Suitable line-side power components are assigned depending on the power rating of the Active Line Modules.
The tables below list recommended components.
Additional information about the line contactors, switch disconnectors, circuit breakers and fuses specified in the table can be found in Catalog IC 10.
Assignment of line-side power components to Active Line Modules in booksize format
|
Rated power
|
Assignment to Active Line Module in booksize format
|
Line contactor
|
Output coupling device for line contactor
|
Main circuit breaker
|
Leading auxiliary switch for main switch
|
|
kW (HP)
|
Type 6SL3130- 6SL3131-
|
Type
|
Article No.
|
Article No.
|
Article No.
|
|
16 (18)
|
7TE21?6AA3
|
3RT1035? …
|
3TX7004?1LB00
|
3LD2504?0TK51
|
3LD9200?5B
|
|
36 (40)
|
7TE23?6AA3
|
3RT1045? …
|
3TX7004?1LB00
|
3LD2704?0TK51
|
3LD9200?5B
|
|
55 (60)
|
7TE25?5AA3
|
3RT1054? …
|
3TX7004?1LB00
|
3KA5330?1GE01
|
3KX3552?3EA01
|
|
80 (100)
|
7TE28?0AA3
|
3RT1056? …
|
3TX7004?1LB00
|
3KA5330?1GE01
|
3KX3552?3EA01
|
|
120 (150)
|
7TE31?2AA3
|
3RT1065? …
|
3TX7004?1LB00
|
3KA5730?1GE01
|
3KX3552?3EA01
|
|
Rated power
|
Assignment to Active Line Module in booksize format
|
Circuit breaker
IEC 60947
|
Circuit breaker
UL489/CSA C22.2 No. 5-02
|
Fuse switch disconnector
|
Switch disconnector with fuse holders
|
Leading auxiliary switch for switch disconnector with fuse holders
|
|
kW (HP)
|
Type 6SL3130- 6SL3131- 6SL3136- 6SL3135-
|
Article No.
|
Article No.
|
Article No.
|
Article No.
|
Article No.
|
|
16 (18)
|
7TE21?6AA3
|
3RV1031?4FA10
|
3VL2505?2KN30?....
|
3NP4010?0CH01
|
3KL5030?1GB01
|
3KX3552?3EA01
|
|
36 (40)
|
7TE23?6AA3
|
3RV1041?4LA10
|
3VL2508?2KN30?....
|
3NP4010?0CH01
|
3KL5230?1GB01
|
3KX3552?3EA01
|
|
55 (60)
|
7TE25?5AA3
|
3VL2712?1DC33?....
|
3VL2512?2KN30?....
|
3NP4270?0CA01
|
3KL5530?1GB01
|
3KX3552?3EA01
|
|
80 (100)
|
7TE28?0AA3
|
3VL3720?1DC33?....
|
3VL3117?2KN30?....
|
3NP4270?0CA01
|
3KL5530?1GB01
|
3KX3552?3EA01
|
|
120 (150)
|
7TE31?2AA3
|
3VL3725?1DC36?....
|
3VL3125?2KN30?....
|
3NP5360?0CA00
|
3KL5730?1GB01
|
3KX3552?3EA01
|
|
Rated power
|
Assignment to Active Line Module in booksize format
|
NEOZED fuse (gL/gG)
|
DIAZED fuse (gL/gG)
|
NH fuse (gL/gG)
|
UL/CSA fuse, Class J 1)
Available from: Mersen http://www.ep.mersen.com
|
|
kW (HP)
|
Type 6SL3130- 6SL3131- 6SL3136- 6SL3135-
|
Rated current
|
Size
|
Article No.
|
Rated current
|
Size
|
Article No.
|
Rated current
|
Size
|
Article No.
|
Rated current
|
Size
|
Reference No.
|
|
16 (18)
|
7TE21?6AA3
|
35 A
|
D02
|
5SE2335
|
35 A
|
DIII
|
5SB411
|
35 A
|
000
|
3NA3814
|
35 A
|
27 ? 60
|
AJT35
|
|
36 (40)
|
7TE23?6AA3
|
–
|
–
|
–
|
80 A
|
DIVH
|
5SC211
|
80 A
|
000
|
3NA3824
|
80 A
|
29 ? 117
|
AJT80
|
|
55 (60)
|
7TE25?5AA3
|
–
|
–
|
–
|
–
|
–
|
–
|
125 A
|
1
|
3NA3132
|
125 A
|
41 ? 146
|
AJT125
|
|
80 (100)
|
7TE28?0AA3
|
–
|
–
|
–
|
–
|
–
|
–
|
160 A
|
1
|
3NA3136
|
175 A
|
41 ? 146
|
AJT175
|
|
120 (150)
|
7TE31?2AA3
|
–
|
–
|
–
|
–
|
–
|
–
|
250 A
|
1
|
3NA3144
|
250 A
|
54 ? 181
|
AJT250
|
1) Not suitable for 3NP and 3KL switch disconnectors.
|