product brand name | | SIPLUS |
Product designation | | HCS POM4220 Lowend |
General technical data: | | |
Type of load | | Ohmic load |
Equipment marking acc. to DIN EN 81346-2 | | Q |
Supply voltage: | | |
Type of voltage of the supply voltage | | AC |
Supply voltage at AC Rated value | V | 230 |
Relative negative tolerance of the supply voltage | % | 10 |
Relative positive tolerance of the supply voltage | % | 10 |
Supply voltage frequency 1 Rated value | Hz | 50 |
Supply voltage frequency 2 Rated value | Hz | 60 |
Relative symmetrical tolerance of the supply voltage frequency | % | 5 |
Power capacity | | |
| kW | 16.1 |
| kW | 7.3 |
| kW | 16.1 |
Switching capacity current per phase maximum | A | 35 |
Design of the electrical isolation | | Optocoupler and/or protective impedance between main circuit and PELV |
Recovery time after power failure typical | s | 1 |
Type of electrical connection for supply voltage | | Connector, 3-pin |
Type of connectable conductor cross-section | | |
| | 1x (0,25 ... 6 mm?) |
| | 24 ... 8 |
Power Electronics: | | |
Control version of heat emitters | | Half-wave control |
Number of outputs for heating power | | 16 |
Number of heat emitters per output maximum | | 1 |
Output voltage at output for heating power | V | 230 |
Power capacity per output | | 100 ... 1 449 |
Output current at output for heating power Rated value | A | 6.3 |
Design of short-circuit protection for heating power per output | | Safety fuse 6.3 A |
Melting I2t value | A?·s | 57 |
Design of the overvoltage protection | | Transil Diode |
Galvanic isolation between the outputs | | No |
Type of electrical connection at output for heating and fan | | Connector, 8-pole |
Type of connectable conductor cross-section | | |
| | 1x (0.2 ... 10 mm?) |
| | 1x (0,25 ... 6 mm?) |
| | 24 ... 8 |
Communication: | | |
Design of the interface | | system interface |
Display: | | |
Number of status displays | | 19 |
Display version as status display by LED | | LED green = ready, LED yellow = heating on/off, LED red = error display, LED red = error for each channel |
Auxiliary circuit: | | |
Design of the power supply | | Power supply via rack |
Active power consumption maximum | W | 1 |
Protective and monitoring functions: | | |
Product function Temperature monitoring | | Yes |
Type of the temperature monitoring | | NTC thermistor |
Diagnostics function | | Voltage diagnostics |
| | Yes |
| | Yes |
| | Yes |
Mechanical data: | | |
mounting position | | vertical |
Mounting type | | Screw mounting to rack |
Type of ventilation | | Self ventilation or forced ventilation |
Vibration resistance | | |
| | 10 ... 58 Hz / 0.075 mm, 58 ... 150 Hz / 1g |
| | 5 ... 8.5 Hz / 3.5 mm, 8.5 ... 500 Hz / 1g |
Shock resistance | | |
| | 25 g / 6 ms / 1000 shocks / axis |
| | 15g / 11 ms / 3 shocks / axis |
Protection class IP | | IP20 |
Depth | mm | 281 |
Height | mm | 285 |
Width | mm | 36 |
Electromagnetic compatibility: | | |
EMC emitted interference | | Limit value in accordance with IEC 61000-6-4:2007 + A1:2011 |
Conducted interference due to burst acc. to IEC 61000-4-4 | | 2 kV power supply lines, 2 kV load lines |
Conducted interference due to surge acc. to IEC 61000-4-5 | | Supply and load lines: 1 kV symmetric, 2 kV unsymmetric PROFINET cables: 1 kV unsymmetric |
Conducted interference due to high-frequency radiation acc. to IEC 61000-4-6 | | 10 V (0.15 ... 80 MHz) |
Field-bound parasitic coupling acc. to IEC 61000-4-3 | | 10 V/m (80 ... 1000 MHz), 3 V/m (1.4 ... 2.0 GHz), 1 V/m (2.0 ... 2.7 GHz) |
Electrostatic discharge acc. to IEC 61000-4-2 | | 4 kV contact discharging, 8 kV air discharging |
Overvoltage category | | III |
Ambient conditions: | | |
Ambient temperature | | |
| | 0 ... 55 |
| | -25 ... +70 |
| | -25 ... +70 |
Air pressure | | |
| | 860 ... 1 080 |
| | 660 ... 1 080 |
Degree of pollution | | 2 |
Installation altitude at height above sea level maximum | m | 2 000 |
Relative humidity | | |
| % | 95 |
| % | 50 |
| | 95% at 25 °C, decreasing linearly to 50% at 50 °C |