycle of 150 % for 60 s or Imax DC for 5 s. High overload Pressure dropPressure drop for frame size FL Pressure drop for frame size GL Current derating as a function of the temperature of the cooling liquid Current derating as a function of ambient temperature Permissible ambient temperature as a function of installation altitude Voltage derating as a function of installation altitude |