Line Connection ModulesLine voltage 380 … 480 V 3 AC | Line Connection Modules |
|---|
| | 6SL3700-0LE32-5AA3 | 6SL3700-0LE34-0AA3 | 6SL3700-0LE36-3AA3 | 6SL3700-0LE38-0AA3 | 6SL3700-0LE41-0AA3 | 6SL3700-0LE41-3AA3 | Infeed/regenerative feedback current | | | | | | | | | A | 250 | 380 | 600 | 770 | 1000 | 1250 | Current demand | | | | | | | | - 24 V DC auxiliary power supply
| A | – | – | – | – | – | – | | A | – | – | – | – | 1.07 | 1.07 | | | | | | | | | | A | 3.6 | 3.6 | 3.6 | 10.8 | 0.5 | 0.5 | | A | 0.04 | 0.04 | 0.04 | 0.12 | 0.06 | 0.06 | Power loss, max. 2) | | | | | | | | | | | | | | | | | kW | 0.115 | 0.19 | 0.31 | 0.39 | 0.18 | 0.29 | | kW | – | – | 0.675 | 0.74 | – | 0.787 | | | | | | | | | | kW | 0.115 | 0.19 | 0.31 | 0.39 | 0.18 | 0.29 | | kW | – | – | 0.675 | 0.74 | – | 0.787 | Cooling air requirement 3) | m3/s | – | – | – | – | 0.36 | 0.36 | Sound pressure level LpA (1 m) at 50/60 Hz | dB | – | – | – | – | 68/70 | 68/70 | Line supply connection L1, L2, L3 | | 2/M12 | 2/M12 | 2/M12 | 2/M12 | 5/M12 + 4/M16 | 5/M12 + 4/M16 | - Conductor cross-section, max. (IEC)
| mm2 | 2 ? 150 | 2 ? 150 | 4 ? 240 | 8 ? 240 | 8 ? 240 | 8 ? 240 | PE/GND connection | | PE bar | PE bar | PE bar | PE bar | PE bar | PE bar | | mm2 | 600 | 600 | 600 | 600 | 600 | 600 | - Conductor cross-section, max. (IEC)
| mm2 | 240 | 240 | 240 | 240 | 240 | 240 | Degree of protection | | IP20 | IP20 | IP20 | IP20 | IP20 | IP20 | Dimensions | | | | | | | | | mm | 400 | 400 | 600 | 600 | 600 | 600 | | mm | 2200 | 2200 | 2200 | 2200 | 2200 | 2200 | | mm | 600 | 600 | 600 | 600 | 600 | 600 | Weight, approx. | | | | | | | | | kg | 210 | 230 | 310 | 340 | 450 | 470 | | kg | – | – | 360 | 420 | – | 570 | Frame size | | FL | FL | GL | HL | JL | JL |
1) Current demand of contactors/circuit breakers and fans with IP23, IP43, IP54 degree of protection (in combination with Basic Line Modules). 2) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions. 3) For IP23, IP43 or IP54 degree of protection only (in combination with Basic Line Modules). 4) The cabinet height increases by 250 mm with IP21 degree of protection, and by 400 mm with IP23, IP43 and IP54 degrees of protection. Line voltage 380 … 480 V 3 AC | Line Connection Modules |
|---|
| | 6SL3700-0LE41-6AA3 | 6SL3700-0LE42-0AA3 | 6SL3700-0LE42-0BA3 | 6SL3700-0LE42-5BA3 | 6SL3700-0LE43-2BA3 | | | | | Prepared for connection to Line Modules connected in parallel | Infeed/regenerative feedback current | | | | | | | | A | 1600 | 2000 | 2000 | 2500 | 3200 | Current demand | | | | | | | - 24 V DC auxiliary power supply
| A | – | – | – | – | – | | A | 1.07 | 2.14 | 2.14 | 2.14 | 2.14 | | | | | | | | | A | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | | A | 0.06 | 0.06 | 0.06 | 0.06 | 0.04 | Power loss, max. 2) | | | | | | | | | | | | | | | kW | 0.41 | 0.6 | 0.6 | 0.95 | 0.95 | | kW | 1.186 | 1.366 | 1.594 | 2.502 | 2.482 | | | | | | | | | kW | 0.41 | 0.6 | 0.6 | 0.95 | 0.95 | | kW | 1.186 | 1.366 | 1.594 | 2.502 | 2.482 | Cooling air requirement 3) | m3/s | 0.36 | 0.72 | 0.72 | 0.72 | 0.72 | Sound pressure level LpA (1 m) at 50/60 Hz | dB | 68/70 | 70/72 | 70/72 | 70/72 | 70/72 | Line supply connection L1, L2, L3 | | 5/M12 + 4/M16 | 5/M12 + 4/M16 | 5/M12 + 4/M16 | 5/M12 + 4/M16 | 5/M12 + 4/M16 | - Conductor cross-section, max. (IEC)
| mm2 | 8 ? 240 | 10 ? 240 | 10 ? 240 | 10 ? 240 | 10 ? 300 | PE/GND connection | | PE bar | PE bar | PE bar | PE bar | PE bar | | mm2 | 600 | 600 | 600 | 600 | 600 | - Conductor cross-section, max. (IEC)
| mm2 | 240 | 240 | 240 | 240 | 240 | Degree of protection | | IP20 | IP20 | IP20 | IP20 | IP20 | Dimensions | | | | | | | | mm | 600 | 1000 | 1000 | 1000 | 1000 | | mm | 2200 | 2200 | 2200 | 2200 | 2200 | | mm | 600 | 600 | 600 | 600 | 600 | Weight, approx. | | | | | | | | kg | 490 | 600 | 620 | 620 | 720 | | Kg | 650 | 760 | 820 | 900 | 1000 | Frame size | | JL | KL | KL | KL | LL |
1) Current demand of contactors/circuit breakers and fans with IP23, IP43, IP54 degree of protection (in combination with Basic Line Modules). 2) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions. 3) For IP23, IP43 or IP54 degree of protection only (in combination with Basic Line Modules). 4) The cabinet height increases by 250 mm with IP21 degree of protection, and by 400 mm with IP23, IP43 and IP54 degrees of protection. Line voltage 500 … 690 V 3 AC | Line Connection Modules |
|---|
| | 6SL3700-0LG32-8AA3 | 6SL3700-0LG34-0AA3 | 6SL3700-0LG36-3AA3 | 6SL3700-0LG38-0AA3 | 6SL3700-0LG41-0AA3 | Infeed/regenerative feedback current | | | | | | | | A | 280 | 380 | 600 | 770 | 1000 | Current demand | | | | | | | - 24 V DC auxiliary power supply
| A | – | – | – | – | – | | A | – | – | – | – | 1.07 | | | | | | | | | A | 3.6 | 3.6 | 3.6 | 10.8 | 0.5 | | A | 0.04 | 0.04 | 0.04 | 0.12 | 0.06 | Power loss, max. 2) | | | | | | | | | | | | | | | kW | 0.125 | 0.19 | 0.31 | 0.39 | 0.18 | | kW | 0.402 | 0.668 | 0.794 | – | 0.963 | | | | | | | | | kW | 0.125 | 0.19 | 0.31 | 0.39 | 0.18 | | kW | 0.402 | 0.668 | 0.794 | – | 0.963 | Cooling air requirement 3) | m3/s | – | – | – | – | 0.36 | Sound pressure level LpA (1 m) at 50/60 Hz | dB | – | – | – | – | 68/70 | Line supply connection L1, L2, L3 | | 2/M12 | 2/M12 | 2/M12 | 2/M12 | 5/M12 + 4/M16 | - Conductor cross-section, max. (IEC)
| mm2 | 2 ? 150 | 2 ? 150 | 4 ? 240 | 8 ? 240 | 8 ? 240 | PE/GND connection | | PE bar | PE bar | PE bar | PE bar | PE bar | | mm2 | 600 | 600 | 600 | 600 | 600 | - Conductor cross-section, max. (IEC)
| mm2 | 240 | 240 | 240 | 240 | 240 | Degree of protection | | IP20 | IP20 | IP20 | IP20 | IP20 | Dimensions | | | | | | | | mm | 400 | 600 | 600 | 600 | 600 | | mm | 2200 | 2200 | 2200 | 2200 | 2200 | | mm | 600 | 600 | 600 | 600 | 600 | Weight, approx. | | | | | | | | kg | 220 | 230 | 310 | 340 | 450 | | kg | 260 | 310 | 400 | – | 650 | Frame size | | FL | FL | GL | HL | JL |
1) Current demand of contactors/circuit breakers and fans with IP23, IP43, IP54 degree of protection (in combination with Basic Line Modules). 2) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions. 3) For IP23, IP43 or IP54 degree of protection only (in combination with Basic Line Modules). 4) The cabinet height increases by 250 mm with IP21 degree of protection, and by 400 mm with IP23, IP43 and IP54 degrees of protection. Line voltage 500 … 690 V 3 AC | Line Connection Modules |
|---|
| | 6SL3700-0LG41-3AA3 | 6SL3700-0LG41-6AA3 | 6SL3700-0LG42-0BA3 | 6SL3700-0LG42-5BA3 | 6SL3700-0LG43-2BA3 | | | | | Prepared for connection to Line Modules connected in parallel | Infeed/regenerative feedback current | | | | | | | | A | 1250 | 1600 | 2000 | 2500 | 3200 | Current demand | | | | | | | - 24 V DC auxiliary power supply
| A | – | – | – | – | – | | A | 1.07 | 1.07 | 2.14 | 2.14 | 2.14 | | | | | | | | | A | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | | A | 0.06 | 0.06 | 0.06 | 0.06 | 0.06 | Power loss, max. 2) | | | | | | | | | | | | | | | kW | 0.29 | 0.41 | 0.6 | 0.6 | 0.95 | | kW | 1.073 | 1.387 | 2.166 | 2.166 | 2.894 | | | | | | | | | kW | 0.29 | 0.41 | 0.6 | 0.6 | 0.95 | | kW | 1.073 | 1.387 | 2.166 | 2.166 | 2.894 | Cooling air requirement 3) | m3/s | 0.36 | 0.36 | 0.72 | 0.72 | 0.72 | Sound pressure level LpA (1 m) at 50/60 Hz | dB | 68/70 | 68/70 | 70/72 | 70/72 | 70/72 | Line supply connection L1, L2, L3 | | 5/M12 + 4/M16 | 5/M12 + 4/M16 | 5/M12 + 4/M16 | 5/M12 + 4/M16 | 5/M12 + 4/M16 | - Conductor cross-section, max. (IEC)
| mm2 | 8 ? 240 | 8 ? 240 | 10 ? 240 | 10 ? 240 | 10 ? 300 | PE/GND connection | | PE bar | PE bar | PE bar | PE bar | PE bar | | mm2 | 600 | 600 | 600 | 600 | 600 | - Conductor cross-section, max. (IEC)
| mm2 | 240 | 240 | 240 | 240 | 240 | Degree of protection | | IP20 | IP20 | IP20 | IP20 | IP20 | Dimensions | | | | | | | | mm | 600 | 600 | 1000 | 1000 | 1000 | | mm | 2200 | 2200 | 2200 | 2200 | 2200 | | mm | 600 | 600 | 600 | 600 | 600 | Weight, approx. | | | | | | | | kg | 470 | 490 | 600 | 620 | 720 | | kg | 670 | 680 | 980 | 1000 | 1080 | Frame size | | JL | JL | KL | KL | LL |
1) Current demand of contactors/circuit breakers and fans with IP23, IP43, IP54 degree of protection (in combination with Basic Line Modules). 2) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions. 3) For IP23, IP43 or IP54 degree of protection only (in combination with Basic Line Modules). 4) The cabinet height increases by 250 mm with IP21 degree of protection, and by 400 mm with IP23, IP43 and IP54 degrees of protection.
|
|