Active field distributors AFD

 

General data

 

Connection of field devices

  • Standard-compliant field devices for PROFIBUS PA or FOUNDATION Fieldbus H1
  • Max. 4 per AFD4
  • Max. 8 per AFD8
  • Max. 31 per fieldbus segment
  • Operating environment up to Zone 2 oder 22; Class I Zone 2/ Division 2
  • The max. current consumption of all fieldbus components of the fieldbus segment is 1 A

Degree of protection

IP66

Voltages, currents, potentials

 

Power supply

Via bus, no auxiliary power necessary

Rated supply voltage, permissible range

16 ... 32 V DC

Reverse polarity protection (together with FDC 157)

Yes

Overvoltage protection

No

Current consumption

 
  • Current consumption at idle

AFD4: 24 mA

AFD8: 34 mA

  • Current consumption with connected field devices

AFD4: 24 mA + total current of all field devices

AFD8: 34 mA + total current of all field devices

  • Additional current consumption of the AFD at end of line (an open main line connection)

30 mA

  • Current consumption at max. power output per spur line

AFD4: 264 mA

AFD8: 514 mA

Power loss

AFD4: Min. 384 mW; max. 3.2 W

AFD8: Min. 544 mW; max. 4.1 W

Grounding

Direct, via grounding rail

Electrical isolation between main line and spur lines

No

Connections, interfaces

 

Main line

 

Number of connections

2

Interfaces

PROFIBUS PA and FOUNDATION Fieldbus H1

Automatic bus terminator

Yes

Spur lines

 

Number of connections

 
  • AFD4

4

  • AFD8

8

Short-circuit-proof

Yes

Intrinsically-safe acc. to FISCO

No

Current Imax (DC) on spur lines 1 to 4 (AFD4) or 1 to 8 (AFD8)

60 mA

Short-circuit current (test current)

6 mA

Debounce logic

Yes

No-load voltage

< 30 V

Current output to field devices

 
  • AFD4

Max. 240 mA

  • AFD8

Max. 480 mA

Status, interrupts, diagnostics

 

Status indicator

Yes

Diagnostics function

Yes

Diagnostics LED

Yes

Interrupts

No

Climatic conditions

 

Permissible operating temperature

-40 ... +70 °C

Permissible storage/transport temperature

-40 ... +85 °C

Relative humidity during operation

Max. 95%

Approvals for potentially explosive atmospheres

 
  • Gas

Zone 2

  • Dust

Zone 22

Dimensions and weight

 

Dimensions (W ? H ? D) in mm (without screwed glands)

 
  • AFD4

220 ? 120 ? 83

  • AFD8

360 ? 120 ? 83

Weight

 
  • AFD4

2 000 g

  • AFD8

3 000 g


Active field distributors AFDiS

 

General data

 

Connection of field devices

  • Standard-compliant field devices for PROFIBUS PA or FOUNDATION Fieldbus H1
  • Max. 6 per AFDiS
  • Max. 31 per fieldbus segment
  • Operating environment up to Zone 1 oder 21; Class I Zone 1
  • The max. current consumption of all fieldbus components of the fieldbus segment is 1 A

Degree of protection

IP66

Voltages, currents, potentials

 

Power supply

Via bus, no auxiliary power necessary

Rated supply voltage, permissible range

16 ... 32 V DC

Reverse polarity protection (together with FDC 157)

Yes; up to 1 A

Overvoltage protection

No

Current consumption

 
  • At 28 V input voltage

? 64 mA + (0.838 ? aggregate current of all field devices)

  • At 24 V input voltage

? 67 mA + (1.008 ? aggregate current of all field devices)

  • At 20 V input voltage

? 74 mA + (1.246 ? aggregate current of all field devices)

Power loss

Min. 1.4 W; max. 5.9 W

Grounding

Direct, via connecting bar

Electrical isolation between main line and spur lines

Yes

Test voltage

2550 V DC, 2 s

Connections, interfaces

 

Main line

 

Number of connections

2

Interfaces

PROFIBUS PA and FOUNDATION Fieldbus H1

Automatic bus terminator

Yes

Spur lines

 

Number of connections

6

Short-circuit proof

Yes

Intrinsically-safe acc. to FISCO

Yes

Current Imax

 
  • on spur line S1

60 mA

  • on spur line S2 to S6

40 mA

  • in total for all field devices

180 mA

Short-circuit current (test current)

5 mA

Debounce logic

Yes

No-load voltage

Max. 15.3 V

Current output to field devices

Max. 260 mA

Status, interrupts, diagnostics

 

Status indicator

Yes

Diagnostics function

Yes

Diagnostics LED

Yes

Interrupts

No

Climatic conditions

 

Permissible operating temperature

-40 ... +70 °C

Permissible storage/transport temperature

-40 ... +85 °C

Relative humidity during operation

Max. 95 %

Approvals for potentially explosive atmospheres

 
  • Gas

Zone 1 and Zone 2

  • Dust

Zone 21 and Zone 22

Dimensions and weight

 

Dimensions (W ? H ? D) in mm

380 ? 85 ? 170

Weight

4 500 g


Active field distributors AFS

 

General data

 

Connection of field devices

  • 1 fieldbus segment with max. 31 field devices
  • Operating environment up to Zone 2 oder 22; Class I Zone 2/ Division 2
  • The max. current consumption of all fieldbus components of the fieldbus segment is 1 A

Degree of protection

IP66

Voltages, currents, potentials

 

Power supply

Via bus, no auxiliary power necessary

Rated supply voltage, permissible range

16 ... 32 V DC

Reverse polarity protection (together with FDC 157)

Yes

Overvoltage protection

No

Current consumption at idle

54 mA

Power loss

Min. 864 mW; max. 2.13 W

Output current for supplying all field devices of the fieldbus segment (for dimensioning the device configuration)

1 A

Grounding

Direct, via connecting bar

Connections, interfaces

 

Main lines to the FDC 157 couplers

 

Number of connections

2

Automatic bus terminator

No

Maximum permissible continuous main line current

1 A

Y-connections for fieldbus line segment

 

Number of connections

1 or 2 (with center feed)

Interfaces

PROFIBUS PA and FOUNDATION Fieldbus H1

Short-circuit proof (together with FDC 157)

Yes

Intrinsically-safe acc. to FISCO

No

Current Imax on Y (limited by FDC 157)

1 A

Debounce logic

No

Continuous output voltage

Max. 32 V

Current output to field devices

Max. 1 A

Status, interrupts, diagnostics

 

Status indicator

Yes

Diagnostics function

Yes

Diagnostics LED

Yes

Interrupts

No

Climatic conditions

 

Permissible operating temperature

-40 ... +70 °C

Permissible storage/transport temperature

-40 ... +85 °C

Relative humidity during operation

Max. 95 %

Approvals for potentially explosive atmospheres

 
  • Gas

Zone 2

  • Dust

Zone 22

Dimensions and weight

 

Dimensions (W ? H ? D) in mm (without screwed glands)

220 ? 120 ? 83

Weight

2 000 g


















skener.ru

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Арматура DENDOR

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Датчики и измерители

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Регуляторы и регистраторы

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Пневматическое оборудование

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Краны и Клапаны

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Измерительные приборы

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Системы беспроводного управления «умный дом»

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Бесконтактные выключатели Конечные выключатели Оптические датчики Энкодеры

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FS - Установка умягчения

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FK - Установка обезжелезивания
Каталог оборудования 2015
Каталог продуктов Siemens Industry Приводная техника Техника автоматизации Системы автоматизации Системы визуализации SIMATIC HMI Системы идентификации Промышленные коммуникации SIMATIC NET Промышленные аппараты управления SIRIUS Промышленные информационные технологии Управление на базе РС Системы управления процессом Система управления процессом SIMATIC PCS 7 Системные компоненты Носитель данных и логистика Системное администрирование Базовые платформы для ES/OS/BATCH/IT Проектирование Операторские станции OS долговременное архивирование Контроль оборудования Системы автоматизации SIMATIC PCS 7 BOX Средства коммуникации Industrial Ethernet PROFINET PROFIBUS Foundation field bus H1 Сетевые переходы FF Active Field Distributors Пассивные компоненты FF Connectivity Pack и Client Access Licences Специальные коммуникации Устройства ввода/вывода Рецептурные процессы SIMATIC Route Control Интеграция средств безопасности в автоматизацию процессов IT Безопасность Технологические компоненты Пакеты обновлений Add-Ons для SIMATIC PCS 7 Датчики Блоки питания Продукты для специальных требований Автоматизация и безопасность зданий Низковольтная коммутационная техника Технология безопасности Системные решения и продукты для отраслей Сервис ... и все, что Вам еще необходимо

  © ООО "СК ЭНЕРГО" 2007-2022
  (4872) 700-366  skenergo@mail.ru
Яндекс.Метрика