Line Connection ModulesLine voltage 380 ... 480 V 3 AC | Line Connection Modules |
|---|
| | 6SL3700-0LE32-5AA3 | 6SL3700-0LE34-0AA3 | 6SL3700-0LE36-3AA3 | 6SL3700-0LE38-0AA3 | 6SL3700-0LE41-0AA3 | 6SL3700-0LE41-3AA3 |
|---|
Infeed/regenerative feedback current | | | | | | | | | A | 250 | 380 | 600 | 770 | 1000 | 1250 | Current demand | | | | | | | | | A | – | – | – | – | 1.07 | 1.07 | | | | | | | | | | A | 3.6 | 3.6 | 3.6 | 10.8 | 0.5 | 0.5 | | A | 0.04 | 0.04 | 0.04 | 0.12 | 0.06 | 0.06 | Power loss, max. 2) | | | | | | | | | | | | | | | | | kW | 0.115 | 0.19 | 0.31 | 0.39 | 0.18 | 0.29 | | kW | – | – | 0.675 | 0.74 | – | 0.787 | | | | | | | | | | kW | 0.115 | 0.19 | 0.31 | 0.39 | 0.18 | 0.29 | | kW | – | – | 0.675 | 0.74 | – | 0.787 | Cooling air requirement 3) | m3/s | – | – | – | – | 0.36 | 0.36 | Sound pressure level LpA (1 m) at 50/60 Hz | dB | – | – | – | – | 68/70 | 68/70 | Line supply connection L1, L2, L3 | | 2/M12 | 2/M12 | 2/M12 | 2/M12 | 5/M12 + 4/M16 | 5/M12 + 4/M16 | - Conductor cross section, max. (IEC)
| mm2 | 2 ? 150 | 2 ? 150 | 4 ? 240 | 8 ? 240 | 8 ? 240 | 8 ? 240 | PE/GND connection | | PE bar | PE bar | PE bar | PE bar | PE bar | PE bar | | mm2 | 600 | 600 | 600 | 600 | 600 | 600 | - Conductor cross section, max. (IEC)
| mm2 | 240 | 240 | 240 | 240 | 240 | 240 | Degree of protection | | IP20 | IP20 | IP20 | IP20 | IP20 | IP20 | Dimensions | | | | | | | | | mm | 400 | 400 | 600 | 600 | 600 | 600 | | mm | 2200 | 2200 | 2200 | 2200 | 2200 | 2200 | | mm | 600 | 600 | 600 | 600 | 600 | 600 | Weight, approx. | | | | | | | | | kg | 210 | 230 | 310 | 340 | 450 | 470 | | kg | – | – | 360 | 420 | – | 570 | Frame size | | FL | FL | GL | HL | JL | JL | Short-circuit current rating according to IEC | kA | 50 | 50 | 50 | 50 | 50 | 50 | Minimum short-circuit current 5) | A | 3000 | 3000 | 8000 | 12000 | 2000 | 2500 |
1) Current demand of contactors/circuit breakers and fans with degree of protection IP23, IP43, IP54 (in combination with Basic Line Modules). 2) The specified power loss represents the maximum value at 100% utilization. The value is lower under normal operating conditions. 3) For IP23, IP43 or IP54 degree of protection only (in combination with Basic Line Modules). 4) The cabinet height increases by 250 mm with degree of protection IP21, and by 400 mm with degrees of protection IP23, IP43 and IP54. 5) Current required to ensure reliable tripping of installed protective devices. Line voltage 380 ... 480 V 3 AC | Line Connection Modules |
|---|
| | 6SL3700-0LE41-6AA3 | 6SL3700-0LE42-0AA3 | 6SL3700-0LE42-0BA3 | 6SL3700-0LE42-5BA3 | 6SL3700-0LE43-2BA3 |
|---|
| | | | Prepared for connection to Line Modules connected in parallel |
|---|
Infeed/regenerative feedback current | | | | | | | | A | 1600 | 2000 | 2000 | 2500 | 3200 | Current demand | | | | | | | | A | 1.07 | 2.14 | 2.14 | 2.14 | 2.14 | | | | | | | | | A | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | | A | 0.06 | 0.06 | 0.06 | 0.06 | 0.04 | Power loss, max. 2) | | | | | | | | | | | | | | | kW | 0.41 | 0.6 | 0.6 | 0.95 | 0.95 | | kW | 1.186 | 1.366 | 1.594 | 2.502 | 2.482 | | | | | | | | | kW | 0.41 | 0.6 | 0.6 | 0.95 | 0.95 | | kW | 1.186 | 1.366 | 1.594 | 2.502 | 2.482 | Cooling air requirement 3) | m3/s | 0.36 | 0.72 | 0.72 | 0.72 | 0.72 | Sound pressure level LpA (1 m) at 50/60 Hz | dB | 68/70 | 70/72 | 70/72 | 70/72 | 70/72 | Line supply connection L1, L2, L3 | | 5/M12 + 4/M16 | 5/M12 + 4/M16 | 5/M12 + 4/M16 | 5/M12 + 4/M16 | 5/M12 + 4/M16 | - Conductor cross section, max. (IEC)
| mm2 | 8 ? 240 | 10 ? 240 | 10 ? 240 | 10 ? 240 | 10 ? 300 | PE/GND connection | | PE bar | PE bar | PE bar | PE bar | PE bar | | mm2 | 600 | 600 | 600 | 600 | 600 | - Conductor cross section, max. (IEC)
| mm2 | 240 | 240 | 240 | 240 | 240 | Degree of protection | | IP20 | IP20 | IP20 | IP20 | IP20 | Dimensions | | | | | | | | mm | 600 | 1000 | 1000 | 1000 | 1000 | | mm | 2200 | 2200 | 2200 | 2200 | 2200 | | mm | 600 | 600 | 600 | 600 | 600 | Weight, approx. | | | | | | | | kg | 490 | 600 | 620 | 620 | 720 | | kg | 650 | 760 | 820 | 900 | 1000 | Frame size | | JL | KL | KL | KL | LL | Short-circuit current rating according to IEC | kA | 100 | 100 | 100 | 100 | 100 | Minimum short-circuit current 5) | A | 3200 | 4000 | 4000 | 5000 | 6400 |
1) Current demand of contactors/circuit breakers and fans with degree of protection IP23, IP43, IP54 (in combination with Basic Line Modules). 2) The specified power loss represents the maximum value at 100% utilization. The value is lower under normal operating conditions. 3) For IP23, IP43 or IP54 degree of protection only (in combination with Basic Line Modules). 4) The cabinet height increases by 250 mm with degree of protection IP21, and by 400 mm with degrees of protection IP23, IP43 and IP54. 5) Current required to ensure reliable tripping of installed protective devices. Line voltage 500 ... 690 V 3 AC | Line Connection Modules |
|---|
| | 6SL3700-0LG32-8AA3 | 6SL3700-0LG34-0AA3 | 6SL3700-0LG36-3AA3 | 6SL3700-0LG38-0AA3 | 6SL3700-0LG41-0AA3 |
|---|
Infeed/regenerative feedback current | | | | | | | | A | 280 | 380 | 600 | 770 | 1000 | Current demand | | | | | | | | A | – | – | – | – | 1.07 | | | | | | | | | A | 3.6 | 3.6 | 3.6 | 10.8 | 0.5 | | A | 0.04 | 0.04 | 0.04 | 0.12 | 0.06 | Power loss, max. 2) | | | | | | | | | | | | | | | kW | 0.125 | 0.19 | 0.31 | 0.39 | 0.18 | | kW | 0.402 | 0.668 | 0.794 | – | 0.963 | | | | | | | | | kW | 0.125 | 0.19 | 0.31 | 0.39 | 0.18 | | kW | 0.402 | 0.668 | 0.794 | – | 0.963 | Cooling air requirement 3) | m3/s | – | – | – | – | 0.36 | Sound pressure level LpA (1 m) at 50/60 Hz | dB | – | – | – | – | 68/70 | Line supply connection L1, L2, L3 | | 2/M12 | 2/M12 | 2/M12 | 2/M12 | 5/M12 + 4/M16 | - Conductor cross section, max. (IEC)
| mm2 | 2 ? 150 | 2 ? 150 | 4 ? 240 | 8 ? 240 | 8 ? 240 | PE/GND connection | | PE bar | PE bar | PE bar | PE bar | PE bar | | mm2 | 600 | 600 | 600 | 600 | 600 | - Conductor cross section, max. (IEC)
| mm2 | 240 | 240 | 240 | 240 | 240 | Degree of protection | | IP20 | IP20 | IP20 | IP20 | IP20 | Dimensions | | | | | | | | mm | 400 | 600 | 600 | 600 | 600 | | mm | 2200 | 2200 | 2200 | 2200 | 2200 | | mm | 600 | 600 | 600 | 600 | 600 | Weight, approx. | | | | | | | | kg | 220 | 230 | 310 | 340 | 450 | | kg | 260 | 310 | 400 | – | 650 | Frame size | | FL | FL | GL | HL | JL | Short-circuit current rating according to IEC | kA | 50 | 50 | 50 | 50 | 85 | Minimum short-circuit current 5) | A | 3200 | 3500 | 9000 | 15000 | 2000 |
1) Current demand of contactors/circuit breakers and fans with degree of protection IP23, IP43, IP54 (in combination with Basic Line Modules). 2) The specified power loss represents the maximum value at 100% utilization. The value is lower under normal operating conditions. 3) For IP23, IP43 or IP54 degree of protection only (in combination with Basic Line Modules). 4) The cabinet height increases by 250 mm with degree of protection IP21, and by 400 mm with degrees of protection IP23, IP43 and IP54. 5) Current required to ensure reliable tripping of installed protective devices. Line voltage 500 ... 690 V 3 AC | Line Connection Modules |
|---|
| | 6SL3700-0LG41-3AA3 | 6SL3700-0LG41-6AA3 | 6SL3700-0LG42-0BA3 | 6SL3700-0LG42-5BA3 | 6SL3700-0LG43-2BA3 |
|---|
| | | | Prepared for connection to Line Modules connected in parallel |
|---|
Infeed/regenerative feedback current | | | | | | | | A | 1250 | 1600 | 2000 | 2500 | 3200 | Current demand | | | | | | | | A | 1.07 | 1.07 | 2.14 | 2.14 | 2.14 | | | | | | | | | A | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | | A | 0.06 | 0.06 | 0.06 | 0.06 | 0.06 | Power loss, max. 2) | | | | | | | | | | | | | | | kW | 0.29 | 0.41 | 0.6 | 0.6 | 0.95 | | kW | 1.073 | 1.387 | 2.166 | 2.166 | 2.894 | | | | | | | | | kW | 0.29 | 0.41 | 0.6 | 0.6 | 0.95 | | kW | 1.073 | 1.387 | 2.166 | 2.166 | 2.894 | Cooling air requirement 3) | m3/s | 0.36 | 0.36 | 0.72 | 0.72 | 0.72 | Sound pressure level LpA (1 m) at 50/60 Hz | dB | 68/70 | 68/70 | 70/72 | 70/72 | 70/72 | Line supply connection L1, L2, L3 | | 5/M12 + 4/M16 | 5/M12 + 4/M16 | 5/M12 + 4/M16 | 5/M12 + 4/M16 | 5/M12 + 4/M16 | - Conductor cross section, max. (IEC)
| mm2 | 8 ? 240 | 8 ? 240 | 10 ? 240 | 10 ? 240 | 10 ? 300 | PE/GND connection | | PE bar | PE bar | PE bar | PE bar | PE bar | | mm2 | 600 | 600 | 600 | 600 | 600 | - Conductor cross section, max. (IEC)
| mm2 | 240 | 240 | 240 | 240 | 240 | Degree of protection | | IP20 | IP20 | IP20 | IP20 | IP20 | Dimensions | | | | | | | | mm | 600 | 600 | 1000 | 1000 | 1000 | | mm | 2200 | 2200 | 2200 | 2200 | 2200 | | mm | 600 | 600 | 600 | 600 | 600 | Weight, approx. | | | | | | | | kg | 470 | 490 | 600 | 620 | 720 | | kg | 670 | 680 | 980 | 1000 | 1080 | Frame size | | JL | JL | KL | KL | LL | Short-circuit current rating according to IEC | kA | 85 | 85 | 85 | 85 | 85 | Minimum short-circuit current 5) | A | 2500 | 3200 | 4000 | 5000 | 6400 |
1) Current demand of contactors/circuit breakers and fans with degree of protection IP23, IP43, IP54 (in combination with Basic Line Modules). 2) The specified power loss represents the maximum value at 100% utilization. The value is lower under normal operating conditions. 3) For IP23, IP43 or IP54 degree of protection only (in combination with Basic Line Modules). 4) The cabinet height increases by 250 mm with degree of protection IP21, and by 400 mm with degrees of protection IP23, IP43 and IP54. 5) Current required to ensure reliable tripping of installed protective devices.
|
|