Suitable line-side power components are assigned depending on the power rating of the Basic Line Module.
The tables below list recommended components.
Additional information about the line contactors, switch disconnectors, circuit breakers and fuses specified in the table can be found in Catalog IC 10.
Assignment of line-side power components to Basic Line Modules in booksize format
|
Rated power
|
Assignment to Basic Line Module in booksize format
|
Line contactor
|
Output coupling device for line contactor
|
Main circuit breaker
|
|
kW (HP)
|
Typ 6SL3130- 6SL3136-
|
Type
|
Article No.
|
Article No.
|
|
20 (25)
|
1TE22?0AA0
|
3RT1035?…
|
3TX7004?1LB00
|
3LD2504?0TK51
|
|
40 (50)
|
1TE24?0AA0
|
3RT1045?…
|
3TX7004?1LB00
|
3LD2704?0TK51
|
|
100 (125)
|
1TE31?0AA0
|
3RT1056?…
|
3TX7004?1LB00
|
3KA5530?1GE01
|
|
Rated power
|
Assignment to Basic Line Module in booksize format
|
Circuit-breaker
IEC 60947
|
Circuit-breaker
UL489/CSA C22.2 No. 5-02
|
Fuse switch disconnector
|
|
kW (HP)
|
Typ 6SL3130- 6SL3136-
|
Article No.
|
Article No.
|
Article No.
|
|
20 (25)
|
1TE22?0AA0
|
3RV1041?4JA10
|
3VL2506?2KN30-....
|
3NP1123-1CA20
|
|
40 (50)
|
1TE24?0AA0
|
3VL2710?1DC33-....
|
3VL2510?2KN30-....
|
3NP1123-1CA20
|
|
100 (125)
|
1TE31?0AA0
|
3VL3725?1DC36-....
|
3VL3125?2KN30-....
|
3NP1123-1DA20
|
|
Rated power
|
Assignment to Basic Line Module in booksize format
|
Switch disconnector with fuse holders
|
NH fuse (gL/gG)
|
UL/CSA fuse, Class J 1)
Available from: Mersen http://www.ep.mesen.com
|
|
kW (HP)
|
Typ 6SL3130- 6SL3136-
|
Article No.
|
Rated current
|
Size
|
Article No.
|
Rated current
|
Size
|
Reference No.
|
|
20 (25)
|
1TE22?0AA0
|
3KL5230?1GB01
|
63 A
|
000
|
3NA3822
|
60 A
|
29 ? 117
|
AJT60
|
|
40 (50)
|
1TE24?0AA0
|
3KL5230?1GB01
|
100 A
|
000
|
3NA3830
|
100 A
|
29 ? 117
|
AJT100
|
|
100 (125)
|
1TE31?0AA0
|
3KL5730?1GB01
|
250 A
|
1
|
3NA3144
|
250 A
|
54 ? 181
|
AJT250
|
1) Not suitable for 3NP and 3KL switch disconnectors.
|